Trickle Speed Factory 
set to setting 2

Trickle Speed Factory 
set to setting 3

12

3.1.5          Use ‘turn pots’ to achieve the desired motor speed at both speeds. Medium speed represents the mid speed 

                  between the two settings.  For example, if the trickle speed ‘pot’ is set to 20% of full motor speed and the boost 
                  speed ‘pot’ is set at 60%, Medium speed will automatically be 40%.

3.1.6          

Commissioning – Factory Settings

                  Factory settings suitable for two bedroom apartments up to 100m

2

floor area, with a Kitchen plus 2 Wet Rooms 

                  (such as Bathroom, Utility Room, Shower Room, Ensuite, WC).

3.1.7          

Commissioning – Fine Tuning

                  Minor adjustments may be required depending on overall ductwork length.

                  Fine-tuning of the motor speeds can be achieved by using the ‘turn pots’ on the fan casing to ensure 
                  optimum efficiency (See Figure 8). Record airflow rates for room extract valves and also the ‘pot’ settings 
                  for trickle and boost speeds on the front page of this installer guide. 

                  Figure 8 - ‘Speed Pot’ Setting Adjustment Panel

                  Note; Fan performance can be adjusted between these set points for further fine tuning, as the motor is 100% 
                  variable in range.

3.1.8          

Valve Set-up

                  Performance levels to be verified at the extract valves using an appropriate method such as a rotating vane 
                  anemometer and air cone kit. 

                  To adjust valves:

                      •         Set the fan speed approximately to achieve the desired extract high flow rate.

                      •        Close all windows and doors, including the rooms in which measurements are being carried out.

                      •        The index terminal (the one furthest away) should be set to fully open.

                      •          All other terminals are adjusted to achieve the required flow rate.

                      •        If the index terminal has to be closed to achieve the correct flow rates, then reduce the fan speed and

                                balance the terminals.

                      •        Switch the unit to low speed to achieve the desired extract low flow rate.It should not be necessary to 

                                adjust the extract valves further.

Содержание Centair CMEV.4e

Страница 1: ...Centair CMEV 4e CMEV 4eHT Central Mechanical Extract Ventilation Installation Instructions CMEV 4e CMEV 4eHT ...

Страница 2: ...Specification 3 2 0 Installation Instructions 4 2 1 General Preparation 4 2 2 Positioning Application 5 2 3 Mounting 5 2 4 Ducting Guidelines 6 2 5 Electrical 7 3 0 On Site Commissioning 11 4 0 Performance Graphs 13 5 0 Guarantee 14 Contents ...

Страница 3: ...ppropriate 125mm Grilles ZGS2 Hardwired switch providing switching between low and high option ZGS1 Hardwired switch providing switching between low medium and high option 1 1 7 Warning This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruc...

Страница 4: ...d to cut out the spigot blank and connect duct See Figure 1 2 1 2 125mm duct should be used to provide the best performance levels required for compliance with building regulations The CMEV 4e range has been tested with both 125mm and 100mm round ducting Note Reducing ductwork to 100mm will increase system resistance and affect overall specific fan power ratings Technical Services can be contacted...

Страница 5: ...ase when positioning mounting the product to a surface 2 2 3 Figure 1 Optional Fifth Spigot 2 2 3 Figure 2 Mounting Orientations 2 3 Mounting 2 3 1 Determine the duct inlet and exhaust configuration and the best orientation for the unit for this installation also taking account of the access to the electrical services and whether the fifth inlet port supplied capped off located on the unit base ma...

Страница 6: ...y fix ducts using metal jubilee clips or heavy duty plastic cable ties and appropriate non hardening sealant for air tightness WARNING Do not use screws for connection and ensure jubilee clips are not over tightened 2 4 6 Flexible Ducting Ensure ducting lengths are kept to a minimum and ducting is pulled taut so that it is smooth and straight Where bends are necessary and where ducting is run in r...

Страница 7: ... see diagrams a triple pole or a double pole switch having a minimum contact separation of 3 0mm must be used to provide isolation for the unit 2 5 7 The recommended switches sensors for use with either models are For CMEV 4e wire using either switch live lighting circuit with without external sensor or via a Zehnder ZGS2 2 position switch with an external sensor see below for function details For...

Страница 8: ...ed 2 6 2 Two speed control via ZGS2 switch CMEV 4eHT only 2 6 3 Three speed control via light switch for trickle boost speeds and medium speed activation via remote sensor CMEV 4e only 2 6 4 Three speed control via ZGS2 switch for trickle boost speeds and medium speed activation via remote sensor CMEV 4e CMEV 4eHT 2 6 5 Three speed control via ZGS1 switch CMEV 4eHT only ...

Страница 9: ...m the mains supply before removing the fan motor assembly 1 Remove external locking screw 1 CAUTION Fan motor assembly is free to move after the next operation in ceiling installations please ensure the fan is manually supported during the following steps 2 Rotate anti clockwise noting LINE INDICATOR moving from the LOCKED to UNLOCKED position See Figure 5a 3 Fan motor assembly can now be lowered ...

Страница 10: ...w Pin 2 is a volt free contact for additional sensors 6 Secure the cable within the internal cable clamp provided 7 Carefully realign the lid to the pot controls and respective screw connections and secure with the three connecting screws 2 7 5 Figure 6 Connecting BMS Wiring Step 1 Step 3 Step 2 Step 4 Step 6 Step 5 Step 7 BMS Cable Pin Function Conection to External Circuit 1 Speed 0 10V positive...

Страница 11: ...ning 3 1 Overview 3 1 1 This section covers set up configuration of the unit on installation and altering pre set factory settings Dependant on which model has been installed the following set up and configuration will apply 3 1 2 CMEV 4eHT Only Greenwood TimerSMARTTM and Greenwood HumidiSMARTTM The CMEV 4eHT features a fully automatic integral timer function and humidity function which monitors t...

Страница 12: ... extract valves and also the pot settings for trickle and boost speeds on the front page of this installer guide Figure 8 Speed Pot Setting Adjustment Panel Note Fan performance can be adjusted between these set points for further fine tuning as the motor is 100 variable in range 3 1 8 Valve Set up Performance levels to be verified at the extract valves using an appropriate method such as a rotati...

Страница 13: ...13 4 0 Performance Graphs 4 0 1 Airflow Characteristics for CMEV 4e CMEV 4eHT Models ...

Страница 14: ...e as standard with the option to extend to a 6 Year Guarantee subject to registration Terms and conditions apply 5 1 1 This does not affect your statutory rights 5 1 2 Full details available on request from 44 0 1276 408404 or www greenwood co uk info greenwood co uk ...

Страница 15: ...15 ...

Страница 16: ...ferred to are in millimetres unless otherwise shown Zehnder Group UK Ltd reserves the right to change specifications and prices without prior notice Copyright Zehnder Group UK Ltd 2021 Zehnder Group UK Limited Watchmoor Point Camberley Surrey GU15 3AD Customer Services 44 0 1276 408404 Technical Services 44 0 1276 408402 Email info greenwood co uk Web www greenwood co uk 05 10 874 Issue 7 May 2021...

Отзывы: