10 / 11
Screen setting
System setting
Range and CT setting
Measurement Adjust
Help page
*Please use password to enter system settings, the password is ”
2010
”;
* During setting, long press “
” key or “
” key can achieve rapid adjustment.
Frequently Asked Questions
No.
Problems
Solutions
Notes
1
Switch on when the icon
is displayed in
the lower right corner of the screen, and
switch off when the icon
is displayed in
the lower right corner of the screen.
The pins of magnetic latching relay are connected reversely. Please switch 5 and 6 pins for rewiring.
Only for external
relay version
2
When powered on, switch is off and the icon
is displayed in the lower right corner of
the screen.
Long press the ”
” key for three seconds to turn on the switch, or enter the "Switch settings" page,
and set the switch status to "On". The monitor will automatically turn on the switch after the next
power on.
Only for external
relay version
3
Switch is off during working, the icon
will
be displayed, or the icon
will flash or the
icon
will flash.
The monitor has entered the output protection state. Check whether the voltage, current and power
exceed the value of output protection setting. If necessary, change the corresponding output
protection setting value or cancel the corresponding output protection setting, or check the "Launch
overload" check box.
Only for external
relay version
4
During working, the monitor sounds and the
icon
in the lower right corner of the
screen flashes.
The monitor has entered the alarm state. Check whether the voltage, current and power exceed the
alarm setting value. If necessary, change the corresponding alarm setting value or cancel the
corresponding alarm setting.
Considerations
1.
The machine cannot work in hot and humid environment, please use it in normal temperature and humidity.
2.
The working voltage of the machine is AC85V~AC265V.
3.
The working current cannot be greater than the maximum current of current transformer.
4.
The current transformer cannot be open circuit, otherwise it will output high voltage, which will cause safety problems.
5.
Do not let the machine expose to the dust, corrosive gases or other harmful substances in the environment when use and keep.
6.
Must power-off operation be carried out during installation, and live operation is prohibited to avoid electric shock.
7.
If the machine failed working, don not open the machine and replace parts by yourself to avoid electric shock, please contact the manufacturer.
Legal Notices