MODELS  MUA006A • MUA008A • MUA010A

Page 9

FREQUENTLY ASKED 
QUESTIONS (FAQS)

1.  What does an automatic make-up air  

damper do?

An automatic make-up air damper (the “Damper”) provides a pathway for 

fresh air to enter a home from outdoors when a compatible range hood is 

operating.  When the hood blower is operating The Damper opens thereby 

creating a known, controlled point for fresh air to enter the home while air 

is being exhausted from the building by the range hood.  
By operating in this manner, the Damper provides two key benefits for the 

home:

•  It facilitates air exchange between indoors and outdoors, by helping to 

allow fresh air into the home to replace air which is exhausted out of 

the home.  

•  By allowing fresh air into the building when a compatible exhaust device 

is on, the Damper helps to avoid negative pressure conditions within 

the home which may interfere with the proper operation of combustion 

equipment within the home.

Overall, the Damper lets your range hood do its job more effectively and 

without interfering with the proper operation of other home systems.

2.  Which automatic make-up air damper do I need?

The required amount of make-up air will vary for each home and the 

amount of exhaust ventilation provided within the home.  As a general rule 

of thumb, Zephyr recommends sizing the make-up air damper as follows:

-  One 6” damper for ventilation rated up to 600 CFM
-  One 8” damper for ventilation rated up to 1000 CFM
-  One 10” damper for ventilation rated up to 1200 CFM

However, Zephyr highly recommends that a qualified professional HVAC 

contractor be consulted after installation to ensure there is no negative 

pressure in the home when the range hood is operating.  If negative 

pressure exists, then additional make-up air should be added.

3.  Does the “Damper” provide combustion air for combustion 

appliances like a water heater or  

a furnace?

No. The Damper helps to replace air which is exhausted by a compatible 

range hood.  But it does NOT help to replace air which is drawn from the 

indoors by a combustion appliance like a natural gas water heater, and it 

should not be relied upon to perform this function. One main reason for 

this restriction is that the Damper is only open when the range hood that 

it’s connected to is operating.  So there is no assurance that the Damper 

would be open when other appliances, like a water heater, are operating.  

Other  means  must  be  provided  to  ensure  adequate  combustion  air  for 

these appliances. 

4.  How do I know if I need make-up air for my  

range hood?

In some cases the local building code may tell you that make-up air is 

necessary.  For example, some codes specify that range hoods with 

exhaust  flows  of  300  cubic  feet  per  minute  (CFM)  or  higher  need  a 

mechanical system to introduce make-up air.
In other cases, make-up air for a range hood is desirable regardless of 

whether code requires it.  This is especially true for:

•  larger range hoods (those over 300 cfm)
•  homes which are well air-sealed 
•  homes  with  atmospherically  vented  combustion  appliances  (i.e.  a 

water heater or natural draft fireplace), which are more susceptible to 

improper venting if depressurization occurs.

In homes with any one of these factors make-up air is advised.  And in 

homes with more than one of these conditions make-up air for the range 

hood is strongly advised.

5.  What are the benefits of providing make-up air to replace air 

which is exhausted out of the home by a range hood?

Range hoods are designed to pull out pollutants like cooking odors or 

moisture at the source, so they don’t linger in the home.  Because these 

fans pull air out of the house, this air needs to be replaced with “new” air 

from outdoors.  Normally this make-up air enters the home through cracks 

and holes in the “shell” of the building.  But modern homes are air-sealed 

much more thoroughly so there are not as many cracks and openings.  

Plus some exhaust fans like range hoods exhaust a lot more air than can 

be replaced through normal cracks in the building shell.
By providing an intentionally designed opening for fresh air to replace 

air which is exhausted out by the range hood, several important benefits 

result:

•  The make-up air entering the home comes in at a known point, where 

it is also filtered

•  Negative pressure conditions, which could arise if air is exhausted from 

a home without being replaced by new fresh air, are prevented

•  Pollutants are more effectively exhausted from the home while fresh 

replacement air is drawn into the home, improving ventilation

6.  Does ASHRAE 62.2-2007 – “Ventilation and Acceptable Indoor 

Air Quality in Low-Rise Residential Buildings” – require the use 

of a make-up air damper?

ASHRAE 62.2-2007 does not specifically require make-up air dampers. In 

a few limited circumstances, this standard does require that net exhaust 

flows from a house be limited.  For example, Section 6.4 of the standard 

limits the net exhaust flow from a home’s two largest exhaust appliances 

if the home has atmospherically vented or solid-fuel burning appliances 

located within the pressure boundary of the house. This standard is 

available at www.ashrae.org. 

7.  Can I use the Zephyr Automatic Make-Up Air Damper with other 

equipment in my home?  

No. The Zephyr Automatic Make-Up Air Damper may only be used with 

compatible Zephyr range hoods over 400 CFM. 

8.  What are the different ways that the Damper can be installed in 

my home?  

The most common way to install the Damper is to connect it to a home’s 

central duct system.  In this application, outside fresh air enters the home 

through the Damper and is then routed and distributed through the home’s 

ducts.  

9.  What happens after a power outage?

The Damper system and the associated exhaust devices will not lose their 

settings following a power outage.  So the system will resume its normal 

operation following a power outage, based on the settings it used prior to 

the outage.

Regular maintenance is necessary to ensure the proper operation 

of the Damper system.  Failure to conduct such routine maintenance 

can jeopardize the ability of the Damper to introduce fresh air into the 

home.  Regular maintenance should include the following activities:

•  Clean the outside bird screen to ensure it is free from debris and 

open to allow fresh air to enter.

•  Clean or replace the interior filter(s) which serve to filter fresh air 

before it enters the home.

•  Maintain a clear opening at the outdoor end cap, which means pre

-

venting the buildup of snow, leaves, or vegetation at the end cap.

•  During regular HVAC maintenance, have the mechanical contrac

-

tor inspect the Damper system for proper operation.

MAINTENANCE

Содержание AK7036BS

Страница 1: ...e and Installation Guide www zephyronline com Model number Serial Number Date of Purchase Sales Dealer APR14 0301 2014 Zephyr Corporation Tempest I AK7000BS AK7036BS AK7042BS READ AND SAVE THESE INSTR...

Страница 2: ...ng collar 5HFWDQJXODU PHWDO FDS for single blower horizontal ducting 1 Hardware package HARDWARE PACKAGE CONTENTS PARTS NOT SUPPLIED Ducting conduit and all installation tools DEOH FRQQHFWRU if requir...

Страница 3: ...Ft 6 Round straight 1 Ft x Ft Subtotal column 1 Duct pieces T otal Equivalent number length x used 6 Round wall cap with damper 30 Ft x Ft Round wall cap with damper 30 Ft x Ft 7 10 Round 900 elbow 15...

Страница 4: ...important to install the hood at the proper mounting height Hoods mounted too low could UHVXOW LQ KHDW GDPDJH DQG UH KD DUG ZKLOH hoods mounted too high will be hard to reach and ZLOO ORVH LWV SHUIRU...

Страница 5: ...garages All exhaust must be ducted to the outside Use metal ductwork only DVWHQ DOO FRQQHFWLRQV ZLWK VKHHW PHWDO VFUHZV DQG WDSH DOO MRLQWV ZLWK FHUWL HG 6LOYHU 7DSH RU XFW 7DSH Some Ducting Options I...

Страница 6: ...1 5 8 1 4 9 16 6 8 1 8 or 10 3 8 9 1 2 or 14 3 16 2 7 7 8 or 9 15 16 Single Blower Dimension Dual Blower Dimension R 9 16 29 7 8 30 35 7 8 36 41 7 8 42 3 12 11 22 1 2 37 C L 9 7 8 11 16 7 3 8 3 1 4 4...

Страница 7: ...al codes and ordinances Electrical Supply This appliance requires a 120V 60Hz electrical supply and connected to an individual properly grounded branch circuit protected by a 15 or 20 ampere circuit b...

Страница 8: ...is necessary If using a dual internal blower please refer to page 14 for cut out dimensions 5 Drill cut out the required openings for duct and electrical access make sure the duct opening is large en...

