background image

Содержание Nova Neo

Страница 1: ...Cooling Fresh Air Clean Air Heating Zehnder Nova NEO Manual ...

Страница 2: ......

Страница 3: ...f your appliance 12 3 1 Standard maintenance operations 12 3 2 Cleaning the airflow filter 12 4 In case of fault 13 5 Service 14 Appendix Fan operation logic 63 Dear customer Thank you for choosing this radiator This product has been manufactured in accordance with our stringent quality requirements to give you total satisfaction To get the most out of your radiator we advise you to read these ins...

Страница 4: ...tput The control panel is used to operate the fans only It does not control the independent water circuit within the radiator this is managed by the water supply device The radiator has two operating modes Heat Mode for which a low tem perature water supply can be used or Refresh Mode which requires a source of cold water In this case you must ensure that your cold water supply is at a sufficient ...

Страница 5: ...Children must be supervised to ensure that they do not play with the appliance Radiators must be used for the purpose for which they are intended and not as a table chair toy ladder etc and as specified in the user and service instructions supplied with the appliance Caution To avoid overheating do not cover the heating appliance Caution Do not sit on the heating appliance Protect the radiator from...

Страница 6: ...igh heat loss windows doors etc wherever possible Use mounting screws suitable for your wall Important this radiator must be installed with the fan control panel positioned topside Ensure that the bottom of the radiator is positioned at least 10 cm from the floor Fan control panel Airflow Water flow Connection to water source Fan power supply 1 Installing your appliance GB ...

Страница 7: ...r a Class 1 product Note the flexible cable supplied with the appliance is designed to be connected to the mains via a plug or a junction box according to local standards 1 3 Radiator installation restrictions This appliance must be installed in accordance with applicable standards and good practice in the country concerned Important the radiator must not be exposed to intense or prolonged ambient...

Страница 8: ... lights up Level 3 high speed the right hand LED lights up The fans will start at high speed boost and revert to level 1 automatically after one hour Note each time the required room temperature is reached your water supply boiler or heat pump will stop supplying hot cold water to your appliance To save energy the sensors in your appliance will detect this and switch the fans off automatically wha...

Страница 9: ...r fault If so further action is required contact your installer or dealer see section 4 Lights OFF mode For your convenience particularly where the appliance is installed in a bedroom all LED warning lights will go out automatically after 10 minutes with no intervention required on your part This mode affects the LEDs only and has no impact on radiator or fan operation Press any button to exit thi...

Страница 10: ...temperature 25ºC Refresh Mode is selected automatically if the water temperature drops below the maximum Refresh Mode temperature 21ºC Note no action by the user is required to switch between these 2 modes Note in all cases a minimum gap of 2ºC between water temperature inside your appliance and ambient temperature in your room is required for fan operation Fan operation logic See Appendix Water t...

Страница 11: ...nce Condensation may form if the temperature of the cold water used with your appliance is too low Be aware that your appliance is not equipped with any condensation recovery gutter or similar Depending on the temperature and pressure in your room water conden sation may develop and possibly cause corrosion of your radiator and damage to its built in fans A water supply device with dew point manag...

Страница 12: ...ed convection control panel 3 2 Cleaning the airflow filter The alarm LED 5 lights up to indicate that you need to clean the filter at the bottom of your appliance which will become clogged with dust over time You can use a vacuum cleaner with the filter still in place or remove the filter from its housing completely by pulling the filter locks forwards as shown above steps 1 to 3 The filter may be ...

Страница 13: ...ghts up when a fault is detected and goes out when the fault is cleared see section 2 1 If the LED remains on further action is required contact your installer or dealer Note if the power cable is damaged for safety reasons it must be replaced by the manufacturer the manufacturer s after sales service department or a similarly qualified person 4 In case of fault GB ...

Страница 14: ...f the guarantee The guarantee shall not apply if the appliance is installed used or maintained in a way that does not comply with standards in force in the relevant country good professional practice or the manufacturer s instructions For all other questions regarding the guarantee please contact your installer or dealer Environmental regulations RoHS Complies with Directive 2002 95 EC WEEE Compli...

Страница 15: ...www zehnder systems com V1110 imprimé par Alliance Partenaires Graphiques ...