background image

INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624

   

 

Approved Document No: GLT2-211-7-2 

 

  

PAGE 22

 

Issue 1.00         Author: NRPJ      Date: 23/1/2013 

Design Certificate 

(Page 1 of 2) 

 

Certificate of DESIGN for the Infinity ID2 Fire Alarm System installed at: 
 
ADDRESS: 

 

 

 

 
I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the design of 
the fire alarm system, particulars of which are set out below, CERTIFY that the said design for which I/we 
have been responsible complies to the best of my/our knowledge and belief with the recommendations of 
section 2 of BS 5839-1:2002 for the system category described below, except for the variations, if any, 
stated in this certificate 
 
Name (

Block Letters

):   

Position:   

Signature: 

 

Date: 

 

For & on behalf of: 

 

Address 

 

 

 

 
The extent of liability of the signatory is limited to the system described below. 
 
System Category (see BS 5839-1:2002, Clause 5): 
 
 
Variations from the recommendations of section 2 of BS 5839-1:2002 (see Clause 7):) 
 
 
 
 
 
 
Extent of system covered by this certificate: 
 
 
 
 
 
 
Brief description of areas protected (not applicable for Category M, L1 or P1 systems): 
 
 
 
 
 
 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание ID2/2/M

Страница 1: ...sions PANEL 0 X R8629 LOOP 0 J R624 Approved Document No GLT2 211 7 2 PAGE 0 Issue 1 00 Author NRPJ Date 23 1 2013 INTELLIGENT 2 WIRE FIRE DETECTION SYSTEM WITH ID TECHNOLOGY USER MANUAL MAINTENANCE GUIDE LOG BOOK www acornfiresecurity com www acornfiresecurity com ...

Страница 2: ...E LEDS MEAN 6 5 THE FIRE CONDITION 7 5 1 HOW THE SIMPLICITY INDICATES AN ALARM 7 5 2 TO TURN OFF THE ALARM SOUNDERS 7 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 7 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING 7 5 5 RESETTING THE PANEL 7 6 THE FAULT CONDITION 8 6 1 DIFFERENT TYPES OF FAULT 8 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS 9 6 3 OTHER LED INDICATIO...

Страница 3: ... cooking food exhaust smoke excessive dust etc can all activate a smoke detector If anything is found try to clear the room by opening a window If a fire is discovered call the fire brigade To reset the panel press the reset button If the panel goes back into alarm silence the sounders and call the engineer WHAT TO DO IF THE FIRE ALARM PANEL SHOWS A FAULT YELLOW LED Write down the LCD reading and ...

Страница 4: ...tinguished if it can be safely tackled or the local fire brigade called according to the company evacuation procedure 2 An Alarm can be raised from Smoke or Heat Detectors or manually by a person operating a Manual Call Point 3 To split the building into Zones each covering a different area of the building This will indicate which area of the system is giving the alarm or fault 4 To start its soun...

Страница 5: ...ts especially Call point elements held on site 47 2 j 1 2 11 In the event of a prealarm determine the cause take appropriate action predetermined fire routine if the cause is the start of a fire arrange maintenance if the cause is a contaminated detector head 47 3 With the Infinity ID2 Fire Alarm Panel we recommend the following tests are carried out Daily Inspection Check that the green Power LED...

Страница 6: ...us The General Test button is used to control the one man test mode The General Disablement button is used to select disablements The numeric section is for entering access codes and for entering device addresses ID using the mobile phone type alpha numeric keys 4 3 IN THE EVENT OF AN ALARM After the site has been deemed safe for return to return the panel to normal 1 Enter access code 123 access ...

Страница 7: ...t button and entering the test code This is a factory preset code which cannot be changed Here the user can put any of the zones or sounder circuits into test mode Turn the keyswitch back to the off position to exit this mode 4 5 CHECKING THE PANELS INDICATION LEDS Enter access code 123 then press the LED test button All the LEDs on the front panel will light for 3 seconds and the panel s internal...

Страница 8: ...so be silenced by pressing the Silence Buzzer button 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE If another detection Zone is activated after the Alarm Sounders have been silenced the panel will Restart the sounders Light the Zone Fire LED s for any new Zone s in alarm Keep the light s for the previous Zone s in fire and General Fire lit 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E ...

Страница 9: ... removed 3 Battery low 4 Battery High Impedance Earth Fault 1 Earth Fault Positive 2 Earth Fault Negative Sounder Fault 1 Sounder Open Circuit 2 Sounder Short Circuit 3 Faults on an addressable sounder will be indicated as a device fault System Fault The System Fault LED lights if the Panel s micro processor has encountered a problem and has rebooted This does not occur during normal operation typ...

