background image

© Zennio Avance y Tecnología S.L. 

Edition 3 

Futher information 

www.zennio.com

 

Page 3/4 

 

 

WIRING DIAGRAMS 

Figure 2: Wiring example (from top to bottom and left to right): 2 loads, 2 loads connected to different phases, shutter channel, 

fancoil three-speed fan, fancoil three-point valves and fancoil open/close valves. 

* In case of using ZN1IO-DETEC-P sensor, its micro switch number 2 must be in 

Type B position

** Zennio temperature probe or any NTC with known resistance values at three points in the range [-55, 150ºC]. 

INPUTS CONNECTION 

Any combination of the following 

accessories

 is allowed in the inputs: 

Zennio  temperature 
probe.

 

 

 

Up  to  two  motion  sensors 
can  be  plugged  into  the 
same  device  input  (parallel 
wiring)

 

 

 

Screw 

terminal 

for 

connecting  Zennio  motion 
sensors*.

 

 

Temperature Probe**

 

Motion Sensor

 

 

 

Switch/Sensor/ 

Push button

 

 

 

 

INPUTS SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Number of inputs 

12 

Inputs per common 

Operation voltage 

+3.3VDC in the common 

Operation current 

1mA @ 3.3VDC (per input) 

Switching type 

Dry voltage contacts between input and common 

Connection method 

Screw terminal block 

Cable cross-section 

0.5-2.5mm² (IEC) / 26-12AWG (UL) 

Maximum cable length 

30m 

NTC probe length 

1.5m (up to 30m) 

NTC accuracy (@ 25°C) ² 

±0.5°C 

Temperature resolution 

0.1°C 

Maximum response time 

10ms 

² For Zennio temperature probes. 

 

 

 In order to ensure the expected status of the 

relays,  please  check  that  the  device  is 
connected  to  the  main  power  supply  before 
energizing the power circuit. 

For  a  4-pipe  fancoil,  the  cooling  valve  should 
always  be  connected  on  the  left  side  and  the 
heating valve on the right side. Before the start-
up of the device, it must be assured that the valve 
is completely closed. 
 
Outputs that are not being used for valve control 
can  be  used  as  individual  outputs  or  shutter 
channels. 
 
Wiring the fancoil to the outputs of the lower side 
of the device is similar to that of the upper outputs 
(E1=A1, E2=A2, F1=B1, ...). 

OPEN 

CLOSE 

OPEN 

CLOSE 