SAFETY INSTRUCTIONS 

 Installation should only be performed by qualified professionals according to the laws and regulations applicable in each cou ntry. 

 Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for th e entire 

KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other 
accessories, in case of being installed. 

 The  facility  must  be  equipped  with  a  device  that  ensures  the  omnipolar  sectioning.  Installation  of  a  10A  mini -circuit-breaker  is 

recommended. To prevent accidents, it must remain open in case of manipulation of the device. 

 Once the device is installed (in the panel or box), it must not be accessible from outside. 

 Keep the device away from water and do not cover it with clothes, paper or any other material while in use. 

 The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at 

http://zennio.com/weee-regulation. 

OUTPUTS SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Number of outputs 

Output type 

Solid state switching device 

Maximum 
recommended load per 
output (AC/DC) 

Quantity of valves ² 

Stationary current 

200mA (@ 35°C) 

Maximum inrush current 

2.5A 

Short-circuit protection 

YES 

Overload protection 

YES 

Connection method 

Screw terminal block 

Cable cross-section 

0.5-4mm² (IEC) / 26-12AWG (UL) 

² This value could be more restrictive depending on the valve stationary current and inrush current. 
 

EXTERNAL POWER SUPPLY SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Voltage 

230VAC 50/60Hz 

Connection method 

Screw terminal block 

Cable cross-section 

0.5-4mm² (IEC) / 26-12AWG (UL) 

 
Connecting more than one valve to each output is allowed as long as the maximum current per output is not exceeded:

 

 

WIRING DIAGRAMS 

230VAC

 

50/60Hz

 

Valve 1

 

 

Valve 

n

 

(n≤5)

 

Valve

 

 

Figure 2: Wiring example: several valves per output and one valve per 

output. 

Figure 3: Mounting HeatingBOX 230V 4X on 

DIN rail 

Attaching HeatingBOX 230V 4X to DIN rail: 

Removing HeatingBOX 230V 4X from DIN rail:

 

 

NOTE

:  Simultaneous  connection  of  one 

valve to several outputs is not allowed. 

Several valves per output 

connection schematic

 

One valve per output 

connection schematic

 