Страница 9: ...UHFWDQJXODU GXFWLQJ WKH PD LPXP DLU RZ RI 0 ZLOO be reduced to 550 CFM Other CFM levels will not be affected VERTICAL TO HORIZONTAL DUCTING CONVERSION 1 Disconnect blower plug 5HPRYH VFUHZV DW WRS RI...

Страница 10: ...RYHG EORZHU screws and reconnect blower plug 7 Attach 8 round duct collar or 3 1 4 x10 rectangular duct collar to back of hood body XVLQJ 0 VFUHZV 8 From inside hood body position top cover plate to t...

Страница 11: ...ved from step 3 Installation PBD 1200A Dual Blower This range hood is equipped standard with a single blower vertical duct option To convert from single blower vertical ducting to dual blower vertical...

Страница 12: ...prevent this size of a cut out then the 10 transition adapter may be mounted to the cabinet bottom rather than the top of the hood Cut out dimensions for this type of installation are 13 1 4 width x...

Страница 13: ...ing Diagrams 22 VOLTS HZ MAX AMPS 120 60 Single Motor 5 USE ONLY TYPE MR16 GU10 35 W MAX HALOGEN LIGHT BULBS CIRCUIT DIAGRAM Dual Motor 9 AK7000BS AK7036BS AK7042BS ACT 390 CFM Fan Max 355W 2 8A ACT 2...

Страница 14: ...VSODVK Z 6KHOYHV 6 DFNVSODVK Z 6KHOYHV 6 Universal Make Up Air Damper 650 CFM MUA008A Universal Make Up Air Damper 1200 CFM MUA010A To order parts visit us online at http store zephyronline com or cal...

Страница 15: ...AK7000BS AK7036BS AK7042BS...

Страница 16: ...1 50120077 Panel Rear AK7042BS 1 12 50210020 Filter Baffle 36 42 x 3 2 13 50500145 Light Socket Assembly 2 14 50110139 Panel Light AK7000BS 1 14 50110139 Panel Light AK7000BS 1 14 50110140 Panel Light...

Страница 17: ...Installation Guide www zephyronline com Model number Serial Number Date of Purchase Sales Dealer J 1 0 01 Zephyr Corporation Tempest Recirculating Kit ZRC 7000 ZRC 7036 ZRC 7042 READ AND SAVE THESE I...

Страница 18: ...1 LIST OF MATERIALS 2 INSTALLATION Speci cations 3 Mounting the Diverter Box 4 Mounting the Filters and Brackets 5 LIST OF PARTS AND ACCESSORIES 6 Table of Contents...

Страница 19: ...UPPLIED 1 Air diverter box Charcoal filters for ZRC 7000B Charcoal filter brackets for ZRC 7000B 1 Hardware package HARDWARE PACKAGE CONTENTS PARTS NOT SUPPLIED Ducting conduit and all installation to...

Страница 20: ...3 Installation Specifi cations 27 1 4 1 3 16 7 1 2 2 9 16 29 15 16 4 12 7 8 2 9 16 1 3 8 35 15 16 41 15 16 or or 33 1 4 39 3 16 or or Top Front Side...

Страница 21: ...f the air diverter box with the screws recently installed Slide the air diverter box towards the wall to temporarily lock in place Hand tighten the 4 screws Fig A 3 Lift Tempest I range hood and align...

Страница 22: ...nto the baffle filter first Push the bracket towards the baffle filter to lock bracket in place There is a clip on top of the bracket that will secure it to the baffle filter Fig C Repeat this step fo...

Страница 23: ...w zephyronline com DESCRIPTION PART Replacement Parts Charcoal Filter each Z0F C002 To order parts visit us online at http store zephyronline com or call us at 1 888 880 8368 List of Parts and Accesso...

Страница 24: ...Use Care and Installation Guide www zephyronline com OCT13 0201 Zephyr Corporation Universal Make Up Air Damper MUA006A MUA008A MUA010A...

Страница 25: ...the outside air duct directly above or closer than 2 ft to any furnace or its supply plenum boiler or other heat producing appliance 4 Any ductwork used in conjunction with the Damper must be installe...

