PHASE SEQUENCE SENSOR CKH - 01

 

INSTRUCTION MANUAL

APPEARANCE

FEATURES

TECHNICAL PARAMETERS

DESCRIPTION 

ver. 0.4.2 _ 2006.06.20_11:00

CKH - 01

Supply cables: L1 (black), N (blue)

Input rated voltage / supervised: 230/400 V~

Input voltage tolerance: from -15 to +10 %

Rated frequency: 50 / 60 Hz

Rated current:  34 mA

Measure cables: L1 (black), L2 (brown), L3 (grey)

Asymmetry voltage threshold: 185 V

Voltage hysteresis: approx. 10 V

Switch on delay t

1

: from 5 to 10 s

Switch off delay t

2

: from 1 to 5 s

Output relay parameters: 1NO - 10 A / 250 V AC1 2500 VA

Number of  terminal clamps: 6

Section of connecting cables: 4x 0,75 mm

2

 and 2x 1,50 mm

2

Connecting cables: 0,5 m

Ambient temperature range: from -20 to +60 

o

C

Operating position: vertical with a cable pointed down

Mounting: 2x stretcher 5x(3x30)

Protection degree: IP65 (EN 60529)

Protective class: II

Overvoltage category: II

Pollution degree: 2

Rated impulse withstand voltage: 2 kV (EN 61000-4-5)

Dimensions (height / width / depth): 69x56x27 mm

Weight: 98 g

Reference standards: EN 60730-1; EN 60730-2-1

EN 61000-4-2,3,4,5,6,11

ی  Wrong phase sequence protection,
ی  phase fading protection,
ی  voltage asymmetry protection,
ی  optimum voltage switch on threshold 

185 V,

ی  switch off delay and voltage hystere-

sis 

ی  momentary voltage fading protection 

max 10 A capacity;

ی  separate input for relay output termi-

nals,

ی  hermetic  (IP65  protection  degree) 

enclosure.

The  CKH-01  phase  sequence  sen-

sor  device  is  used  to  protect  devices 

powered  from  a  three-phase  installa-

tion  (e.g.  a  motor)  from  being  damage 

in  case  of  phase  voltage  switch  off.  It 

is  because  of  phase  voltage  asym-

metry  or  wrong  phase  sequence.  The 

threshold  value  switch  on  is  preset  to 

185 V and it can not be regulated by the 

user. The  system  does  not  protect  from 

voltage drop asymmetry and it is powered 

from L1 phase. The switch off delay and 

voltage hysteresis cause the system is re-

sistant to momentary voltage changes.

Zakład Mechaniki i Elektroniki 

ZAMEL 

sp.j.

J.W. Dzida, K. Łodzińska

ul. Zielona 27, 43-200 Pszczyna, Poland

Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04

www.zamel.pl, 

e-mail:

 [email protected]

The device is designed 

for three-phase installa-

tion and must be instal-

led  in  accordance  with 

standards valid in a par-

ticular  country. The  de-

vice should be connec-

ted  according  to  the  details  included  in 

this  operating manual. Installation, con-

nection and control should be carried out 

by a qualified electrician staff, who act in 

accordance with  the service manual and 

the device functions. Before  installation 

make  sure  the  connection  cables  are 

not  under  voltage.  The  cruciform  head 

screwdriver  3,5  mm  should  be  used  to 

instal the device. Improper transport, sto-

rage, and use of the device influence its 

wrong functioning. It is not advisable to 

instal the device in the following cases: if 

any device part is missing or the device 

is damaged or deformed. In case of  im-

proper functioning of the device contact  

the producer. 

CAUTION

brown

b

lack

bl

u

e

gre

y

brown

blue

RELAY

CABLES

Power supply cable / 

measure (L1)

Power supply cable (N)

Measure cable (L3)

Measure cable (L2)