background image

38

3-speed control 
card

The unit has been factory 
configured to produce the same 
airflow as the standard PSC 
motor on all speeds when using 
the 3-speed control card with a 
maximum of 10% higher than the 
high speed setting available on 
most units during readjustment. 
If these settings are acceptable, 
then no further configuring is 
required.

If alternative airflows are 
desired, use board mounted 
potentiometers, marked as FL01, 
FL02, FL03, to adjust the airflow 
associated with each input. Each 
output can be adjusted from 0 
to 100% of the motor’s factory 
programmed operating range 
using an instrument screwdriver. 
Insert the screwdriver into 
the white center of the 
potentiometer and turn clockwise 
for an increase in airflow or 
counterclockwise for a decrease 
in airflow.

0-10 VDC control 
card

The 0-10 VDC control card is 
not configured at the factory 
and needs to be used in 
conjunction with a field installed/
provided thermostat and/or DDC 
controller.

EC Motor

If the unit is equipped with an EC 
motor, additional steps may be 
required during the air balancing 
process. Review project submittals 
or order acknowledgment to 
determine what type of EC motor 
control is provided. Alternatively, 
match the control board to the 
illustrations.

The unit has been factory configured 
to produce the same airflow as the 
standard PSC motor on all speeds 
when using the 3-speed control card 
for vertical units and a maximum 
of 10% higher than the high speed 
setting when using the 0-10 VDC 
control card. If these settings 
are acceptable, then no further 
configuring is required.

EC motor nameplate amperage 
indicates the motor hardware peak 
amperage while the motor full 
load amperage (FLA) is limited by 
the motor’s factory programmed 
operating range, programmed 
specifically for each unit size. The 
programmed operating range is 
generally only a portion of the motor 
hardware full potential resulting in 
the motor FLA being lower than the 
nameplate FLA. Motor FLA will be 
reflected on the Fan Coil serial tag 
and should be used when sizing 
building electrical requirements.

The control box needs to be powered 
while adjustments are made. Line 
voltage components are concealed 
within a covered junction box. 
However, the installer should take 
all necessary precautions to avoid 
contact with live voltage wires.

Controls operation

Before proper control operation 
can be verified, all other systems 
must be operating properly. 
The correct water and air 
temperatures must be present 
to determine if the control 
function is operating to design. 
Some controls and features are 
designed to not operate under 
certain conditions. For example, 
a 2-pipe cooling/heating system 
with auxiliary electric heat, the 
electric heat will not energize 
when hot water is present.

A wide range of controls, 
electrical options and 
accessories may be used 
with the units covered in this 
manual. Review the approved 
project submittals or order 
acknowledgment for detailed 
information regarding each 
individual unit and its controls. 
Since controls may vary from 
one unit to another, care should 
be taken to identify the controls 
being used with each individual 
unit and its proper control 
sequence. 

Controls

Содержание FC series

Страница 1: ...i Cooling Fresh Air Clean Air Heating Room Fan Coils Installation Operation and Maintenance ...

Страница 2: ... Electrical connections 29 Wiring diagram 30 Exposed unit touch up 35 Start up 35 Air system balancing 36 Cooling heating system 36 Water system balancing 37 Water treatment 37 EC Motor 38 Control cards 38 Controls operation 38 Normal operation maintenance 39 Replacement parts 41 Equipment start up checklist 42 IMPORTANT Submittal documentation specific to each project supersedes the general guide...

Страница 3: ...models FF 200 FF 220 FS 200 FF Floor FF 200 shown FF 220 available FS Sloped FS 200 FLF 510 FLF Low profile FLF 510 FFH 450 FFH 460 FFH Floor hideaway FF 450 shown FFH 460 available FLH 520 FLH Low profile hideaway FLH 520 1 Models and arrangements ...

