Document No: GLT-207-7-2
Issue No: 007
Author: NRP Jones
Date: 11/01/2018
Page 5
ADDRESSABLE XTRATONE SOUNDER BEACON - INSTALLATION MANUAL
Technical Data
Model
MKII-AXT/R
MKII-AXT/W
MKII-AXTB/R
MKII-AXTB/W
Part Number
42-610A
42-611A
42-617
42-618
Colour
Red
White
Red
White
Flash Colour
N/A
White flash
Flash Rate
N/A
0.33 - 1.5 Hz (depends on setting)
Flasher Coverage
N/A
W-3.1-9.1 for setting 1
Sounder Output
(Anechoic)
80.4dB @ 1m
Operating Voltage
17-28 V
Quiescent Current
1.5 mA
Alarm Current
5.4 mA max
19-44 mA (depends on setting)
Sounder Type
Type A (Indoor use)
Operating Temperature
-10
o
C to +55
o
C
Minimum Continuous
Operating Temperature
0
o
C
Max Humidity
95% RH Non Condensing
IP Rating
IP21C
Size (H x W x D in mm )
105 x 105 x 56 (105 x 105 x 89)
105 x 105 x 56 (105 x 105 x 89)
Weight (with Back Box)
200g
210g
Minimum sound output 66.3dB
Troubleshooting
Problem
Possible Cause
Device Not Seen By Panel Check the device is addressed within the range of the panel :-
1 To 250 for a Quatro / 1 To 126 for a Simplicity Plus
Other panels – check panel manuals for info
Check that loop is connected with correct polarity
Check that sounder flying leads have been connected to the backbox.
Check the panel is running the Zeta Fyreye MkII protocol
Sounder Is Not Operating Check panel`s actions (cause & effect) programming is correct.
Flasher is not operating
Check that the flasher LED wires have not been disconnected
Check panel`s actions (cause & effect) programming is correct.
Can Not Start An
Individual Sounder
Check whether triggering individual sounders is supported by the
control panel
Check the cause & effect programming to see if common operation
has been selected