Zennio ZRX-KCI4SO Скачать руководство пользователя страница 2

 

Technical Documentation 

© Zennio Avance y Tecnología S.L.                      Edition 1                                               Further information 

www.zennio.com

                       

Page 

2

 

 

 

 

INPUTS: SPECIFICATIONS AND CONNECTIONS 

 

 

 

 

 

 

 

 

 

 

 

BATTERY REPLACEMENT 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SAFETY INSTRUCTIONS

 

  Do not connect Mains Voltage (230 V) or any other external voltages to any point of the BUS.   Connecting an external 

voltage might put the entire KNX system at

 

risk.  

  Make sure during the installation that there is always sufficient insulation between the mains voltage 230V and the bus or 

the extension inputs. 

  Once the device is installed, the terminals should not be accessible. 

Concept 

Description 

Number of S0 or dry inputs 

Minimum pulse length 

30ms 

Inputs connection 

Terminal block (screw) 

Inputs per common 

2  

Recommended cable section  0.25 mm² to 2.5 mm²  
Max. cable length  

30m 

Cable type 

Stranded or solid wire 

Operating voltage 

6VDC 

 

1.

 Extract the battery holder from the upper 

side of KCI. It is recommended to have the 
bus KNX connected during this process to 
prevent S0 pulses loss. 

2.

 Place the batteries in the battery holder (respecting the polarity 

shown) and insert it as indicated in the figure. 

Figure 2: 

Example of connections with SO pulse generators

 

Отзывы: