12 • Plumbing - Case Drain Line to Floor Drain
PLUMBING
DRAIN LINE
The drain is located at the center of the case in the floor pan. The drain can be reached by removing the
center coil covers and then removing a fan motor. The 1" PVC drain outlet is located at the center front of the
case behind the kickplate.
Install the tee to the outlet pipe and a drain trap to the tee. Plug the open end of the tee using the clean-out
plug supplied with the drain trap kit. The drain line must be pitched away from the case. The tee, drain trap,
and plug are supplied with the case. The factory installs a drain support at the front of the case on all 30"
door cases. We supply a trap support that is field mounted to the case. The drain trap must be level. The
drain trap should be primed with water after installation.
Note (if applicable): Typically Hybrid cases are equipped with a condensate collection and removal
system which includes a collection pan, pump, float switch, condensate evaporation pan with heater
element, and connecting tubing.
Case Drain Line to Floor Drain
(If Applicable)