Introduction 

The TS2-C is a 2kW timer and part of a family of controllers designed to provide energy 
saving  when  used  with  Quartz  Infrared  Halogen  Lamps  or  other  Heating  and  Lighting 
Products.  The  ‘T’  model  switches  the  lamps  on  for  a  pre-determined  time  period  of 
between 5 and 60 seconds.    
The  microcontroller-based  unit  incorporates  zero-voltage  switching  and  a  soft-start 
function to eliminate the lamps’ initial high inrush current – potentially increasing lamp 
life by as much as 30%. Installation of the unit is simple and once installed is relatively 
maintenance-free. 
 

Applications:

 

patio  areas,  smoking  shelters,  restaurants,  warehouses,  workshops  and  garden 
lighting. 

 
Installation 
Important

: Read carefully the following information before installing the unit. 

The TS2-C should be fixed securely using the four mounting holes accessible from the 
front of the unit. Remove the lid to access the mounting holes.  

IMPORTANT! The unit must be orientated with the cable glands facing down. 
 
Wiring 

It  is  recommended  that  installation  and  maintenance  of  this  equipment  should  be 
done with reference to the current edition of the I.E.E. wiring regulations (BS7671) by 
suitably  qualified/trained  personnel.  These  regulations  contain  important 
requirements  regarding  safety  of  electrical  equipment  (for  International  Standards 
refer to I.E.C/ directive IEC950). 

Warning! Isolate the mains supply before commencing any work on this unit. Ensure 
all earth wires are connected to maintain earth continuity to the lamp fittings.  

The  unit  is  fitted  with  two  cable  glands.  Only  one  cable should be fitted per gland to 
prevent degrading the unit’s IP rating. When fitting two lamps it is recommended that 
a junction box is used. 
The  mains  supply  connects  to  the  terminal  block  marked  ‘

LINE

’.  Connect  the  supply 

LIVE

 to the ‘

L

’ terminal, 

NEUTRAL

 to the ‘

N

’ terminal and 

EARTH

 to the ‘

E

’ terminal. 

The lamps connect to the terminal block marked ‘

LOAD

’. Connect the load 

LIVE

 to the 

L

’ terminal, 

NEUTRAL

 to the ‘

N

’ terminal and 

EARTH

 to the ‘

E

’ terminal. If two lamps 

are to be fitted they must be wired in parallel.Check all wiring and make sure the cable 
glands are tightened. 

   

Mounting Template 

   
 
 

 

 

Technical Specification

 

   Supply Voltage   

 

 

 

/- 10%  

Supply Frequency 

 

 

 

50 Hz 

Switching Capacity 

 

 

 

2kW Max. 

Lamp On-Time    

 

 

 

5 to 60 seconds 

Current Consumption (control circuit) 

 

50mA 

Terminals 

 

 

 

 

2.5mm

2

 Rising Clamp 

Operating Temperature   

 

 

-20 to 40°C 

Protection Rating 

 

 

 

IP55 

Gland Diameter  

 

 

 

Max Cable Entry 2.5mm² 

Fixings  4 x 3.5Ø holes    

 

 

97 x 82mm centres 

 

   

  Not for general waste                                  

 

 

 

   

IMPORTANT! 

Drilling of any holes through the enclosure 
will immediately invalidate the warranty of 
the unit. The unit MUST be orientated with 
the cable glands facing down. 