Страница 4: ...0 Fan Coil models and airflow arrangements Wall models FW Wall FW 280 shown FW 260 and FW 270 available FFRW Fully recessed wall FFRW 340 FRW Partially recessed wall FRW 320 FW 260 FW 280 FRW 320 FFRW 340 2 ...

Страница 5: ...rangements Ceiling models FC Ceiling Bottom in front out shown FFRC Fully recessed ceiling Bottom in front out shown FCH Ceiling hideaway FCHP Ceiling hideaway with plenum Back in front out shown FTHP Telescoping ceiling hide away 3 ...

Страница 6: ...10 1100 1130 Low 280 330 430 520 780 950 970 Coil FPI 12 12 12 12 12 12 12 Face area ft2 0 94 1 25 1 56 2 19 2 50 2 92 3 44 Coil connections 1 2 Cu 1 2 Cu 1 2 Cu 1 2 Cu 1 2 Cu 1 2 Cu 1 2 Cu Blower Quantity 1 1 2 2 1 2 4 4 Diameter 5 7 5 7 5 7 5 7 5 7 5 7 5 7 Width 7 5 10 4 7 5 10 4 7 5 10 4 7 5 10 4 Filter Number 1 1 1 1 1 1 1 Length in 22 28 34 46 52 60 70 Width in 9 75 9 75 9 75 9 75 9 75 9 75 9...

Страница 7: ... 60 0 GPM 1 8 1 9 2 5 3 6 5 1 6 0 7 6 PD ft of H2O 5 9 10 1 3 0 4 0 6 9 6 0 11 2 Heating capacity optional 1 row reheat coil MBH 11 2 11 9 17 0 25 1 31 8 36 7 47 7 GPM 1 3 1 2 1 8 2 6 3 3 3 8 5 0 PD ft of H2O 1 0 0 6 2 5 1 2 1 9 2 5 3 9 Heating capacity optional 2 row reheat coil MBH 17 6 24 6 29 8 43 9 55 6 66 0 78 7 GPM 1 8 2 5 3 1 4 5 5 7 6 8 8 1 PD ft of H2O 3 7 7 9 3 4 7 9 6 7 7 1 10 3 CFM st...

Страница 8: ... 290 390 580 Medium 150 170 290 325 Low 100 120 150 220 CFM high capacity High 275 390 480 680 Medium 260 375 460 625 Low 240 350 400 520 Coil FPI 12 12 12 12 Face area ft2 1 25 1 67 2 08 2 92 Coil connections 1 2 Cu 1 2 Cu 1 2 Cu 1 2 Cu Blower Quantity 1 1 2 2 Diameter 5 7 5 7 5 7 5 7 Width 7 5 10 4 7 5 10 4 Filter Number 1 1 1 1 Length in 21 75 27 75 33 75 45 75 Width in 8 25 8 25 8 25 8 25 Thic...

Страница 9: ...6 30 25 04 50 3 16 34 3 16 36 29 1 4 06 62 3 16 46 3 16 48 42 08 68 3 16 52 3 16 54 51 1 8 10 76 3 16 60 3 16 62 59 12 86 3 16 70 3 16 72 69 Dimensional data Coil E F G H J K L M 3 Row N A N A N A N A 18 9 16 3 19 7 8 4 5 8 4 Row N A N A N A N A 18 9 16 3 19 7 8 4 5 8 3 1 Row 18 7 3 4 21 3 4 4 5 16 18 9 16 3 19 7 8 4 5 8 4 1 Row 19 3 8 8 1 16 23 1 8 5 1 4 18 9 16 3 19 7 8 4 5 8 Notes 3 and 4 row c...

Страница 10: ...6 3 16 60 3 16 62 59 12 86 3 16 70 3 16 72 69 Dimensional data Coil E F G H J K L M 3 Row N A N A N A N A 18 9 16 3 19 7 8 4 5 8 4 Row N A N A N A N A 18 9 16 3 19 7 8 4 5 8 3 1 Row 18 7 3 4 21 3 4 4 15 16 18 9 16 3 19 7 8 4 5 8 4 1 Row 19 3 8 8 1 16 23 1 8 5 1 4 18 9 16 3 19 7 8 4 5 8 Dimensions and data Model FS Notes 3 and 4 row coil supply and return 1 2 nominal 5 8 OD all sizes 1 row coil reh...

Страница 11: ...3 44 3 16 28 3 16 25 04 50 3 16 34 3 16 29 1 4 06 62 3 16 46 3 16 42 Notes All coil connections are 1 2 nominal 5 8 OD all sizes Left hand piping connections shown right hand electrical as standard Piping hand determined when facing air outlet All listed dimensions are approximate and are subject to change without notice Modifications to the product specifications must be accepted by Zehnder Rittl...

Страница 12: ... A B 02 22 5 16 16 3 16 03 28 5 16 22 3 16 04 34 5 16 28 3 16 06 46 5 16 40 3 16 Notes All coil connections are 1 2 nominal 5 8 OD all sizes Left hand piping connections shown right hand electrical as standard Piping hand determined when facing the air outlet All listed dimensions are approximate and are subject to change without notice Modifications to the product specifications must be accepted ...

Страница 13: ...ply hot water Return steam 5 8 3 8 2 1 4 7 1 8 9 1 8 Dimensions and data Model FFH Dimensional data Unit size A B C D E 02 24 1 8 22 3 8 24 21 18 03 30 1 8 28 3 8 30 27 24 04 36 1 8 34 3 8 36 33 30 06 48 1 8 46 3 8 48 45 42 08 54 1 8 52 3 8 54 51 48 10 62 1 8 60 3 8 62 59 56 12 72 1 8 70 3 8 72 69 66 Dimensional data Coil F G H J 3 1 Row 19 3 16 15 7 16 4 15 16 7 3 4 4 1 Row 20 9 16 16 13 16 5 1 4...

Страница 14: ... hand piping connections shown right hand electrical as standard Piping hand determined when facing the air outlet Unit length for 6 extended end pocket add 6 to dimension A All listed dimensions are approximate and are subject to change without notice Modifications to the product specifications must be accepted by Zehnder Rittling at its base office Dimensions and data Model FW Dimensional data U...

Страница 15: ...16 46 3 16 48 42 65 3 16 08 68 3 16 52 3 16 54 51 1 8 71 3 16 10 76 3 16 60 3 16 62 59 79 3 16 12 86 3 16 70 3 16 72 69 89 3 16 Dimensional data Coil F G H J K L M N 3 Row N A N A N A N A 16 1 8 3 17 3 8 4 5 8 4 Row N A N A N A N A 16 1 8 3 17 3 8 4 5 8 3 1 Row 15 9 16 7 3 4 19 5 16 4 15 16 16 1 8 3 17 3 8 4 5 8 4 1 Row 16 15 16 8 1 16 20 11 16 5 1 4 16 1 8 3 17 3 8 4 5 8 Notes 3 and 4 row coil su...

Страница 16: ... TOP VIEW A F BAR GRILLE BOTTOM VIEW D LOUVERED SUPPLY OPENING CENTERED FRONT VIEW LOUVERED SUPPLY A C FRONT VIEW DUCTED SUPPLY E FILTER POSITION RETURN COOLING SIDE VIEW LOUVERS SHOWN RETURN HOT WATER SUPPLY STEAM SUPPLY HOT WATER RETURN STEAM SUPPLY COOLING D LOUVERED OUTLET OPENING CENTERED Dimensional data Coil E 3 Row N A 4 Row N A 3 1 Row 22 1 8 4 1 Row 23 3 2 Row 23 4 2 Row 24 3 16 Dimensio...

Страница 17: ...turn shown Back ducted return also available with filter positioned vertically All listed dimensions are approximate and are subject to change without notice Modifications to the product specifications must be accepted by Zehnder Rittling at its base office Dimensional data Unit Size A B C D F 2 33 3 8 20 17 7 8 25 3 4 22 3 39 3 8 26 23 7 8 31 3 4 28 4 45 3 8 32 29 7 8 37 3 4 34 6 57 3 8 44 41 7 8...

Страница 18: ...isted dimensions are approximate and are subject to change without notice Modifications to the product specifications must be accepted by Zehnder Rittling at its base office Dimensional data Coil E 3 Row N A 4 Row N A 3 1 Row 5 3 4 4 1 Row 5 3 4 3 2 Row 4 3 4 4 2 Row 3 7 8 Dimensional data Unit Size A B C D 2 22 19 20 28 1 2 3 28 25 26 34 1 2 4 34 31 32 40 1 2 6 46 43 44 52 1 2 8 52 49 50 58 1 2 1...

Страница 19: ...o available with filter positioned horizontally All listed dimensions are approximate and are subject to change without notice Modifications to the product specifications must be accepted by Zehnder Rittling at its base office Dimensional data Coil E 3 Row N A 4 Row N A 3 1 Row 21 13 16 4 1 Row 22 3 4 3 2 Row 22 3 4 4 2 Row 23 7 8 Dimensional data Unit Size A B C D 2 22 19 20 28 1 2 3 28 25 26 34 ...

Страница 20: ... hand determined when facing the air outlet Filter removal from bottom through access panel All listed dimensions are approximate and are subject to change without notice Modifications to the product specifications must be accepted by Zehnder Rittling at its base office Dimensional data Unit Size A B C D F G H 2 22 19 20 28 1 2 33 7 8 25 3 4 22 3 28 25 26 34 1 2 39 7 8 31 3 4 28 4 34 31 32 40 1 2 ...

Страница 21: ... data Unit size A B C D 02 38 3 16 22 3 8 24 18 5 8 03 44 3 16 28 3 8 30 18 5 8 04 50 3 16 34 3 8 36 23 5 8 06 62 3 16 46 3 8 48 23 5 8 08 68 3 16 52 3 8 54 33 5 8 10 76 3 16 60 3 8 62 33 5 8 12 86 3 16 70 3 8 72 33 5 8 Notes Damper motor always on right side when viewing unit from front side All listed dimensions are approximate and are subject to change without notice Modifications to the produc...

Страница 22: ...l data Unit size A B C 02 38 3 16 22 5 16 18 5 8 03 44 3 16 28 5 16 18 5 8 04 50 3 16 34 5 16 23 5 8 06 62 3 16 46 5 16 33 5 8 Notes Damper motor always on right side when viewing unit from front side All listed dimensions are approximate and are subject to change without notice Modifications to the product specifications must be accepted by Zehnder Rittling at its base office 20 Dimensions and da...

Страница 23: ...louvered inlet grille with internal bug screen 3 1 2 A Front View Weep holes 2 5 8 4 to 8 1 2 2 13 16 Side View Dimensions and data Outside air wall box Dimensional data Model A Rough opening WB 0203 24 22 1 2 x 3 WB 0406 29 27 1 2 x 3 WB 081012 39 37 1 2 x 3 21 ...

Страница 24: ...urize equipment beyond specified pressures as shown on unit rating plate Always pressure test with an inert fluid such as water or dry nitrogen to avoid possible damage or injury in the event of a leak or component failure during testing Always protect adjacent flammable material when welding or soldering Use a suitable heat shield material to contain sparks or drops of solder Have a fire extingui...

Страница 25: ...ration of the equipment The installation of fan coils and all associated components parts and accessories shall be in accordance with the regulations of all authorities having jurisdiction and must conform to all applicable codes It is the responsibility of the installing contractor to determine and comply with all applicable codes and regulations contractor to inspect and verify that the units sh...

Страница 26: ...store or install units in corrosive environments or in locations subject to temperature or humidity extremes e g attics garages rooftops etc Corrosive conditions and high temperature or humidity can significantly reduce system performance reliability and overall service life a clean dry area of the building or in a warehouse Do not remove any equipment from its shipping package until it is needed ...

Страница 27: ...hen the unit is installed level Care must be taken to ensure that the drain pan does not slope away from the drain connection Vertical units are designed to be bolted to the wall structure through the slotted wall mounting holes in the chassis used for anchoring to pre installed wall studs Horizontal units are provided with slotted ceiling mounting brackets where hanging rod and rubber in shear or...

Страница 28: ...ensions Improper mounting could result in the unit falling from its position causing personal injury or even death After mounting the unit it is then ready for the various service connections such as water drain and electrical At this time it should be verified that the proper types of services are actually provided to the unit On those units requiring chilled water and or hot water the proper lin...

Страница 29: ...ng tightening to prevent damage to the coil tubing Over tightening must be avoided to prevent distorting the union seal surface and destroying the union ultimately causing a leak Secure the union nut hand tight and then tighten no more than an additional 1 4 turn The inlet supply connection is marked at the appropriate coil stub out with the other coil stub out being the outlet return connection I...

Страница 30: ...with re insulating piping if the installing contractor failed to establish system integrity prior to insulating All chilled water piping and valves not located over the drain pan or drip pan must be insulated to prevent damage from sweating This includes factory and field piping inside the unit cabinet The condensate drain should always be connected and piped to an acceptable disposal point For pr...

Страница 31: ...wired in strict accordance with the wiring diagram Failure to do so could result in personal injury or damage to components and will void the manufacturer warranty All wiring connections should be checked prior to start up to ensure connections have not come loose during shipment or installation minimizing problems during start up The fan motor s should never be controlled by any wiring or device ...

Страница 32: ...MINATION FACTORY WIRE NOT CONNECTED WIRE CONNECTION FIELD WIRED FACTORY WIRED 18AWG FACTORY WIRED 12AWG Vertical wiring schematic 120V Blower motor wiring chart Size Motor Sizes High Medium Low 02 12W Blue Red Yellow 03 12W Black Red Yellow 04 30W Black Blue Red 06 50W Black Yellow Gray 08 50W 25W Black Red Gray 10 2 50W Blue Yellow Gray 12 2 50W Black Red Gray Notes Complete the wiring in accorda...

Страница 33: ...ing schematic 208V 240V 277V Blower motor wiring chart Size Motor Sizes High Medium Low 02 12W Blue Red Yellow 03 12W Black Red Yellow 04 30W Black Blue Red 06 50W Black Yellow Gray 08 50W 25W Black Red Gray 10 2 50W Blue Yellow Gray 12 2 50W Black Red Gray Notes Complete the wiring in accordance with national and local codes Wiring diagram is for typical application If other controls are specifie...

Страница 34: ... QUICK CONNECT 4 CIRCUIT TERMINAL BLOCK WHITE WHITE DAMPER MOTOR BLUE BLUE BLUE RED BLACK BLACK BLACK WHITE WHITE WHITE N N L N L GND BLACK BLACK LINE L N L N LOAD BLACK L1 L1 L2 T2 T1 HEATER YELLOW BROWN BROWN TERMINATED IF NO DAMPER MOTOR OPTIONAL MANUAL MOTOR STARTER OPTIONAL DISCONNECT SWITCH OPTIONAL 3 CIRCUIT TERMINAL BLOCK 120VAC 60Hz GFCI RECEPTACLE OPTIONAL 3 SPEED SWITCH CONTROL PACKAGE ...

