Zeta ZT-CP4/WP Скачать руководство пользователя страница 2

TSD-ZT-CP4-WP-00B - Rev. date: 2023-01-10 09:31:13

Reset Instructions

Dimensions

Mounting dimensions

30.00

73.00

19.00

M20X1.50

.

88.00

87.00

Turn clockwise to reset

70.00

50.00

Ø3.50

3.50

*Below minimum voltage LED current is lower than 5 mA

Maximum Voltage

30 Volt

Minimum Voltage*

5,0 Volt if LED with R1 is chosen

6,0 Volt if LED with R2 is chosen

Current Rating (non-operated)

0 mA

Current Rating (operated)

19 mA @12 Volt - R1
13 mA @12 Volt - R2
45 mA @24 Volt - R1
31 mA @24 Volt - R2

Technical Specifications

Cable Termination

Operating Temperature

Humidity

IP rating

Material

0,5 - 2,5 mm

2

-30 / +70 °C

0 - 95 %

67

ABS/Policarbonate/PA6+glass fiber

EN 54-11:2001+ A1:2005

Conventional Type A

Outdoor Manual Call Point

Zeta CP4/WP 

Conventional Weatherproof 

Manual Call Point

Red series only

2831

21

0832

21

21

2831-CPR-F4661

Detection House, 72-78 Morfa Road Swansea, SA1 2EN

Telephone: +44 (0)1792 455 175

Email: [email protected]

Zeta Alarms Limited

21

0832-UKCA-CPR-F1086

Cable Gland

M20 (6-12mm cable) IP67/IP68