Doc: GLT-211-7-3 

Iss: 2.0 

Date 03/08/2016 

 

Introduction 

This guide is designed to be used by competent persons who are familiar with the installation and 

setting up of fire alarm systems.  

This guide covers the basic setup of the ID2 panel and devices which connect to the system 

(detectors, call points, modules and sounders).  

One important thing to remember with the ID2 system is that the devices address/ID will dictate 

which zone it will be seen in (See below chart). 

Zone 

Switch 5,6,7,8 

Available IDs 

Zone 

Switch 5,6,7,8 

Available IDs 

ON,ON,ON,ON 

ID 1-15 

OFF,ON,ON,ON 

ID 1-15 

ON,OFF,ON,ON 

ID 1-15 

OFF,OFF,ON,ON 

ID 1-15 

ON,ON,OFF,ON 

ID 1-15 

OFF,ON,OFF,ON 

ID 1-15 

ON,OFF,OFF,ON 

ID 1-15 

OFF,OFF,OFF,ON 

ID 1-14 

Note: Only 15 devices per zone (zone 8 only 14 devices) 

The panel is available in 2,4 or 8 zone sizes. The panel can be wired as radial circuits, or as a loop. In 

loop mode, the number of addresses available matches the panel zone size. 

Installation Steps. 

1.

 

The panel should be mounted to a firm surface and powered to check it sits without any 

issues  

2.

 

All cables must be check to make sure there are no shorts or open circuits.  

3.

 

Address all the devices. 

All products will come with their own wiring instructions. This should be used when connecting a 

product. But the wiring info for the most common item (Detector) is shown below.

 

 

 

 

 
 

 

 

 

 

The panel is supplied set to 

radial

 wiring by default. To set the panel to use 

loop

 wiring go to 

Engineer Menu / Misc / Topology , and set to Loop with Prev/Next buttons 

 

The connection for the detectors  
bases are made as follows:  
Terminal L1IN is –ve (Blue)  
Terminal L2 is +ve (Brown) 
These are the only two  
connections required. 
 