PHASE SEQUENCE SENSOR CKH - 01
INSTRUCTION MANUAL
APPEARANCE
FEATURES
TECHNICAL PARAMETERS
DESCRIPTION
ver. 0.4.2 _ 2006.06.20_11:00
CKH - 01
Supply cables: L1 (black), N (blue)
Input rated voltage / supervised: 230/400 V~
Input voltage tolerance: from -15 to +10 %
Rated frequency: 50 / 60 Hz
Rated current: 34 mA
Measure cables: L1 (black), L2 (brown), L3 (grey)
Asymmetry voltage threshold: 185 V
Voltage hysteresis: approx. 10 V
Switch on delay t
1
: from 5 to 10 s
Switch off delay t
2
: from 1 to 5 s
Output relay parameters: 1NO - 10 A / 250 V AC1 2500 VA
Number of terminal clamps: 6
Section of connecting cables: 4x 0,75 mm
2
and 2x 1,50 mm
2
Connecting cables: 0,5 m
Ambient temperature range: from -20 to +60
o
C
Operating position: vertical with a cable pointed down
Mounting: 2x stretcher 5x(3x30)
Protection degree: IP65 (EN 60529)
Protective class: II
Overvoltage category: II
Pollution degree: 2
Rated impulse withstand voltage: 2 kV (EN 61000-4-5)
Dimensions (height / width / depth): 69x56x27 mm
Weight: 98 g
Reference standards: EN 60730-1; EN 60730-2-1
EN 61000-4-2,3,4,5,6,11
ی Wrong phase sequence protection,
ی phase fading protection,
ی voltage asymmetry protection,
ی optimum voltage switch on threshold
185 V,
ی switch off delay and voltage hystere-
sis
ی momentary voltage fading protection
max 10 A capacity;
ی separate input for relay output termi-
nals,
ی hermetic (IP65 protection degree)
enclosure.
The CKH-01 phase sequence sen-
sor device is used to protect devices
powered from a three-phase installa-
tion (e.g. a motor) from being damage
in case of phase voltage switch off. It
is because of phase voltage asym-
metry or wrong phase sequence. The
threshold value switch on is preset to
185 V and it can not be regulated by the
user. The system does not protect from
voltage drop asymmetry and it is powered
from L1 phase. The switch off delay and
voltage hysteresis cause the system is re-
sistant to momentary voltage changes.
Zakład Mechaniki i Elektroniki
ZAMEL
sp.j.
J.W. Dzida, K. Łodzińska
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04
www.zamel.pl,
e-mail:
The device is designed
for three-phase installa-
tion and must be instal-
led in accordance with
standards valid in a par-
ticular country. The de-
vice should be connec-
ted according to the details included in
this operating manual. Installation, con-
nection and control should be carried out
by a qualified electrician staff, who act in
accordance with the service manual and
the device functions. Before installation
make sure the connection cables are
not under voltage. The cruciform head
screwdriver 3,5 mm should be used to
instal the device. Improper transport, sto-
rage, and use of the device influence its
wrong functioning. It is not advisable to
instal the device in the following cases: if
any device part is missing or the device
is damaged or deformed. In case of im-
proper functioning of the device contact
the producer.
CAUTION
brown
b
lack
bl
u
e
gre
y
brown
blue
RELAY
CABLES
Power supply cable /
measure (L1)
Power supply cable (N)
Measure cable (L3)
Measure cable (L2)