31 / 64
Identificazione: MD-AL-GI-00
Rev. 4.0 del 31.01.18 - Applicazione: GID
Manual of 07/06/2019 Rev. 2.1 “User Manual for 3K-6KTLM LITE
Figure 30 – Connecting the AC output cables (4)
4.5.
Connecting the communication cables
Connecting the communication port
Note: The wiring procedure is the same for the RS485 input, DRMS0 and CT input. This chapter describes
the steps to be followed for connecting the communication cables.
Communication port
RS485
DRM0
CT
cable cross-section
0.5-1.5 mm
2
0.5-1.5 mm
2
0.5-1.5 mm
2
Outer diameter
2.5~6 mm
2.5~6 mm
2.5~6 mm
Table 3 – Recommended specifications for AC output cables
1)
Remove the central waterproof cover of the communication terminal block using a star screwdriver;
Figure 31 – Removing the central cover
2)
Turn the waterproof cable gland; remove the cap in the waterproof cable gland;