Power Supplies and Ringing Generators
System Installation
2.4.1
System Power (Redundancy)
Note:
The system always requires a 120/240 VAC or -48 VDC Power Supply. For backup,
you may add a second identical power supply. The shelf can also be power off of one
AC supply and one DC supply.
2.4.2
-48V Talk Battery Requirements
Talk battery is required whenever you have voice user cards in the system, unless (a) all of
those are E&M cards and are used in the Transmission-Only mode, or (b) Type 1 E&M
signaling is used. A -48 VDC power source is also required for use with the Alarm Cards,
OCU-DP cards, and to provide sealing current for BRI cards. The -48 VDC talk battery can
be provided from an external source, or by using a 115 VAC to -48 VDC Converter. This unit
is only available for 115 VAC sources. A similar AC-to-DC Converter is also available for use
with either 115 or 220 VAC.
2.4.3
Setting the U.S./European Configuration Jumper
Before inserting any cards into the chassis, set its JP1 jumper for either the U.S. or European
configuration. This jumper is shown in Figure 2-3; it is on the resource card backplane and is
accessible from the chassis front. The default jumper setting is US (for systems in the U.S. and
Canada). To change the chassis electrical configuration for European compliance (EUR),
move the jumper to pins 2 and 3.
Figure 2-3. JP1 Jumper Settings
Also be sure to set the jumper on the system resource cards and external alarm cards to agree
with the above setting for the chassis. Refer to the associated chapters in this guide for
information on those card jumpers.
1
2
3
JP1
EU
R
/US
1
2
3
JP1
EU
R
/US
U.S. Configuration
European Configuration
Содержание IMACS 8000
Страница 20: ...xviii Table of Contents Model No Running Head Table of Contents...
Страница 38: ...1 6 Reference Guide Model No Running Head Customer Service and Ordering Information What s New...
Страница 58: ...2 20 Reference Guide Model No Running Head Installing the Other Plug In Cards System Installation...
Страница 82: ...4 18 Reference Guide Model No Running Head PWE IP Uplink Server 8000 PWE Applications...
Страница 210: ...6 12 Reference Guide Model No Running Head Performance Monitoring System Testing and Diagnostics...
Страница 270: ...7 60 System Cards Model No Running Head CPU Card Specifications CPU Card...
Страница 300: ...8 30 System Cards Model No Running Head Interface Card Specifications Interface Card...
Страница 337: ...System Cards 9 37 WAN Card WAN Card User Screens and Settings Figure 9 21 T1 WAN Cross Connect Screen display only...
Страница 352: ...9 52 System Cards Model No Running Head WAN Card Specifications WAN Card...
Страница 360: ...10 8 System Cards Model No Running Head Alarm Card Troubleshooting Alarm Cards...
Страница 382: ...11 22 Voice Cards Model No Running Head E M Card Specifications E M Card...
Страница 454: ...14 34 Data Cards Model No Running Head HSU Card User Screens and Settings HSU Card Figure 14 16 HSU Broadcast Screen...
Страница 474: ...14 54 Data Cards Model No Running Head HSU Card Specifications HSU Card...
Страница 484: ...15 10 Data Cards Model No Running Head OHSU Card Specification OHSU 4P Card...
Страница 536: ...18 8 Data Cards Model No Running Head DS0 DP Card Specifications DS0 DP Card...
Страница 596: ...21 38 Server Cards Model No Running Head IPR 4 Server Card Specifications IPR 4 Router Card...
Страница 614: ...22 18 Server Cards Model No Running Head ACS MCC Card Troubleshooting MCC Card...
Страница 644: ...24 18 Server Cards Model No Running Head PWE Card Troubleshooting PWE Card...
Страница 659: ...Reference Guide A 15 A 4 2 External Talk Battery Fuses Manufacturer Part NumberA3 Little Fuse 218 005 Bussman GDC 5...
Страница 674: ...A 30 Reference Guide Model No Running Head...
Страница 729: ...Pin Outs C 31 C 8 HSU Cards...
Страница 752: ...C 54 Pin Outs Model No Running Head...