FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE

Technical Specification

Model

ZAZM-MI

Part Number

48-117

Operating Voltage

17 – 28V DC

Quiescent Current

3.5mA

Alarm Current (LED OFF)

12.6 mA

Alarm Current (LED ON)

13.2 mA

Isolating Current

7.3mA

End of Line Resistor

6.2k

Nominal Alarm Triggering Resistor 

1k

Operating Temperature

"-10C to 55C"

Max Humidity

95% RH Non Condensing

IP Rating

IP21C

Size

150 x 90 x 45 mm

Weight

220g

For information on the short circuit isolator operation see document GLT-224-6-9 

available from your distributor.

LED Indications

Status

LED Indication

Alarm

Illuminated red when conventional detector zone is in alarm

Polling

Flashed green when the zone monitor is communicating with panel

Isolating

Illuminated yellow when the loop is short or wrong connection circuit

Address Setting

The address of the Zone Monitor Module is set using the eight segments of the DIL 

switch. Each segment of the switch must be set to “0”(ON) or “1”(OFF), using a small 

screwdriver or similar tool. A complete list of address settings is shown overleaf. The 

maximum address is 250.

Содержание Fyreye MKII ZAZM-MI

Страница 1: ...must be performed to determine the permissable quantity of ZAZM MI per loop Model No ZAZM MI Fyreye MkII Addressable Zone Monitor Module With Isolator Surface Mounting 1 Mount the backbox as required...

Страница 2: ...o 010 Author NRP Jones Date 10 05 2021 Page 2 FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR INSTALLATION GUIDE Wiring Details All wiring terminals will accept solid or stranded cables up t...

Страница 3: ...1C Size 150 x 90 x 45 mm Weight 220g For information on the short circuit isolator operation see document GLT 224 6 9 available from your distributor LED Indications Status LED Indication Alarm Illumi...

Страница 4: ...FF OFF OFF ON ON 61 OFF ON OFF OFF OFF OFF ON ON 62 ON OFF OFF OFF OFF OFF ON ON 63 OFF OFF OFF OFF OFF OFF ON ON ADDRESS SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 64 ON ON ON ON ON ON OFF ON 65 OFF ON ON ON ON...

Страница 5: ...FF OFF OFF 248 ON ON ON OFF OFF OFF OFF OFF 249 OFF ON ON OFF OFF OFF OFF OFF 250 ON OFF ON OFF OFF OFF OFF OFF 251 252 253 254 255 ADDRESS SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 128 ON ON ON ON ON ON ON OFF...

Страница 6: ...0000 Step 2 Connect leads to LOOP IN and LOOP IN as shown below Step 3 Follow the procedure as described in the handheld programmer manual NOTE When a device is soft addressed as above the address CAN...

Страница 7: ...rmed 0 RESET 0 Normal 1 Reset on 0 RESET 0 Normal 1 Reset on Input Condition and Status Status Safe Area Circuit Analogue LED State Short circuit fault 150 8 Indeterminate 150 200 8 or 192 Alarm Alarm...

Страница 8: ...05 Zeta Alarms Limited 72 78 Morfa Road Swansea SA1 2EN 14 GLT 235 DoP 1 EN54 18 2005 EN54 17 2005 Fire detection and fire alarm systems Input Output Devices Fire detection and fire alarm systems Shor...

Отзывы: