14
open the adapter, open the bottle valve and up side down it.press
key, use the
or
key to select the item you want (highlight field is
activated), select “INTERNAL TANK REFILL”
2. Press
to confirm. Follow the instructions on the display.
3. Press
to confirm. The quantity of refrigerant in the inner tank is shown.
4. The filling will stop automatically when the quantity of refrigerant is 9 KG
5. Close the refrigerant bottle valve, press
to confirm. Press
key
to start recovery operation!
No t e :
you should recover the refrigerant. If you do not recycle the
refrigerant inside the hose, it will cause refrigerant leakage when you
release connections, as this can cause frosty.
6. Disconnect the LP adapter from the external refrigerant bottle. The
device now is ready for operation.
FUNCTION
1
.
INNER TANK REFILL
2
.
LANGUAGE SELECT
3
.
ZERO BALANCE
INNER TANK REFILL
CONNECT THE LP HOSE TO
THE SOURCE TANK,OPEN THE
VALVE UP_SIDE DOWN IT .
REFILL
RUNNING
**
:
**
RECOVERED
*****G
Press ESC to exit
INNER TANK REFILL
FINISHED!
PRESS OK TO CONFIRM