Страница 10: ...this Manual Take appropriate action to correct the fault Usually by contacting the service engineer On the Infinity ID2 panel the fault indications except system fault are non latching That is when the fault has been cleared the fault indication will turn off When all faults have been cleared the panel will return to its quiescent normal condition When a fault has been rectified the indicator ligh...

Страница 11: ...IDE LOG BOOK Software Versions PANEL 0 X R8629 LOOP 0 J R624 Approved Document No GLT2 211 7 2 PAGE 10 Issue 1 00 Author NRPJ Date 23 1 2013 6 3 OTHER LED INDICATIONS DISABLEMENTS TEST MODE www acornfiresecurity com www acornfiresecurity com ...

Страница 12: ...ISABLEMENT ZONE 1 The panel is now in SELECT DISABLEMENT MODE 5 Press NEXT BUTTON until the required zone or sounder circuit is DISPLAYED Press ENTER to confirm the disablement The screen will now show that the zone is disabled and the GENERAL DISABLEMENTLED will light This section is now disabled Zone Disablement Zone 1 Zone Enabled Disabled Devices 0 Zone Disablement Zone 3 Zone Disabled Disable...

Страница 13: ... INFORMATION SOUNDER CIRCUIT SOUNDER CIRCUIT DESCRIPTION A brief description of all the rooms and areas contained in each zone QTY SNDR QTY BELL QTY STROBE 1 2 OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED AUXILIARY OUTPUT YES NO FAULT OUTPUT YES NO ADDITIONAL INFORMATION Any additional information the User needs to know about should be inserted into this box incl...

Страница 14: ...ription Verify Sndr Flsh ID Type Description Verify Sndr Flsh ID Type Description Verify Sndr Flsh Zone 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Zone 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Zone 3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Zone 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Zone 5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Zone 6 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Zone 7 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 ...

Страница 15: ...ing work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that fire alarm events should be subdivided recorded on separate sheets in the log book The event categories are Maintenance work False alarms where the sounders have activated with no signs of a fire Any...

Страница 16: ...L 0 X R8629 LOOP 0 J R624 Approved Document No GLT2 211 7 2 PAGE 15 Issue 1 00 Author NRPJ Date 23 1 2013 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SIGNED www acornfiresecurity com www acornfiresecurity com ...

Страница 17: ... R8629 LOOP 0 J R624 Approved Document No GLT2 211 7 2 PAGE 16 Issue 1 00 Author NRPJ Date 23 1 2013 MAINTENANCE WORK CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SIGNED www acornfiresecurity com www acornfiresecurity com ...

Страница 18: ... GLT2 211 7 2 PAGE 17 Issue 1 00 Author NRPJ Date 23 1 2013 UNWANTED FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN CE FINDINGS CATEGORY OF FALSE ALARM FURTHER ACTION REQUIRED SIGNED www acornfiresecurity com www acornfiresecurity com ...

Страница 19: ... 211 7 2 PAGE 18 Issue 1 00 Author NRPJ Date 23 1 2013 UNWANTED FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN CE FINDINGS CATEGORY OF FALSE ALARM FURTHER ACTION REQUIRED SIGNED www acornfiresecurity com www acornfiresecurity com ...

Страница 20: ...proved Document No GLT2 211 7 2 PAGE 19 Issue 1 00 Author NRPJ Date 23 1 2013 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE COMPLETED INITIALS www acornfiresecurity com www acornfiresecurity com ...

Страница 21: ...d Document No GLT2 211 7 2 PAGE 20 Issue 1 00 Author NRPJ Date 23 1 2013 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE COMPLETED INITIALS www acornfiresecurity com www acornfiresecurity com ...

Страница 22: ...V All call points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for compliance with the recommendations of BS5839 Pt1 2002 clause 16 2 Any deviations from BS5839 Pt1 clause 7 2 should be listed in the Certificate of Installation Commissioning The Certificate of Instal...

Страница 23: ...hich I we have been responsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 2002 for the system category described below except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of Address The extent of liability of the signatory is limited to the system described below System Cat...

Страница 24: ...guidance has been provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commissioning be undertaken in accordance with the recommendations of section 4 and section 5 of BS 5839 1 2002 respectively SOAK TEST In accordance with the recommendations of clause 35 2 6 of BS 5839 1 20...

Страница 25: ...ribed below and with the recommendations of BS5839 1 2002 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of Address The extent of liability of the signatory is limited to the system described below Extent of the installation work covered by this certificate Specification against which the system was installed Variations from the...

Страница 26: ...see clause 7 All equipment operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with the recommendations of 39 2 c of BS 5839 1 2002 The system performs as required by the specifications prepared by Taking into account the guidance contained in section 3 of BS 5839 1 2002 I we have no...

Страница 27: ... by this certificate All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre operates correctly Delete if not applicable The following documents have been provided to the purchaser or user As fitted drawings Operating and maintenance instructions Certificates of Design Installat...

Отзывы: