background image

 

 

 

 

      

inBOX 24 v2 / inBOX 20 v2

 

http://www.zennio.com

 

 

   

                     

Technical Support:

 http://support.zennio.com 

 

23 

155

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] [Sx] Control Variable (Heat)

 

PI Control (PWM)

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] [Sx] Control Variable

 

2-Point Control

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] [Sx] Control Variable

 

PI Control (PWM)

 

36, 42, 74, 80, 112, 118, 150, 

156

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] [Sx] PI State (Cool)

 

0 = PI Signal 0%; 1 = PI Signal Greater 

than 0%

 

37, 43, 75, 81, 113, 119, 151, 

157

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] [Sx] PI State (Heat)

 

0 = PI Signal 0%; 1 = PI Signal Greater 

than 0%

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] [Sx] PI State

 

0 = PI Signal 0%; 1 = PI Signal Greater 

than 0%

 

158

 

1 Bit

 

I

 

C - - W -

 

DPT_Switch

 

0/1

 

[ML] Trigger

 

Trigger the Master Light Function

 

159, 160, 161, 162, 163, 164, 

165, 166, 167, 168, 169, 170

 

1 Bit

 

I

 

C - - W -

 

DPT_Switch

 

0/1

 

[ML] Status Object x

 

Binary Status

 

171

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[ML] General Status

 

Binary Status

 

172

 

1 Bit

 

 

C T - - -

 

DPT_Switch

 

0/1

 

[ML] General Switch Off: Binary 

Object

 

Switch Off Sending

 

173

 

1 Byte

 

 

C T - - -

 

DPT_Scaling

 

0% - 100%

 

[ML] General Switch Off: Scaling

 

0-100%

 

174

 

1 Byte

 

 

C T - - -

 

DPT_SceneControl

 

0-63; 128-191

 

[ML] General Switch Off: Scene

 

Scene Sending

 

175

 

1 Byte

 

 

C T - - -

 

DPT_HVACMode

 

1=Comfort  

2=Standby  

3=Economy  

4=Building  

Protection

 

[ML] General Switch Off: HVAC mode

 

Auto, Comfort, Standby, Economy, 

Building Protection

 

176

 

1 Bit

 

 

C T - - -

 

DPT_Switch

 

0/1

 

[ML] Courtesy Switch On: Binary 

Object

 

Switch On Sending

 

177

 

1 Byte

 

 

C T - - -

 

DPT_Scaling

 

0% - 100%

 

[ML] Courtesy Switch On: Scaling

 

0-100%

 

178

 

1 Byte

 

 

C T - - -

 

DPT_SceneControl

 

0-63; 128-191

 

[ML] Courtesy Switch On: Scene

 

Scene Sending

 

179

 

1 Byte

 

 

C T - - -

 

DPT_HVACMode

 

1=Comfort  

2=Standby  

3=Economy  

4=Building  

Protection

 

[ML] Courtesy Switch On: HVAC mode

 

Auto, Comfort, Standby, Economy, 

Building Protection

 

180, 184, 188, 192

 

2 Bytes

 

O

 

C T R - -

 

DPT_Value_Temp

 

-273.00º -  

670760.00º

 

[Ix] Current Temperature

 

Temperature Sensor Value

 

181, 185, 189, 193

 

1 Bit

 

O

 

C T R - -

 

DPT_Alarm

 

0/1

 

[Ix] Overcooling

 

0 = No Alarm; 1 = Alarm

 

182, 186, 190, 194

 

1 Bit

 

O

 

C T R - -

 

DPT_Alarm

 

0/1

 

[Ix] Overheating

 

0 = No Alarm; 1 = Alarm

 

183, 187, 191, 195

 

1 Bit

 

O

 

C T R - -

 

DPT_Alarm

 

0/1

 

[Ix] Probe Error

 

0 = No Alarm; 1 = Alarm

 

204, 210, 216, 222

 

1 Bit

 

I

 

C - - W -

 

DPT_Enable

 

0/1

 

[Ix] Input Lock

 

0 = Unlock; 1 = Lock

 

205, 211, 217, 223

 

1 Bit

 

 

C T - - -

 

DPT_Switch

 

0/1

 

[Ix] [Short Press] 0

 

Sending of 0

 

1 Bit

 

 

C T - - -

 

DPT_Switch

 

0/1

 

[Ix] [Short Press] 1

 

Sending of 1

 

1 Bit

 

I

 

C T - W -

 

DPT_Switch

 

0/1

 

[Ix] [Short Press] 0/1 Switching

 

Switching 0/1

 

Содержание inBOX 20 v2

Страница 1: ...inBOX 24 v2 inBOX 20 v2 Multifunction Actuator for Flush Mounting ZIOIB24V2 USER MANUAL ZIOIB20V2 ds kmfroi Application program version 1 1 1 2 User manual edition 1 2 _a www zennio com...

Страница 2: ...ation 4 1 3 Start Up and Power Loss 5 2 Configuration 6 2 1 General 6 2 2 Inputs Only inBOX 24 v2 8 2 2 1 Binary Input 8 2 2 2 Temperature Probe 9 2 2 3 Motion Detector 9 2 3 Outputs 10 2 3 1 Manual C...

Страница 3: ...dividual ON OFF outputs 4 multi purpose inputs only in inBOX 24 v2 configurable as Temperature probe either models provided by Zennio or other NTC temperature probes from other suppliers being in that...

Страница 4: ...entirely analogous for inBOX 20 v2 although the inputs are not available The main elements of the device are described next Test Prog Pushbutton 3 a short press on this button sets the device into the...

Страница 5: ...evice and also available at www zennio com 1 3 START UP AND POWER LOSS During the start up of the device the Test Prog LED will blink in blue colour for a few seconds before the device is ready Extern...

Страница 6: ...TION From the General screen it is possible to activate deactivate all the required functionality Figure 2 Default screen Once activated Inputs only on inBOX 24 v2 Outputs Logic Functions Thermostats...

Страница 7: ...eat Periodical Alive Notification this parameter lets the integrator incorporate a one bit object to the project Heartbeat Object to Send 1 that will be sent periodically with value 1 to notify that t...

Страница 8: ...detector from Zennio Important older models of the Zennio motion detector e g ZN1IO DETEC and ZN1IO DETEC N will not work properly with inBOX 24 v2 ETS PARAMETERISATION When Inputs has been activated...

Страница 9: ...product section at the Zennio website www zennio com 2 2 3 MOTION DETECTOR It is possible to connect motion detectors from Zennio to the input ports of inBOX 24 v2 Please refer to the specific user ma...

Страница 10: ...therefore available per output Manual operation can be done in two different ways named as Test On Mode for testing purposes during the configuration of the device and Test Off Mode for a normal use a...

Страница 11: ...d the device will act over the output according to the length of the button press and to the current state A long press makes the shutter start moving upwards or downwards depending on the button bein...

Страница 12: ...eaving the Test On mode the status objects will recover the values they had prior to entering Test On As the device is never aware of the actual position of the shutter as the shutter drive does not p...

Страница 13: ...g pressing the Prog Test button Lock Manual Control unless the above parameter has been Disabled the Lock Manual Control parameter provides an optional procedure for locking the manual control in runt...

Страница 14: ...xecution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterizable communication objects The result after ex...

Страница 15: ...4 v2 implements four Zennio thermostats which can be enabled and configured independently Please refer to the specific Zennio Thermostat user manual available in the inBOX 24 v2 product section at the...

Страница 16: ...at to send to the KNX bus in both cases a shutter order a thermostat setpoint or mode switch order a constant value a scene Only the trigger object and the twelve status objects are required to be bin...

Страница 17: ...off takes off Scene if checked object ML General Switch off Scene will be enabled which will send a scene run save order configurable in Action and Scene Number whenever the general switch off takes o...

Страница 18: ...http support zennio com 18 when the courtesy switch on takes place in contrast to object ML General Switch Off Binary Object which sends the value 0 during the general switch off as explained above F...

Страница 19: ...ending for that output or that channel such temporisation will be interrupted and only the delay and the action of the new scene will be executed ETS PARAMETERISATION Prior to setting the scene tempor...

Страница 20: ...the scene temporisation Therefore parameter Scene m Z Delay defines the delay that will be applied to the action defined in Z for the execution of scene m where Z may be a specific individual output...

Страница 21: ...Byte I C W DPT_SceneControl 0 63 128 191 Thermostat Scene Input Scene Value 6 44 82 120 2 Bytes I C W DPT_Value_Temp 273 00 670760 00 Tx Temperature Source 1 External Sensor Temperature 7 45 83 121 2...

Страница 22: ...t 0 1 Tx Setpoint Reset Reset Setpoint to Default 1 Bit I C W DPT_Reset 0 1 Tx Offset Reset Reset Offset 24 62 100 138 1 Bit I C W DPT_Heat_Cool 0 1 Tx Mode 0 Cool 1 Heat 25 63 101 139 1 Bit O C T R D...

Страница 23: ...eneControl 0 63 128 191 ML General Switch Off Scene Scene Sending 175 1 Byte C T DPT_HVACMode 1 Comfort 2 Standby 3 Economy 4 Building Protection ML General Switch Off HVAC mode Auto Comfort Standby E...

Страница 24: ...0 0xF Inc by 1 Ix Short Press Brighter Increase Brightness 4 Bit C T DPT_Control_Dimming 0x0 Stop 0x1 Dec by 100 0x7 Dec by 1 0x8 Stop 0xD Inc by 100 0xF Inc by 1 Ix Short Press Darker Decrease Bright...

Страница 25: ..._UpDown 0 1 Ix Long Press Move Up Shutter Sending of 0 Up 1 Bit C T DPT_UpDown 0 1 Ix Long Press Move Down Shutter Sending of 1 Down 1 Bit C T DPT_UpDown 0 1 Ix Long Press Move Up Down Shutter Switchi...

Страница 26: ...Ix Long Press Release Stop Shutter Release Stop Shutter 209 215 221 227 1 Byte I C W DPT_Scaling 0 100 Ix Long Press Dimming Status Input 0 100 1 Byte I C W DPT_Scaling 0 100 Ix Long Press Shutter Sta...

Страница 27: ...T_Switch 0 1 Ix Cx Detection State Binary Binary Value 259 264 269 288 293 298 317 322 327 346 351 356 1 Bit I C W DPT_Enable 0 1 Ix Cx Enable Channel According to parameters 260 265 270 289 294 299 3...

Страница 28: ...1 On 496 1 Bit I C W DPT_UpDown 0 1 CA Auto Move 0 Raise 1 Lower 497 1 Bit I C W DPT_Step 0 1 CA Auto Stop Step 0 Stop StepUp 1 Stop StepDown 1 Bit I C W DPT_Step 0 1 CA Auto Stop 0 Stop 1 Stop 498 1...

Страница 29: ...Data Entry 665 666 667 668 669 670 671 672 4 Bytes I C W DPT_Value_4_Count 2147483648 2147483647 LF 4 Byte Data Entry x 4 Byte Data Entry 673 674 675 676 677 678 679 680 681 682 1 Bit O C T R DPT_Bool...

Страница 30: ...n and send us your inquiries about Zennio devices http support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio c...

Отзывы: