5
Technical specifications
General description:
A stationary gas detection system consists of a detector (transmitter) and a central controller. The
detector and the controller are connected with a cable. The detector converts the gas concentration into
an electric measurement signal and transmits it via the cable for processing to the controller.
Gas detectors GS-220.BC.V.ZETA are intended for detection of explosive and toxic gases. They are
suitable for detection of different gases depending on the gas detection element.
Measuring method:
The following measuring methods are used:
1.
Catalytic sensors for measurement of explosive gases.
2.
Electrochemical sensors for toxic gases.
3.
Infrared sensors for CO2.
4.
Semiconductor sensors for refrigerant gases.
Table. 1
DETECTED GASES
See Table. Ordering codes
Gas feed
Diffusion
POWER SUPPLY
Working voltage
12
–
30 VDC
Power Consumption
3W
OUTPUT SIGNAL
GS-220.BC.V.ZETA
4
–
20mA
ENVIRONMENTLE CONDITIONS
Working temperature
-20 - + 50
ᵒ
C
Humidity range
10
–
90% R.H.
Atmospheric pressure range
800
–
1100 hPa
MECHANICAL
Dimensions
155 x 120 x 48mm
Weight
0,320kg
Enclosure material
Aluminium
Ingress protection
IP65
Cable connection
Cable gland(s) M16 (M20)
CERTIFICATION
Conformity mark
CE
ATEX certification
ATEX II 2G Ex d (ib) ma IIC T4 Gb
ATEX II 2D Ex tb (ib) ma IIIC T135oC IP65 Db