KLIC-SG

 

https://www.zennio.com

                                                                  

Technical Support:

 

https://support.zennio.com

 

 

29 

2)  Reset the A/C unit (IDU). 

3)  If wired control is available, check if it reports any error. 

4)  If internal communication error is still active, contact technical support. 

  Errors in the A/C machine: 

 

[AC] A/C Unit Error: Active Error

”: 1-Bit object which indicate that there 

is an error in the A/C unit.  

 

[AC] A/C Unit Error: Error Code

”: 14-Byte object that supplies the error 

code. 

In case the A/C unit reports an error, the 

former object will be sent with value of “1”, while 

the latter will report the corresponding error code. Once the error is over, both binary and 

14-

byte objects will send a value of “0”. Please, refer to the user manual of the A/C unit 

for details about the error codes. 

Содержание KLIC-SG

Страница 1: ...KLIC SG KNX F3 F4 Gateway for Indoor Samsung A C Units USER MANUAL ZCLSG Application program version 1 1 User manual edition 1 1 _a www zennio com...

Страница 2: ...2 Installation 5 1 3 Start Up and Power Loss 6 2 Configuration 7 2 1 General 7 2 2 A C Gateway 10 2 2 1 Configuration 10 2 2 2 Fan 20 2 2 3 Initial Configuration 24 2 2 4 Scenes 26 2 2 5 Error Handli...

Страница 3: ...pport zennio com 3 DOCUMENT UPDATES Version Changes Page s 1 1 _a Changes in the application program Fan step control Flaps horizontal and vertical Ionizer Wind free Wireless remote control restrictio...

Страница 4: ...ual status of the unit can be monitored and periodically sent to the KNX bus to inform other devices The most outstanding features of KLIC SG are Bidirectional control of indoor Samsung A C units IDU...

Страница 5: ...ing mode making the associated LED 1 light in red Note if this button is held while plugging the device into the KNX bus the device will enter into safe mode The LED will blink in red every 0 5 second...

Страница 6: ...the device packaging and also available at www zennio com 1 3 START UP AND POWER LOSS Depending on the configuration some specific actions will be performed during the device start up The integrator m...

Страница 7: ...unctions A C gateway The latter entails all functions specific to KLIC SG i e all the functions related to interfacing with the A C unit and to the management of the climate control system ETS PARAMET...

Страница 8: ...project Heartbeat Object to Send 1 that will be sent periodically with value 1 to notify that the device is still working still alive Note the first sending after download or bus failure takes place...

Страница 9: ...on mode either Automatic Heating Cooling Fan or Dry or reading the current mode respectively See section 2 2 1 for further options AC Fan Percentage Control and AC Fan Percentage Control Status allow...

Страница 10: ...nctions Simplified Operation Mode which allows switching between heating and cooling operation modes by means of a 1 bit object Fan which allows advanced configuration of the ventilation see section 2...

Страница 11: ...isable wireless controller Filter which allows to know the filter status of the A C Unit Ionizer which allows to activate the air purification function These functionalities imply changes in the state...

Страница 12: ...l Support https support zennio com 12 ETS PARAMETRISATION The Configuration window under A C Gateway provides the following parameters Figure 5 A C Gateway Configuration OPERATION MODES Figure 6 A C G...

Страница 13: ...operating modes Additionally a simplified mode can be configured to select Cooling and Heating mode Simplified Mode Only Cooling Heating disabled enabled in addition to the Mode and Mode Status 1 Byt...

Страница 14: ...l loop Once enabled a secondary parameter will show Sending Type Variation Periodic Periodic Variation sets whether the above object should be sent only in case of a change in the value periodically i...

Страница 15: ...ue will be rounded to X 0 if Y 5 or to X 5 if Y 5 Status object will be updated to the last setpoint temperature value received by the A C unit after a complete communication cycle and will be sent to...

Страница 16: ...Temperature Setpoint Upper Limit 2 Byte object that allows changing the upper limit at run time AC Temperature Setpoint Upper Limit Status 2 Byte object with the upper limit current value Notes If Min...

Страница 17: ...r or a similar event trigger Automatic off will be also active if the unit is previously in off state so the unit will not be able of being on until this situation finishes During the temporary switch...

Страница 18: ...state will be the last one KLIC SG is aware of Custom see section 2 2 3 SCENES Figure 13 A C Gateway Configuration Scenes Scenes disabled enabled allows setting up different scenes up to 5 consisting...

Страница 19: ...erating time retransmission period If set to 0 the periodic send is disabled When operating time object reaches its maximum value 65535h it will be sent through KNX bus in spite of the fact that the p...

Страница 20: ...the Fan tab KLIC SG allows advanced configuration of the fan functionality The following features are displayed 360 CST allows configuration for 360 cassette unit enabling custom objects and configura...

Страница 21: ...ir Flow and AC CST Air Flow Status for airflow control of this IDU type Fan Speeds 3 4 specifies the number of the fan levels distinguished by A C unit KLIC SG allows the sending of fan speed orders t...

Страница 22: ...rol 1 bit disabled enabled enables the AC Fan Step Control one bit object If the parameter is enabled the following options are displayed Non Cyclical the automatic mode will be ahead the minimum spee...

Страница 23: ...r the polarity can be configured by parameter Fan Stop Object Polarity 0 Fan Stop Protection 1 Normal Operation 0 Normal Operation 1 Fan Stop Protection sets the polarity of the above object Flaps dis...

Страница 24: ...vated in fan mode when Wind Free mode is activated or when the A C unit is switched off 2 2 3 INITIAL CONFIGURATION The custom initial configuration allows setting the desired status that KLIC SG will...

Страница 25: ...he value of the setpoint temperature will be kept Only available if the Setpoint parameter remains disabled 16 25 30 C Note this initial setpoint value may be modified by the setpoint limits during ru...

Страница 26: ...AMETRISATION After enabling this function see section 2 2 1 a new tab named Scenes will be incorporated to the tab tree It allows setting up different scenes up to 5 consisting each of them in a set o...

Страница 27: ...the Fan tab See section 2 2 2 Air Flow Direction4 No Change Spot Mid Wide Swing Horizontal Flaps No Change Swing Off Swing On Vertical Flaps No Change Swing Off Swing On Setpoint disabled enabled Val...

Страница 28: ...METRISATION The error handling function does not entail any parameter configuration The following objects are available by default Internal error objects AC Internal Error Communication 1 Bit object t...

Страница 29: ...C Unit Error Active Error 1 Bit object which indicate that there is an error in the A C unit AC A C Unit Error Error Code 14 Byte object that supplies the error code In case the A C unit reports an er...

Страница 30: ...etector for the connection of a motion detector from Zennio 2 2 1 BINARY INPUT Please refer to the Binary Inputs user manual available in the KLIC SG product section at the Zennio website www zennio c...

Страница 31: ...cution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterisable communication objects The result after exec...

Страница 32: ...etpoint Lower Limit 16 30 C 2 Bytes I C W DPT_Value_Temp 273 00 670433 28 EHS Water Temperature Lower Limit Status 5 55 C 7 2 Bytes O C R T DPT_Value_Temp 273 00 670433 28 AC Temperature Setpoint Lowe...

Страница 33: ...rmal operation 20 1 Byte I C W DPT_Value_1_Ucount 0 255 AC 360 CST Air Flow 0 Spot 1 Mid 2 Wide 3 Swing 21 1 Byte O C R T DPT_Value_1_Ucount 0 255 AC 360 CST Air Flow Status 0 Spot 1 Mid 2 Wide 3 Swin...

Страница 34: ...h 0 1 AC Wind Free Mode 0 Deactivate 1 Activate 42 1 Bit O C R T DPT_Switch 0 1 AC Wind Free Mode Status 0 Deactivated 1 Activated 43 1 Bit I C W DPT_Switch 0 1 AC Quiet Mode 0 Deactivate 1 Activate 4...

Страница 35: ...C T DPT_UpDown 0 1 Ix Short Press Move Up Shutter Sending of 0 Up 1 Bit C T DPT_UpDown 0 1 Ix Short Press Move Down Shutter Sending of 1 Down 1 Bit C T DPT_UpDown 0 1 Ix Short Press Move Up Down Shut...

Страница 36: ...x Short Press Shutter Status Input 0 Top 100 Bottom 1 Byte I C W DPT_Scaling 0 100 Ix Short Press Dimming Status Input 0 100 74 80 1 Bit C T DPT_Switch 0 1 Ix Long Press 0 Sending of 0 1 Bit C T DPT_S...

Страница 37: ...5 Ix Long Press Constant Value Integer 0 65535 1 Byte C T DPT_Scaling 0 100 Ix Long Press Constant Value Percentage 0 100 1 Byte C T DPT_Value_1_Ucount 0 255 Ix Long Press Constant Value Integer 0 255...

Страница 38: ...tected by an external sensor 99 104 109 128 133 138 1 Byte O C R T DPT_Scaling 0 100 Ix Cx Detection State Scaling 0 100 100 105 110 129 134 139 1 Byte O C R T DPT_HVACMode 1 Comfort 2 Standby 3 Econo...

Страница 39: ...t 0 255 LF Function x Result 1 Byte Unsigned 2 Bytes O C R T DPT_Value_2_Ucount 0 65535 LF Function x Result 2 Byte Unsigned 4 Bytes O C R T DPT_Value_4_Count 2147483648 2147483647 LF Function x Resul...

Страница 40: ...n and send us your inquiries about Zennio devices https support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio...

Отзывы: