INSTRUCTION MANUAL
Rev. A
Dongguan Zerun Electronics Technology Co.,Ltd.
( NO.1 Xianxi Industrial Park, Zhen‘an Road, Shangjiao, Chang’an Dongguan, Guangdon, P.R. China )
4 / 9
During storage, transportation and installation, it is necessary to protect the non-inserted contacts
against contamination from dust or moisture. Connectors should be protected with the appropriate
recommended dust caps* prior to being fully connected.
* Dust caps supplied by Zerun are available. Refer to section 3.6.
Articles which can erode the plastics must not be used to clean the products. We recommend the use of
soft cloths moistened with isopropyl alcohol for cleaning.
Un-mated contacts must be protected against moisture, dust and any environmental
pollution. Only clean and dry mated contacts fulfill their respective pollution class.
3.2
Cable
Preparation
and
Stripping
Process
The possible connectable wire gauge sizes are 2.5 mm², 4.0 mm², 6.0 mm² (or AWG14, AWG12,
AWG10).
Use a strip tool* to strip cable 7.0±0.5mm* and be careful not to nick conductors. See Picture 4.
* Zerun specified strip tool can be used in this step.
* The strip length can refer to the mark on Zerun wrench. See Picture 5.
Adjust the striper stopper (Picture 6) and put the cable in corresponding notch to strip the length of 7mm.
7.0±0.5
Picture 4
Picture 5
Picture 6