Installation –
Mounting Height & Clearance
6
www.zephyronline.com
DUCTING
A minimum of 7” round or 3-1/4” x 10” rectangular
duct must be used to maintain maximum air flow
efficiency.
Always use rigid type metal ducts only. Flexible
ducts could restrict air flow by up to 50%.
Also use calculation (on page 5) to compute total
available duct run when using elbows, transitions
and caps.
ALWAYS, when possible, reduce the number or
transitions and turns. If long duct run is required,
increase duct size.
If turns or transitions are required; install as far
away from hood duct output and as far apart,
between the two as possible.
Minimum mount height between range top to hood
bottom should be no less than 26”.
Maximum mount height should be no higher than
36”.
It is important to install the hood at the proper
mounting height. Hoods mounted too low could
result in heat damage and fire hazard; while hoods
mounted too high will be hard to reach and will
lose its performance and efficiency.
If available, also refer range manufacturer’s height
clearance requirements and recommended hood
mounting height above range.
Vertical Ducting:
7” round or 3 1/4” x 10” rectangular minimum
Horizontal Ducting:
3 1/4” x 10” rectangular minimum
DAMAGE-SHIPMENT / INSTALLATION:
• Please fully inspect unit for damage before
installation.
• If the unit is damaged in shipment, return the
unit to the store in which it was bought for
repair or replacement.
• If the unit is damaged by the customer, repair
or replacement is the responsibility of the
customer.
• If the unit is damaged by the installer (if other
than the customer), repair of replacement must
be made by arrangement between customer
and installer.
26” min.
36” max.
36”
Содержание Monsoon Mini
Страница 2: ...www zephyronline com ...
Страница 24: ...www zephyronline com ...