Страница 26: ...ings in exterior walls including steps to prevent moisture intrusion around the opening Note that the screen over the outside air opening is not a filter It is intended to prevent the intake of leaves...

Страница 27: ...d notes as guidance for your own installation Always comply with local code requirements and in any instance where a detail shown below conflicts with local code the local code provision shall apply D...

Страница 28: ...ure when the range hood exhausts at high speed PRESSURE SWITCH OPERATION The pressure switch is designed to operate when the static pressure increases to 0 05 Ps or more It may not operate at low spee...

Страница 29: ...LINE BLOWER RANGE HOOD PROBE EXHAUST DUCT PRESSURE SWITCH HOOD FLUE ROOF CAP w DAMPER INLINE BLOWER TYPICAL INSTALLATION WITH EXTERIOR BLOWER RANGE HOOD PROBE EXHAUST DUCT PRESSURE SWITCH HOOD FLUE EX...

Страница 30: ...PROBE PRESSURE SWITCH PRESSURE SWITCH TUBING PROBE air flow arrow pointing in direction of air flow AIR FLOW DUCTWORK GASKET SHEET METAL SCREWS Connect tubing onto outside of black fitting Drill 3 8...

Страница 31: ...ood and check to see if the damper closes A qualified HVAC contractor should also ensure the proper operation and venting of all combustion equipment in the home Wire the system as shown FALSE TRIPPIN...

Страница 32: ...dvised And in homes with more than one of these conditions make up air for the range hood is strongly advised 5 What are the benefits of providing make up air to replace air which is exhausted out of...

Страница 33: ...E D I M E N S I O N S BACK DRAFT DAMPE FEATURES 3 4 View Side View A B E D C Galvanized G 90 NOT FOR USE WITH DRYER VENT APPLICATIONS Side View C B A A B C 7x6 8x6 8x7 1 3 4 1 3 4 5 4 3 4 4 1 4 10x8 5...

Страница 34: ...tch A B C D E 6 7 8 12 6 3 15 10 12 7 2 1 2 15 11 15 8 3 1 2 15 12 10 F G H I 15 10 2 1 2 20 16 3 1 4 5 1 8 5 1 8 5 1 2 6 1 2 3 1 4 3 1 2 4 1 4 1 7 8 1 7 8 2 2 1 4 3 1 4 3 1 4 3 1 4 3 1 2 AK00046 AK00...

Страница 35: ...y used with make up air kits M O D E L D U C T S I Z E D I M E N S I O N S FEATURES A B C D E 6 7 6 7 5 8 8 1 8 1 2 7 8 5 8 9 5 8 1 8 1 2 8 10 11 5 8 1 3 4 8 1 2 10 F G 8 H 10 12 13 1 3 4 8 1 2 8 5 8...

Страница 36: ...matically opens when range hood is operating Automatically closes when range hood is off 24 gauge galvanized steel construction Adjustment screw to adjust damper opening AK00030 Fresh air inlet cap wi...

Страница 37: ...www zephyronline com Use Care and Installation Guide Tempest I II Stainless Steel Duct Cover AK0720 30 AK0726 36 AK0728 48 SEP16 0401 AK0722 42 AK0724 54...

Страница 38: ...Table of Contents LIST OF MATERIALS 2 SPECIFICATIONS 3 INSTALLATION 4 CLEANING AND CONTACT INFORMATION 5 1...

Страница 39: ...List of Materials 1 Center Panel 2 Side Panels 12 Philips Head Metal Screws Note If any parts are missing please call 1 888 880 8368 for replacements 2...

Страница 40: ...Specifications 3 For use with Tempest I For use with Tempest II AK7000 AK7500 AK7036 AK7536 AK7548 30 36 42 48 54 AK7542 AK7554 AK7042...

Страница 41: ...panel with screws provided 2 Place assembled duct cover on top of hood Make sure the screw holes of the center panel are facing down and line up with the holes on top of hood 3 Attach the duct cover t...

Страница 42: ...ng on your cooking habits When cleaning use a non abrasive cleaner do not use orange cleaner Abrasive cleaners may scratch the surface and discolor the stainless steel You may also polish the stainles...

Отзывы: