
YZ Systems, Inc. • 3101 Pollok Drive • Conroe, Texas • USA • 77303 • P: 936.788.5593 • F: 936.788.5720
Page 91
NJEX 7300L ver.09042003
SSSSS
ECTION
ECTION
ECTION
ECTION
ECTION
13:
13:
13:
13:
13: 7300L S
7300L S
7300L S
7300L S
7300L S
Y
YY
Y
YSTEM
STEM
STEM
STEM
STEM
TTTTT
R
RR
R
ROUBLESHOO
OUBLESHOO
OUBLESHOO
OUBLESHOO
OUBLESHOOTING
TING
TING
TING
TING
Technical Services.
Verometer Expansion Tank
High
Alarm Troubleshooting Steps
When an active XTank High alarm is indicated the
following steps should be taken:
1. Verify that the expansion tank pressure is at 25 psi
(1.72 Bar) and correct if necessary.
2. Inspect the alarm set point programmed into the N-
300 controller and verify that it is correclty pro-
grammed and correct if necessary,
parameters section on programming the N-300
controller Section 5, page 29 or Section 6, page 35
depending on the mode of operation.
3. Observe if the alarm is still active, if it is, contact YZ
Technical Services.
Verometer Overfill Non-Alarm Indicator
Troubleshooting Steps
When an active Overfill non-alarm is indicated the
following steps should be taken:
IMPOR
MPOR
MPOR
MPOR
MPORTTTTTANT NO
ANT NO
ANT NO
ANT NO
ANT NOTE:
TE:
TE:
TE:
TE:
Prior to troubleshooting an overfill indicator verify that the
Verometer is not in a full level position as the fill valve
commands can not be processed if the Verometer is full.
1. Empty the Verometer by performing a forward purge.
2. After returning all pressures and valves to their
normal operating position. Observe the Verometer
level for 5 -10 minutes and note if a change in the
Verometer level occurs without operator influence.
If level in the Verometer does increases without
operator influence,
proceed to the Fill Valve Trouble-
shooting section of this manual on page 89.
level in the Verometer does not increase then
otherwise proceed to the next step below.
3. Initiate a Verometer fill and record the time required
to fill to 100%, and note the level. If the Verometer
fills in a time faster than 30 seconds, partially close
the volume throttling valve between the odorant
storage tank and the NJEX System. This should
slow the fill rate. Repeate step 3 until the NJEX
System fills in over 30 seconds, and the fill valve
turns off between 100 - 108% of fill volume.
Verometer Fill Rate Non-Alarm Indicator
Troubleshooting Steps
When an active Fillrate non-alarm is indicated the
following steps should be taken:
1. Verify the correct set pints on the following pressures.
a. Expansion Tank set at 25 psi (1.72 Bar)
b. Bulk Tank set at 30 - 36 psi (2.07-2.41 Bar)
c. System Supply set at 75 psi (5.17 Bar)
2. Empty the Verometer by performing a forward purge.
Re-establish the pressures and valves to their normal
operating position, and then proceed to step 3.
3. Perform the Verometer fill procedure as indicated in
System Maintenance, Section 12, page 78,
adjust fill rate control valve V9 to achieve a apporiate
fill rate.
Pump Alarm Troubleshooting
There are three pump alarms monitored by the N-300
Controller to ensure correct and safe operation of the
NJEX System. The alarms relating to the pump perfor-
mance and their description is as follows:
• Over Pump alarm will indicate if the actual pump
displacement exceeds the programed pump displace-
ment value by 30%.
• Under Pump alarm will indicate when the actual
pump displacement ranges from 30 - 75% of the
programed pump displacement value.
• Pump Failure alarm will indicate when the actual
pump displacement is less than 25% of the pro-
Содержание NJEX 7300L
Страница 1: ...NJEX 7300L L P G O D O R I Z A T I O N S Y S T E M...
Страница 2: ......
Страница 3: ...THE NJEX 7300L INSTRUCTION OPERATING MANUAL Version NJEX7300L 10012003...
Страница 4: ......