background image

   7 - EN

2.2   P menus for the user

A summary of all the accessible P-menus is given 
below.

Menu P1 > Status of time programmes

Status

Submenu

Description

Activated

P10**

Is menu P20 currently 
active?

Yes (1) / No (0)

P11

Is menu P21 currently active? Yes (1) / No (0)

P12

Is menu P22 currently 
active?

Yes (1) / No (0)

P13

Is menu P23 currently 
active?

Yes (1) / No (0)

P14

Is menu P24 currently active? Yes (1) / No (0)

P15

Is menu P25 currently active? Yes (1) / No (0)

P16

Is menu P26 currently 
active?

Yes (1) / No (0)

P19**

Is menu P29 currently 
active?

Yes (1) / No (0)

Menu P9 > Status of additional programmes

Status

Submenu

Description

Activated

P90

Open fire programme active?

Yes (1) / No (0)

P91

Bypass open?

Yes (1) / No (0)

P92**

ComfoFond-L** valve open?

Yes (1) / No (0)

P93**

Post heater on?

Yes (1) / No (0)

P94

Analogue input (0-10V) 
active?

Yes (1) / No (0)

P95

Frost protection or pre 
heater active?

Yes (1) / No (0)

P96**

ComfoHood** on?

Yes (1) / No (0)

P99

Enthalpy programme active?

Yes (1) / No (0)

Menu P2 > Setting time delays

Time delay values

Submenu

Description

Minimum

Maximum

General 
reset

P20**

 Only applies to systems 

fitted with a ComfoHood**.

Overrun timer for the ComfoHood** programme.

■  

’x’ minutes after operating the ComfoHood** switch the 
unit reverts back to the normal setting.

0 Min.

180 Min.

0 Min.

P21

Delay timer for the bathroom switch (to switch to high 
position).

■  

‘x‘ minutes after operating the bathroom switch,  
the unit switches to the high setting.

0 Min.

15 Min.

0 Min.

P22

Overrun timer for the bathroom switch (to switch to normal 
position).

■  

‘x‘ minutes after operating the bathroom switch, the unit 
switches back to the normal setting.

0 Min.

120 Min.

30 Min.

P23

n/a

0 Min.

120 Min.

0 Min.

P24

Filter warning

■  

‘x’ weeks after cleaning the filters the “filter dirty” alert 
will reappear.

10 weeks

26 weeks

16 weeks

P25

 Only applies to systems 

fitted with an RFZ swith.

Overrun timer for ventilation setting 3 (using 

).

■  

 After pressing 

 briefly (< 2 sec.), the unit will switch to 

the high setting for ‘x’ minutes and then  
automatically returns to the normal setting.

If any switch is operated during this lagging time the unit will 
instantly revert to the ventilation position as set at that time.

1 Min.

20 Min.

10 Min.

P26

 Only applies to systems 

fitted with an RFZ swith.

Overrun timer for ventilation setting 3 (using 

).

■  

After pressing 

 continously (> 2 sec.), the  

unit will switch to the high setting for ‘x’ minutes and then 
automatically returns to the normal setting.

If any switch is operated during this lagging time the unit will 
instantly revert to the ventilation position as set at that time.

1 Min.

120 Min.

30 Min.

P27

 Only applies to systems 

fitted with a ComfoSense 
or CC Luxe**.

Time for the boost setting.

■  

After pressing 

  on the CC Luxe** or after  

turning on the PARTY TIMER on the ComfoSense, the 
unit will switch to the high setting for ‘x’ minutes and then 
automatically returns to the normal setting.

If any switch is operated during this lagging time the unit will 
instantly revert to the ventilation position as set at that time.

0 Min.

120 Min.

30 Min.

P29**

 Only applies to systems 

fitted with a ComfoHood**.

Setting the ComfoHood** ventilation levels.

■  

When the ComfoHood** is switched on the ComfoHood** 
ventilation settings can be set x-% higher than the 
corresponding ‘normal’ ventilation levels.

1%

99%

10%

** Only available on the ComfoAir350Luxe and ComfoAir550Luxe.

All manuals and user guides at all-guides.com

Содержание ComfoAir Luxe

Страница 1: ...1 EN Ventilation system ComfoAir Luxe User document Cooling Fresh Air Clean Air Heating ComfoAir 160 ComfoAir 200 ComfoAir 450 ComfoAir 550 ComfoAir 350 All manuals and user guides at all guides com...

Страница 2: ...e is compromised if instructions are not observed carefully Risk of personal injury for the user Maintenance Questions Please contact the supplier if you have any questions or would like to order a ne...

Страница 3: ...ning or replacing the filters 9 4 1 1Replacing the internal filters 10 4 1 2 Cleaning the internal filters 11 4 1 3 Replacing or cleaning the external filter 11 4 2 Cleaning the valve 11 4 3 Condensat...

Страница 4: ...EN 4 All manuals and user guides at all guides com...

Страница 5: ...and if present the storage room E Safety instructions Always follow the safety regulations warnings comments and instructions given in this document Personal injury or damage to the unit can arise fr...

Страница 6: ...Indicating and setting the comfort temperature Setting the P menus Resetting the malfunctions and filter alert Setting a preset ventilation programme Setting and showing date and time CC Luxe Indicat...

Страница 7: ...0 Min 120 Min 30 Min P23 n a 0 Min 120 Min 0 Min P24 Filter warning x weeks after cleaning the filters the filter dirty alert will reappear 10 weeks 26 weeks 16 weeks P25 Only applies to systems fitte...

Страница 8: ...gulations The defects are due to incorrect connection inexpert use or contamination of the system On site dis assembly costs are not covered by the terms of the warranty This also applies to normal we...

Страница 9: ...o the unit is disconnected mechanical ventilation of the dwelling will cease This can lead to a build up of moisture and results in problems with mould 4 1 Cleaning or replacing the filters Replace th...

Страница 10: ...A ComfoAir 550 4 B ComfoAir 160 200 ComfoAir 350 550 Remove the dirty filters B from the unit 5 Install the clean filter back into the unit and reconnect the power When using the unit for the first ti...

Страница 11: ...erefore do not change the setting of the valves 4 3 Condensation drain Ensure that the water seal u bend connected to the domestic waste water system is always full of water 4 4 Maintenance by the ins...

Страница 12: ...uired m3 h Tested m3 h Type valve Settings valve Settings unit Kitchen P30 Bathroom P31 Toilet P32 P33 Total Supply Room Position Required m3 h Tested m3 h Type valve Settings valve Settings unit Livi...

Страница 13: ...ctivity Y1 Y2 Y3 Y4 Y5 Y6 Y7 Clean the filters 12 months after installation Activity Y1 Y2 Y3 Y4 Y5 Y6 Y7 Replace the filters Clean the valves Inspect and clean the condensation drain Inspect and clea...

Страница 14: ...8 Y9 Y10 Y11 Y12 Y13 Y14 Clean the filters 12 months after installation Activity Y8 Y9 Y10 Y11 Y12 Y13 Y14 Replace the filters Clean the valves Inspect and clean the condensation drain Inspect and cle...

Страница 15: ...15 EN All manuals and user guides at all guides com...

Страница 16: ...d B V Lingenstraat 2 8028 PM Postbus 621 8000 AP Zwolle T 31 38 429 69 11 F 31 38 422 56 94 ventilatie zehnder nl www zehnder nl ZGNL Manual_40002051 V0117 EN Subject to change All manuals and user gu...

Отзывы: