MAXinBOX 24
http://www.zennio.com
Technical Support:
http://support.zennio.com
21
613, 645, 677, 709, 741,
773
1 Bit
I
C - - W U
DPT_Step
0/1
[FCx] Manual Fan: Step Control
0 = Down; 1 = Up
614, 646, 678, 710, 742,
774
1 Bit
I
C - - W U
DPT_Switch
0/1
[FCx] Manual Fan: Speed 0
0 = Off; 1 = On
615, 647, 679, 711, 743,
775
1 Bit
I
C - - W U
DPT_Switch
0/1
[FCx] Manual Fan: Speed 1
0 = Off; 1 = On
616, 648, 680, 712, 744,
776
1 Bit
I
C - - W U
DPT_Switch
0/1
[FCx] Manual Fan: Speed 2
0 = Off; 1 = On
617, 649, 681, 713, 745,
777
1 Bit
I
C - - W U
DPT_Switch
0/1
[FCx] Manual Fan: Speed 3
0 = Off; 1 = On
618, 650, 682, 714, 746,
778
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] Fan: Speed 0 (Status)
0 = Off; 1 = On
619, 651, 683, 715, 747,
779
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] Fan: Speed 1 (Status)
0 = Off; 1 = On
620, 652, 684, 716, 748,
780
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] Fan: Speed 2 (Status)
0 = Off; 1 = On
621, 653, 685, 717, 749,
781
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] Fan: Speed 3 (Status)
0 = Off; 1 = On
622, 654, 686, 718, 750,
782
1 Byte
I
C - - W U
DPT_Value_1_Ucount
0 - 255
[FCx] Manual Fan: Enumeration
Control
S0 = 0; S1 = 1; S2 = 2; S3 = 3
1 Byte
I
C - - W U
DPT_Value_1_Ucount
0 - 255
[FCx] Manual Fan: Enumeration
Control
0 = S0; 1 = S1; 2 = S2
1 Byte
I
C - - W U
DPT_Value_1_Ucount
0 - 255
[FCx] Manual Fan: Enumeration
Control
0 = S0; 1 = S1
623, 655, 687, 719, 751,
783
1 Byte
O
C T R - -
DPT_Value_1_Ucount
0 - 255
[FCx] Fan: Speed Enumeration
(Status)
S0 = 0; S1 = 1; S2 = 2; S3 = 3
1 Byte
O
C T R - -
DPT_Value_1_Ucount
0 - 255
[FCx] Fan: Speed Enumeration
(Status)
S0 = 0; S1 = 1; S2 = 2
1 Byte
O
C T R - -
DPT_Value_1_Ucount
0 - 255
[FCx] Fan: Speed Enumeration
(Status)
S0 = 0; S1 = 1
624, 656, 688, 720, 752,
784
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[FCx] Manual Fan: Percentage Control
S0 = 0%; S1 = 0,4-33,3%; S2 = 33,7-
66,7%; S3 = 67,1-100%
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[FCx] Manual Fan: Percentage Control
0% = S0; 1-50% = S1; 51-100% = S2
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[FCx] Manual Fan: Percentage Control
0% = S0; 1-100% = S1
625, 657, 689, 721, 753,
785
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[FCx] Fan: Speed Percentage (Status)
S0 = 0%; S1 = 33,3%; S2 = 66,6%; S3 =
100%
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[FCx] Fan: Speed Percentage (Status)
S0 = 0%; S1 = 50,2%; S2 = 100%
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[FCx] Fan: Speed Percentage (Status)
S0 = 0%; S1 = 100%
626, 658, 690, 722, 754,
786
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[FCx] Cooling Fan: Continuous Control
0 - 100%
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[FCx] Cooling Valve: PI Control
0 - 100%