34
9) MAINTENANCE & SERVICING
9.1 GENERAL MAINTENANCE
This section contains instructions for Servicing, Inspecting, and Preventive Maintenance on the Model MAC240 Air
Conditioner unit.
To ensure that the unit is kept in correct operating condition, inspect and maintain it on a regular basis. Proper replace-
ment of filters, lubricating oil, etc.., at recommended intervals help prevent damage or failure of the unit, and provide
optimum performance.
Overhaul Intervals: Under normal operating conditions and with proper preventive maintenance practices, the Model
MAC 240 Air Conditioner Unit provides years of excellent service. Typically 7,000 to 10,000 hours (depending upon local
conditions). After this 7,000 to 10,000 hour interval, major component overhaul, i.e.., diesel engine, may be required.
A. Engine Oil Change Schedule:
Time schedules indicated in preventive maintenance inspection schedule are based on average operating conditions. It
may be necessary to change oil and air filters more frequently under severe operating conditions, such as operating in
dry, hot, dusty climates (desert), areas of high humidity (tropical), excessive periods of heavy load or frequent intermit-
tent operations. Refer to Genset Manual for Engine Oil Change Instructions.
B. Refrigeration System:
The refrigerant system oil is sealed within the compressor and requires no checking.
C. Engine oil specifications:
Refer to the Genset Manual for engine lubrication specifications and requirements.
D. Fuel
Refer to the Genset Manual for engine fuel specifications and requirements.
9.2 INSPECTION & PREVENTIVE MAINTENANCE
Establish and maintain a periodic Preventive Maintenance Inspection Schedule as per table below. The criteria listed
meet the minimum requirements necessary to ensure safe reliable service under normal operating conditions. Modify it
as required to meet varying operating and environmental conditions.
PREVENTIVE MAINTENANCE SCHEDULE
This Preventive Maintenance Schedule is only for quick reference and not replacing the manufacturer manual by any means which shall be followed
by the users. Therefore, please read and follow the manufacturer manual before and during operation without any responsibility on Zamil Air Condi-
tioners. For more information, please refer to the manufacturer directly.
NOTE
: repeat the schedule every 1000 HR.
#
Operation
50 Daily 125
250
500 1000 12000
1
2
hour
hour hour hour hour hour year year
E10 E20 E30 E40 E50 E60 E70
1
Check engine for leaks (visual inspection)
X
2
Check oil level
X
3
Check Top up lube oil if necessary (also with separate container)
X
X
4
Change Lube oil (oil change intervals depending on engine use),
see 6.1.1/6.1.2 of the engine manual attached for engine model
F6L914 (Naturally aspirated engine type).
X
X
X
5
Replace Oil filter cartridge (at each lube oil change)
X
X
X
6
Check Oil bath air filter
X
7
Replace Bypass - oil filter
X
Engine Lubricant
Содержание MAC-240
Страница 1: ...MOBILE AIR CONDITIONING SYSTEM Model MAC 240 INSTALLATION OPERATION MAINTENANCE MANUAL...
Страница 9: ...8 D Alarms Shutdowns...
Страница 15: ...14 SCHEMATIC REFRIGERATION DIAGRAM...
Страница 44: ...43 10 EQUIPMENT DIMENSIONAL DETAILS Model No MAC240FZ600...
Страница 45: ...44 11 MAIN CONTROL PANEL COMPONENT LAYOUT...
Страница 46: ...45 12 MAIN CONTROL PANEL COMPONENT PARTS LIST...
Страница 56: ...55 16 UNIT OVERALL VIEW...
Страница 57: ...56 UNIT REAR SIDE GENERATOR SECTION...
Страница 58: ...57 OPTIONAL DOWN DISCHARGE PLENUM EXTENSION FLEXIBLE DUCT STORAGE BOX...
Страница 59: ...58 DIESEL FILLING POINT FUEL GAUGE...
Страница 60: ...59 COIL SECTION...
Страница 61: ...60 FAN MOTOR ASSEMBLY...
Страница 62: ...61 CONDENSER SECTION...
Страница 63: ...62 OPERATIONAL PANEL...
Страница 64: ...63 MAIN CONTROL BOX...
Страница 65: ...64 VFD GENERATOR...
Страница 66: ...65 GENERATOR DISPLAY PANEL...
Страница 67: ...66 GENERATOR SECTION...