FEATURES

TECHNICAL PARAMETERS

DESCRIPTION

APPEARANCE

ASM-02

Input (supply) terminals: L, N

Input rated voltage: 230 V~

Input voltage tolerance: from -15 to +10 %

Nominal frequency: 50 / 60 Hz

Rated  power consumption: 35 mA

Release terminals: IN, IN, IN 

Release  control current: 300 µA

Time adjustment range: from 2 sec to 10 min (rotational potentiometer)

Time accuracy adjustment: ±10 %

Time repeatability adjustment: ±5 %

Power/relay supply indicator: red LED

Output relay parameters: 1NO - 16 A / 250 V AC1 4000 VA

Number of  terminal clamps: 8

Section of connecting cables: from 0,2 to 2,50 mm

2

Ambient temperature range: from -20 to +45 

o

C

Operating position: free

Mounting: TH35 rail (PN-EN 60715)

Protection degree: IP20 (PN-EN 60529)

Protective class: II

Overvoltage category: II

Pollution degree: 2

Rated impulse withstand voltage: 1 kV (PN-EN 61000-4-5)

Dimensions (height / width / depth): monomodular (17,5 mm) 90x17,5x66 mm

Weight: 76 g

Reference standards: PN-EN 60669-1; PN-EN 60669-2-1

PN-EN 61000-4-2,3,4,5,6,11

●  Staircase lighting control,

●  operating time adjustment from 2 sec 

to 10 min,

●  power supply indicator – red LED,

●  cooperation  with  monostable  push-

buttons  equipped  with  illumination 

lamps,

● 

anti blocking function,

●  cooperation with 4-wire installation,

●  voltage relay output - one NO contact 

max 16 A capacity,

●  monomodular casing,

●  TH 35 DIN rail installation.

The  staircase  lighting  time  delay 

switch ASM-02 is used to control lighting 

devices on staircases and corridors. After 

releasing  the  system  it  switches  on  the 

lighting  for  the  preset  time  by  the  user. 

After  that  it  switches  off  automatically. 

The operating time can be adjusted from 

2 s to 10 min by means of  the potentio-

meter  placed  on    the  front  panel  of  the 

device. The  device  is  equipped  with  an 

anti-blocking  function.  The  staircase  li-

ghting time delay switch ASM-02 can be 

used as standard time delay relay.

The device is designed 

for  one-phase  instal-

lation  and  must  be  in-

stalled  in  accordance 

with  standards  valid 

in  a  particular  country. 

The  device  should  be 

connected  according  to  the  details  inc-

luded in this operating manual. Installa-

tion,  connection  and  control  should  be 

carried out by a qualified electrician staff, 

who  act  in  accordance  with  the  service 

manual and the device functions. Disas-

sembling  of  the  device  is  equal  with  a 

loss of guarantee and can cause electric 

shock. Before installation make sure the 

connection cables are not under voltage. 

The cruciform head screwdriver 3,5 mm 

should be used to instal the device. Im-

proper transport, storage, and use of the 

device  influence  its  wrong  functioning. 

It is not advisable to instal the device in 

the following cases: if any device part is 

missing or the device is damaged or de-

formed. In case of  improper functioning 

of the device contact  the producer.

CAUTION

Output (load) relay 

Time adjustment

Power/relay supply indicator

Input supply terminal (L)

Input supply terminal (N)

terminals  (11,11,14)

Release  terminals   

(IN,IN,IN)

Отзывы: