INFINITY 8 INSTALLATION MANUAL 

Approved Document No. GLT-201-7-1 

 

PAGE 4 

Issue: 1.6      Author:  NRPJ          Date: 27/7/2012 

2. FIRST FIX 

All wiring must be installed to meet BS5839: Pt1: 2002 and BS 7671 (Wiring Regs) standards.  Other National standards of fire 
alarm system installation should be adhered to where applicable. 

2.1 RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS 

Screened cables should be used throughout the installation to help shield the Panel from outside interference and ensure EMC 
compatibility. 

The two categories of cable according to BS5839: Pt1: 2002, Clause 26 “Fire Detection and Alarm Systems for Buildings (Code of 
Practice for System Design, Installation and Servicing)” are: 

 

Standard fire resisting cable – to PH30 classification of EN 50200 

 

Enhanced fire resisting cable – to PH120 classification of EN 50200 

(Note that all cables should be at least 1mm2 cross section 

On the Infinity Panel the general recommendation would be to use standard fire resistant cable, such as Fire Defence, Firetuff™ , 
FP200 or an equivalent. These cables are screened, and will provide good ECM shielding when properly grounded at the panel.  
Certain system specifications may demand the use of a particular type of cable and due regard should be paid to this fact. 

Depending on the environment, the cables may need mechanical protection (such as a conduit). 

2.2 MAINS WIRING RECOMMENDATIONS 

The Mains supply to the FACP is fixed wiring, using 

Fire resisting

 3-core cable (Between 1 mm² and 2.5mm²) or a suitable 3-

conductor system, fed from an isolating double pole switch fused spur, fused at 3A. This should be secure from unauthorised 
operation and be marked ‘FIRE ALARM: DO NOT SWITCH OFF’.  The supply must be exclusive to the Fire Panel.  

For information on how to connect Mains to the Panel’s Power Supply PCB, see page 8. 

Also refer to rating information inside the FACP. 

2.3 DETECTOR CIRCUIT WIRING DIAGRAM 

The Infinity comes with one, two, four, six or eight Detection circuits (Zones).  A maximum of 32 devices (i.e. smoke detectors, heat 
detectors, or Manual Call Points) can be fitted to each circuit. ALL DEVICES MUST BE POLARISED. 

Typical detector circuit wiring:  

An End of Line diode (provided in the Panel) must be connected across the terminals of the last device on each circuit to allow the 
wiring to be monitored. It is polarity sensitive, and connected cathode (STRIPE) to +ve 

Using detector bases with continuity diodes fitted will allow all devices, including Manual Call Points to remain operational if a 
detector is removed from its base. 

Old Manual call points, which just cause a short circuit, are not directly compatible, as they would cause a short circuit fault. Fitting 
a 470R resistor in line with the call point will allow it to work. (Wired in a similar way to non-polarised bells shown at the foot of this 

Содержание INFINITY 8

Страница 1: ...INFINITY 8 INSTALLATION MANUAL Approved Document No GLT 201 7 1 Issue 1 6 Author NRPJ Date 27 7 2012 FIRE ALARM CONTROL PANEL INSTALLATION MANUAL...

Страница 2: ...S 5 FIELD DEVICE TERMINATION 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 5 2 AUXILIARY OUTPUT TERMINATIONS 6 SOUNDER ACTIVATION DELAY 6 1 DECIDING TO USE A DELAY 6 2 TO SET A DELAY 6 3 WI...

Страница 3: ...wer failure It has the ability to disable any zone or the sounder circuits It has a one man test mode which resets the Zone in test after 5 seconds EN54 option with requirements It has a sounder delay...

Страница 4: ...taller Engineer Open enclosure Connect wiring during install Battery check during Maintenance Set configuration switches 4 Authorised Service Engineer Open enclosure PC programming software Update pan...

Страница 5: ...d mechanical protection such as a conduit 2 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed wiring using Fire resisting 3 core cable Between 1 mm and 2 5mm or a suitable 3 conduct...

Страница 6: ...of old mechanical bell or a relay are used then a diode will have to be placed in line with the device to enable fault monitoring They may also need a back EMF protection diode 2 5 AUXILIARY OUTPUT W...

Страница 7: ...AL Approved Document No GLT 201 7 1 PAGE 6 Issue 1 6 Author NRPJ Date 27 7 2012 The termination for the above inputs must be as indicated on the main PCB See page 15 The Earthing of the cable screens...

Страница 8: ...x If a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via...

Страница 9: ...WER 4 1 CONNECTING THE MAINS POWER Figure 3 Power Supply PCB layout and Mains connection details Figure 3 4 2 CONNECTING THE BATTERIES Figure 4 Battery location and connection details CAUTION RISK OF...

Страница 10: ...l screens should be fed through the gland to make electrical contact with it and be terminated at the brass earthing strip as shown below see Figure 6 For detailed detector and alarm circuit wiring di...

Страница 11: ...he number with the keypad 0 minutes type nothing 9 minutes type 81 10 minutes type 82 Press 5 The panel will flash a confirmation of the selected delay 6 Press 3 times to exit access level 3 6 3 WIRIN...

Страница 12: ...isable one zone at a time 1 Enter access code default 1245 and press 2 Press for 3 seconds 3 Type the number of the zone you want to disable If you wish to disable the sounders press 4 Press to disabl...

Страница 13: ...not in test mode at this point 4 Press to start test mode The Zone test LEDs will be flashing with a pattern 12 flashes then a pause repeated The zone is now in test mode 5 To set a different zone int...

Страница 14: ...ase that is not making the connection c A short circuit on a zone could be caused by the end of line diode being fitted backwards d Check that the detectors are compatible with this FACP Note that som...

Страница 15: ...nect the earth screens one at a time to determine the problem line Note connecting other equipment e g an oscilloscope to the panel can give an earth fault 9 5 SOUNDER FAULTS Similar to the zone fault...

Страница 16: ...00005 Amp 50 A Optical Detector 0 0001 Amp 100 A Typical Example A system comprises of 20 ionisation detectors 14 bells and the required standby is 24 hours It will need to operate in alarm for hour...

Страница 17: ...bells 10 SND 2 Connect to sounder circuit 2 sirens bells 11 SND 3 Connect to sounder circuit 3 sirens bells 12 SND 4 Connect to sounder circuit 4 sirens bells 13 FAULT RELAY NC CM NO Normally powered...

Страница 18: ...TAGE 22 5V DC NOMINAL SOUNDER ALARM OUTPUTS 2 x 150mA 24V DC 1 2 zone panel 4 x 150mA 24V DC 4 6 8 zone panel AUXILIARY FAULT OUTPUT 1 x RELAY SELV 1A MAX AUXILIARY FIRE OUTPUT 1 x RELAY SELV 1A MAX N...

Страница 19: ...e condition Giving 2 fire relays Switch 8 ON Makes the last zone on the panel a call point zone alarms from that zone not delayed Note The above options my not comply with local regulations Please che...

Отзывы: