KLIC-DA LT
Technical Support:
http://zennioenglish.zendesk.com
9
4. Any communication object received from the KNX bus during the previous
stages will be taken into account by KLIC-DA, which will in fact update the
status of the Altherma system –after the initial sequence– according to them.
The above sequence occurs whenever KLIC-DA powers up, or detects communication
errors with the P1/P2 bus. It also takes place when the Altherma system itself restarts
the communication, for example after a configuration change from the main control.
Finally, the KLIC-DA LT application program brings the option to
send all the status
objects
to the KNX bus after a voltage recovery, in order to update other KNX devices.