Zamel exta PNM-10 Скачать руководство пользователя страница 2

MOUNTING

CONNECTING

DIMENSIONS

PRODUCT FAMILY 

LED MODE 

TIME COURSE 

UP

Mode

Voltage in the adjusted time, 

relay switched on.

Voltage higher than U

max

,

relay switched off.

Voltage lower than U

min

,

relay switched off.

“Soft net” effect detected.

1.  Disconnect the power supply from the 

mains by the phase fuse, the circuit-

breaker or the switch-disconnector 

that are joined to the proper circuit,

2.  Check if there is no voltage on con-

nection cables by means of a spe-

cial measure equipment,

3.  Install PNM-10 device in the switch-

board on TH-35 DIN rail,

4.  Connect the cables with the terminals 

according to installing diagram,

5.  Switch on the power supply from the 

mains,

6.  Adjust  the  required  voltage  value 

Umax and Umin and time delay 

switch off toff.

EXAMPLE OF INSTALLATION 

PNM-10 voltage relay belongs to PNM 

voltage relay product family.

RELAY CAPACITY 

INNER DIAGRAM 

FUNCTIONING

After the relay has been switched on 

it controls the voltage value on its supply 

terminals. In case the voltage is above the 

<Umin, Umax> level, toff time is meas-

ured. The relay is switched off if the volt-

age is not equal with the preset voltage 

value. The relay is not switched off in 

case voltage value is lower than toff time. 

Another relay switch on occurs when the 

voltage value is equal with the preset volt-

age value (taking into account the hyster-

esis about 3 V). The system protects the 

load capacity from the “soft net” effect that 

occurs in a situation when the connected 

load causes voltage drop below Umin. 

In case there are three switch off effects 

the output access is cut for about 10 min-

utes (red LED diode pulses). The green 

LED diode is switched on when there is a 

proper voltage value, in the range <Umin, 

Umax>. The green LED pulses rapidly, 

when voltage is higher than Umax or it 

pulses slowly when voltage is lower than 

Umin.

PNM-10 voltage relay cooperates with 

the LDM-10 voltage indicator. The value 

of voltage in a single-phase network is 

measured in the circuit of the relay whose 

outputs cut off the power supply to the pro-

tected circuit (e.g. motor) if the set voltage 

range has been exceeded. Voltage indica-

tor allows ongoing visualisation of value of 

voltage supplying the protected circuit.

300 W

1250 W

600 W

450 W

Device version:

10 – single phase

31 – three-phase

32 – three-phase, LCD

Device type

WARRANTY CARD

Manufacturer provides a 24-month warranty

Seller’s stamp and signature, date of sale

1. ZAMEL Sp. z o.o. shall offer a 24-month warranty on the products sold.

2. The warranty provided by ZAMEL Sp. z o.o. shall not cover:

a) mechanical damage caused during transport, loading/unloading or in other circumstances,

b) damage caused by incorrect installation or operation of products manufactured by ZAMEL Sp. z o.o.,

c) damage resulting from any changes made by the BUYER or third parties in the products sold or equipment necessary for the 

proper operation of the products sold,

d) damage resulting from force majeure or other fortuitous events for which ZAMEL Sp. z o.o. is not liable.

3. Any warranty claims shall be made by the BUYER at the point of sale or to ZAMEL z o.o. in writing after defects have been identi-

fied.

4. ZAMEL Sp. z o.o. undertakes to handle complaints in accordance with the applicable provisions of Polish law.

5. The choice of the form of complain resolution, e.g. replacement of a product with a product free from defects, repair, or reimburse-

ment of money, shall lie with ZAMEL Sp. z o.o.

6. The warranty does not exclude, limit, or suspend BUYER’s rights under the statutory warranty for defects in the item sold.

: Robert Rosz

kowski

e-mail: senseir@

wp.pl

TV

owski

e-mail: 

senseir@w

p.pl

Отзывы: