FYREYE II SANDWICH SOUNDER - INSTALLATION MANUAL

Technical Data

Model

MKII-SSB

Part Number

80-224

Operating Voltage

17 – 28V DC

Quiescent Current

650µA

Alarm Current

5.5mA

Sound Output

Aprox 85 dB (Depending on tone – See Table)

Min 75dB

Minimum Operating Temperature 0°C
Operating Temperature

-10°C to +55°C 

Max Humidity

95% RH Non Condensing

Ip Rating

IP 21C

Size

100mm dia x 40mm (Without Detector)

Weight

160g

For further information, including directional A-weighted sound output information 

please see doc MKII-SSB-OD, available from the manufacturer

Troubleshooting

Symptom

Probable Cause

Device Not Seen By Panel

This is normal. This is a platform sounder and does not 

reply to the panel.

Detector Fitted To Base 

Not Seen

Check that a Fyreye II detector is used. Previous versions of 

detector will not work on a Fyreye II loop.

Check that the wiring to the common base is correct (+ve = 

L2, -ve = L1 IN)

Sounder Is Not Operating

Check if Platform sounder has been disabled for the 

address of the detector fitted.

Check that the wiring to the common base is correct (+ve = 

L2, -ve = L1 IN)

Check Panel`s actions (Cause & Effect) programming is 

correct.

Can Not Start An 

Individual Sounder

Check whether triggering individual sounders is supported 

by the control panel.

Check the Cause & Effect programming to see if common 

sounder operation has been selected.

Содержание MKII-AHR

Страница 1: ...e Fyreye II Detector All loop cables are terminated at the detector base with the sounder base clipping onto the common base The sounder should then be secured with it s grub screw to prevent unauthorised removal The sounder does not need to be addressed If it is to be started individually it is controlled by the detector s remote LED output The sounder does not need to be addressed If it is to be...

Страница 2: ... tone No Tone Description Pattern Frequency Rate dBA Reverb Chamber 0 BS Fire Default Zeta tone Alternating 800 970 1Hz 500ms 500ms 96 2dB 1 BS Fire Alternating 800 970 2Hz 250ms 250ms 95 2dB 2 BS Fire Sweep 800 to 970 1Hz 1 per second 98 2dB 3 BS Fire Sweep 800 to 970 7Hz 7 per second 99 2dB 4 BS Fire Sweep 800 to 970 50Hz 50 per second 99 2dB 5 BS Fire Alternating 510 610 1Hz 500mS 500mS 100 2dB...

Страница 3: ...from the manufacturer Troubleshooting Symptom Probable Cause Device Not Seen By Panel This is normal This is a platform sounder and does not reply to the panel Detector Fitted To Base Not Seen Check that a Fyreye II detector is used Previous versions of detector will not work on a Fyreye II loop Check that the wiring to the common base is correct ve L2 ve L1 IN Sounder Is Not Operating Check if Pl...

Страница 4: ... this unit should not be disposed of in a refuse bin It should be taken to a local reprocessing site as per the guidelines of the WEEE directive for correct disposal 330r 02 0832 Zeta Alarms Limited 72 78 Morfa Road Swansea SA1 2EN 14 0832 CPR F0110 EN54 3 2001 A1 2002 A2 2006 Alarm Devices Sounder Type A For Indoor Use MKII SSB Other Technical Data See Doc MKII SS Product file held by the manufac...

Отзывы: