CONNECTION
FUNCTIONIG
WARRANTY CARD
There is a 24-month guarantee on the product
Salesman stamp and signature, date of sale
MOUNTING
1. Disconnect power supply by the phase
fuse, the circuit-breaker or the switch-
-disconnector combined to the proper
circuit.
2. Check if there is no voltage on connec-
tion cables by means of a special me-
asure equipment.
3. Mount the APM-20 device on the TH35
rail.
4. Connect the cables with the terminals in
accordance with the installing diagram.
5. Switch on the power supply from the
mains.
6. Check if the device operates correctly.
1. ZAMEL Sp. z o.o. assures a 24-month guarantee for the product.
2. The manufacturer’s guarantee does not cover any of the following actions:
a) mechanical damage during transport, loading / unloading or under other circumstances,
b) damage caused by incorrect product mounting or misuse,
c) damage caused by unauthorised modifications made by the PURCHASER or any third parties to the product or any other
devices required for the product functioning,
d) damage caused by Act of God or any other incidents independent of the manufacturer – ZAMEL Sp z o.o.
e) supply sources (batteries) included in the device during selling (if they are included).
3. The PURCHASER shall lay any claims in writing in the place of purchase or to ZAMEL Sp. z o.o.
4. ZAMEL Sp. z o.o. is liable for processing any claim according to current Polish legislation.
5. ZAMEL Sp. z o.o. shall process the claim at its own discretion: product repair, replacement or money return.
6. The manufacturer’s guarantee is valid in the Republic of Poland.
7. The PURCHASER’s statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or
otherwise are not affected by this warranty.
The device is designed for single-pha-
se installation and must be installed
in accordance with standards valid in
a particular country. Installation, con-
nection and control should be carried
out by a qualified electrician staff, who
act in accordance with the instruction
manual and the device functions. In
case of casing dismantling, the guaran-
tee is lost and an electric shock may
occur. Before installation make sure
the connection cables are not under
voltage. The cruciform head screwdri-
ver 3,5 mm should be used to install
the device. Improper transport, stora-
ge, and use of the device influence its
wrong functioning. It is not advisable
to install the device in the following
cases: if any device part is missing
or the device is damaged or defor-
med. In case of improper functioning
of the device contact the producer.
CAUTION
CASING DIMENSIONS
After power supply is applied, the device is ready to operate. If the voltage on the L1 phase
is higher than 180 V AC, then the receiver is supplied from another phase. If the voltage on
the L1 drops below 180 V AC, then there is an automatic switch to the L2 phase in <150
ms. Analogically, if the L2 phase voltage drops below 180 V AC, then there is an automatic
switch to the L3 phase. In case the L3 phase voltage is below 180 V AC, there is a power
supply switch off for the receiver connected to this output. If the given phase is switched off
due to a voltage drop of <180 V AC, then it is switched on again at a value of >190 V AC
(hysteresis 10 V). The L1 is the priority phase. In case its parameters are correct, then this
phase will supply the receiver. For example, if a receiver is supplied by the L3 phase and, at
the same time, the L1 has correct parameters again, then an automatic switch to the L1 pha-
se supply will occur. If the voltage on a particular phase is >180 V AC, the appropriate LED
switches on. This LED switches off if voltage drops below 180 V AC. The phase switching
on and switching off times are the same and equals about 150 ms.
Operation – time diagram:
Internal connection arrangement – PK1, PK2, PK3 relays:
L1
L2
L3
N
L2
L3
OUT
OUT
OFF
OUT
OFF
L1
PK1
PK2
PK3
L1
L2
L2
L3
L3
L1
180 V AC
180 V AC
180 V AC
180 V AC
190 V AC
190 V AC
190 V AC
150 ms