ZANTINGH TR-LMV26 Скачать руководство пользователя страница 9

 
 
 

 
 

  
 

 

Page. 9 

LMV2635.EN.202001_V2 

 

 

which is mounted on the second safety valve (pos. VA2), makes sure the 
correct output gas pressure for the burner load is obtained. 

 

Five (5) seconds after opening the safety valves the pilot gas is shut off. 

 

The main flame has to be stable, itis checked by the flame monitoring unit 
continuously. 

 The 5 seconds during which the pilot valve (pos. MK) and the main valves (pos. 
VA1 and VA2) are in the open position is called the second safety time. If the 
flame is not formed within this time the flame guard goes into lockout and an 
error message is displayed on the electronic module. 

 

 
The maximum gas pressure switch (pos. HD1) ensures an easy steady start of 
the main flame. It is only active when starting the flame. The minimum gas 
pressure switch (pos. LD1) monitors the supply gas pressure continuously at 
the lowest applicable level. 
 

H.

  After the main flame has formed and the start sequence of the burner control 

panel is successfully gone through, the burner is “in operation” on low flame. 
Approx. 35 seconds after opening the main valves the load controller starts 
setting the load. 

 

I. 

If the load control switch on the control panel is set to 1 Auto, the burner load 
and switching on and off will be controlled by the load control unit.  

  

The maximum gas pressure switch (pos. HD) monitors the maximum burner 
load by measuring the gas pressure. 

 

 

Содержание TR-LMV26

Страница 1: ...YOU CAN COUNT ON OUR EXPERTISE OPERATING AND INSTRUCTION MANUAL ZANTINGH FORCEDGASBURNER TR RKB LMV26 3 5 SAMBA...

Страница 2: ...tem Contents Page 1 INTRODUCTION 3 2 REGULATION 3 3 IMPORTANT NOTES 3 3 1 Maintenance 4 3 2 Instruction manual instructions 4 4 SYSTEM COMPONENTS 5 4 1 Burner component 5 4 2 Air fan component 5 4 3 G...

Страница 3: ...ertified heating or electrical installer should instal the product The instructions meet the applicable local standards and regulations Please contact your Zantingh representative or local service dep...

Страница 4: ...end user s responsibility to ensure safety through annual maintenance work on the system according to applicable regulations To ensure the good operation of the heating system the boiler room has to...

Страница 5: ...the required combustion air This air fan has a directly coupled and balanced fan wheel The fan wheel is driven by an electromotor The air fan of a TR burner is directly connected to the air valve sec...

Страница 6: ...ety device pos HD The HD pressure switch monitors the maximum burner boiler capacity and is mounted on the burner head to control the burner load by means of air pressure The settings of the pressure...

Страница 7: ...e control panel includes a few switches and press button valves Fire on off switch Selector switch for load control with the following two options 1 Automatic modulated by load controller 2 External t...

Страница 8: ...e the air fan is set to low speed 25 Hz and the air quantity control valve is positioned to the start low flame position The gas quantity control valve pos HR1 controlled by a servomotor is also posit...

Страница 9: ...on the electronic module The maximum gas pressure switch pos HD1 ensures an easy steady start of the main flame It is only active when starting the flame The minimum gas pressure switch pos LD1 monito...

Страница 10: ...D display with a simple menu structure which displays the status in plain text In order to diagnose possible malfunctions the operation mode failure type and moment are displayed In case of failure be...

Страница 11: ...and A with or simultaneously reset Info and Enter button For navigating in info and service mode Incrementing the selection flashing symbol press button for 1 s Going one menu level down press button...

Страница 12: ...tronics Samba failures display further called Samba is a digital display viewing the status of the precondition circuit safety chain boiler preconditions Main screen Below an image of the main screen...

Страница 13: ...he right bottom corner of the main screen and the following screen is displayed Arrow buttons and Use the arrow keys to view other notifications Back Press the arrow pointing to the left to return to...

Страница 14: ...ates the burner start stop and controls its load based on the requested boiler temperature setpoint The corresponding display integrated in the burner s switch panel casing shows the following values...

Страница 15: ...ly pressure before the gas train by pressing the press button valve pos K2 under the manometer to read the current pressure on the manometer pos M Or check the manometer on the gas supply gas train Th...

Страница 16: ...previous item Check The air fan inlet Maximum temperature and or pressure The boiler is protected against high temperatures and or pressure A maximum thermostat or maximum pressostat device forms the...

Страница 17: ...Frequency control code F When an internal or external frequency control error is triggered the frequency control is switched off and the F symbol error code is displayed followed by a number includin...

Страница 18: ...ng unit or flame signal is too low No main flame Defect safety valve s pos VA1 and VA2 The air gas ratio is not appropriate because of which the air gas mixture does not ignite or even goes out during...

Страница 19: ...tton on the switch panel door The burner will attempt to restart Note The maximum thermostat and the low water protection device may be mechanically locked The reset button on the safety device itself...

Страница 20: ...nlet valve of the condenser on bypass 5 Check that every valve to the oil pump is open and whether the oil pump is filled with oil The complete system has to be filled with oil without any air If this...

Страница 21: ...as inlet valve of the condenser to standard operation 6 Open shut off valve A1 7 Set the main switch on the burner control panel to ON WARNING Before starting the system check the furnace for oil If t...

Страница 22: ...periodically not performed even though the equipment requires it Corrosion has been caused by polluted flue gas to be determined by Zantingh B V If after research is carried out one or more of the ab...

Страница 23: ...way or by any means be it electronically mechanically photocopy or otherwise without prior written consent from Zantingh B V Reprinting the document or any excerpt thereof is forbidden Changes errors...

Страница 24: ...Phone 31 0 297 219 100 Fax 31 0 297 219 199 E mail info zantingh com France Zantingh France SARL 95 rue F de Lesseps F 44150 Ancenis France Phone 33 0 240 83 94 30 Fax 33 0 240 83 96 72 E mail info z...

Отзывы: