FYREYE II SANDWICH SOUNDER - INSTALLATION MANUAL

FYREYE II SANDWICH SOUNDER INSTALLATION MANUAL

Description

The Fyreye II Sandwich sounder base is a platform 

sounder that works with the Zeta Fyreye II 

protocol. The sounder can be triggered from 

it`s detectors remote LED output, allowing the 

sounders to be triggered individually. It can 

also be triggered using the Protocol`s common 

sounder group command, meaning that it can be 

triggered even if it`s detector has been removed.

Connections & Address Setting

This sounder has been designed to be sandwiched 

between a common base and an addressable 

Fyreye II Detector. All loop cables are terminated 

at the detector base, with the sounder base 

clipping onto the common base. The sounder 

should then be secured with it`s grub screw to 

prevent unauthorised removal. The sounder does 

not need to be addressed. If it is to be started 

individually, it is controlled by the detector`s 

remote LED output.

The sounder does not need to be addressed. If it 

is to be started individually, it is controlled by the 

detector`s remote LED output.

Compatible Devices & Bases

Part Number Model

Description

80-210

MKII-AOP

Fyreye MKII Addressable Optical Smoke Detector

80-212

MKII-AHR

Fyreye MKII Addressable Rate of Rise Heat Detector (A1R)

80-214

MKII-AHF

Fyreye MKII Addressable Fixed Heat Detector (A2S)

80-216

MKII-AOH

Fyreye MKII Addressable Opto-heat Detector

80-220

MKII-CB

Fyreye MKII Common Base (Shallow)

LOOP +

LOOP -

L2 = Loop +ve

L1IN = Loop -ve

Содержание MKII-AHR

Страница 1: ...e Fyreye II Detector All loop cables are terminated at the detector base with the sounder base clipping onto the common base The sounder should then be secured with it s grub screw to prevent unauthorised removal The sounder does not need to be addressed If it is to be started individually it is controlled by the detector s remote LED output The sounder does not need to be addressed If it is to be...

Страница 2: ... tone No Tone Description Pattern Frequency Rate dBA Reverb Chamber 0 BS Fire Default Zeta tone Alternating 800 970 1Hz 500ms 500ms 96 2dB 1 BS Fire Alternating 800 970 2Hz 250ms 250ms 95 2dB 2 BS Fire Sweep 800 to 970 1Hz 1 per second 98 2dB 3 BS Fire Sweep 800 to 970 7Hz 7 per second 99 2dB 4 BS Fire Sweep 800 to 970 50Hz 50 per second 99 2dB 5 BS Fire Alternating 510 610 1Hz 500mS 500mS 100 2dB...

Страница 3: ...from the manufacturer Troubleshooting Symptom Probable Cause Device Not Seen By Panel This is normal This is a platform sounder and does not reply to the panel Detector Fitted To Base Not Seen Check that a Fyreye II detector is used Previous versions of detector will not work on a Fyreye II loop Check that the wiring to the common base is correct ve L2 ve L1 IN Sounder Is Not Operating Check if Pl...

Страница 4: ... this unit should not be disposed of in a refuse bin It should be taken to a local reprocessing site as per the guidelines of the WEEE directive for correct disposal 330r 02 0832 Zeta Alarms Limited 72 78 Morfa Road Swansea SA1 2EN 14 0832 CPR F0110 EN54 3 2001 A1 2002 A2 2006 Alarm Devices Sounder Type A For Indoor Use MKII SSB Other Technical Data See Doc MKII SS Product file held by the manufac...