Страница 35: ...ue med black high PSC MOTOR OPTION BLOWER MOTOR MOTOR QUICK CONNECT 4 CIRCUIT TERMINAL BLOCK DAMPER MOTOR BLUE BLUE BLUE RED RED RED RED RED RED BLACK BLACK L2 L GND GND GREEN BLACK BLACK RED RED L1 K1 K1 L N L2 YELLOW BROWN BROWN TERMINATED IF NO DAMPER MOTOR OPTIONAL DISCONNECT SWITCH OPTIONAL 3 CIRCUIT TERMINAL BLOCK 208 240VAC 60Hz 3 SPEED SWITCH CONTROL PACKAGE OPTION L M M H H Blower motor w...

Страница 36: ...d low blue med black high Blower motor wiring chart Size Motor Sizes High Medium Low 02 12W Blue Red Yellow 03 12W Black Red Yellow 04 30W Black Blue Red 06 50W Black Yellow Gray 08 50W 25W Black Red Gray 10 2 50W Blue Yellow Gray 12 2 50W Black Red Gray PSC MOTOR OPTION BLOWER MOTOR MOTOR QUICK CONNECT 4 CIRCUIT TERMINAL BLOCK DAMPER MOTOR BLUE BLUE BLUE RED WHITE WHITE BLACK BLACK N N L1 L GND W...

Страница 37: ...o isolate the factory finish from the quick drying touch up paint Start up general Before beginning any start up the start up personnel should take the time to familiarize themselves with the unit options accessories and control sequence to fully understand how the unit should operate properly under normal conditions All personnel should have a good working knowledge of general start up procedures...

Страница 38: ... some systems may require repeated venting over time to fully eliminate air in the system Prior to the water system start up and balancing the chilled hot water system should be thoroughly flushed to clean out dirt and debris which may have accumulated in the piping during construction During this procedure all unit service valves must be in the closed position This will prevent any foreign materi...

Страница 39: ...ert The system must be complete and all components must be in operating condition before beginning the water system balancing procedures Each hydronic system has different operating conditions depending on the devices and controls installed for the particular application The actual balancing technique may vary from one system to another After the proper system operation is established the appropri...

Страница 40: ...ntrol card If these settings are acceptable then no further configuring is required EC motor nameplate amperage indicates the motor hardware peak amperage while the motor full load amperage FLA is limited by the motor s factory programmed operating range programmed specifically for each unit size The programmed operating range is generally only a portion of the motor hardware full potential result...

Страница 41: ... or more containing sodium potassium or ammonium hydroxide are not recommended as they will aggressively corrode aluminum tubes and fins Strong ammonium hydroxide cleaners will also cause stress corrosion cracking of copper tubes Zehnder Rittling recommends completely rinsing all cleaners from the coil including cleaners identified as no rinse cleaners Residual cleaners may decompose over time pro...

Страница 42: ...t is determined by the components and wiring of the unit This may vary from unit to unit Refer to the wiring diagram located in a zip lock plastic bag in the electrical control box of each unit for the actual type and number of controls provided on each unit The integrity of all electrical connections should be verified at least twice during the first year of operation Afterwards all controls shou...

Страница 43: ...hould be used wherever possible to maintain unit performance it s normal operating characteristics and its safety testing agency listings Replacement parts may be purchased through the local Zehnder Rittling Sales Representative Failure to do this may result in significant property damage and void the manufacturer s warranty The manufacturer will not be responsible for any consequential damages du...

Страница 44: ... valve packages n n Connect field piping to unit n n Pressure test all piping for leaks n n Install drain lines and traps as required n n Insulate all piping as required n n Install drip pan under piping as required Ductwork connections n n Install ductwork fittings and grilles as required n n Flexible duct connections at unit n n Proper supply and return grille type and size n n Control outside a...

Страница 45: ...SMART IDEAS Always the best climate for ...

Страница 46: ...tling 100 Rittling Boulevard Buffalo NY USA 14220 T 844 934 6337 844 ZEHNDER F 716 827 6523 sales zehnder rittling com www zehnder rittling com Zehnder Rittling August 2017 English subject to change without notice ...

Отзывы: