FLUE SYSTEM REQUIREMENTS FIG. E 

 

More than 3000

3000

or less

6

0

0

 m

in

.

3000

1000 min. if clear

within 3000 of
flue top

.

3000

Any nearby

structure

.

1000 min. if clear

within 3000 of
flue top

MINIMUM HEIGHT OF FLUE SYSTEM EXIT

NOTE : Dimensions are in millimetres

3000

or less

6

0

0

 m

in

.

More than 3000

3000

.

Increase from
1000 min. until

clear within
3000 of flue top

 

IMPORTANT INFORMATION 

 

A. 

THE APPLIANCE AND FLUE SYSTEM SHALL BE INSTALLED IN COMPLIANCE WITH AS/NZS 
2918:2001 AND THE APPROPRIATE REQUIREMENTS OF THE RELEVANT BUILDING CODE OR 
CODES. 

 
B. 

APPLIANCES INSTALLED IN ACCORDANCE WITH THIS STANDARD SHALL COMPLY WITH THE 
REQUIREMENTS OF AS/NZS 4013 WHERE REQUIRED BY THE REGULATORY AUTHORITY I.E. THE 
APPLIANCE SHALL BE IDENTIFIABLE BY A COMPLIANCE PLATE WITH THE MARKING “TESTED TO 
AS/NZS 4013” 

 
C. 

ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN WRITING BY THE 
TESTING AUTHORITY IS CONSIDERED TO BE IN BREACH OF THE APPROVAL GRANTED FOR 
COMPLIANCE WITH AS/NZS 4013 

 
D. 

MIXING OF APPLIANCE OR FLUE SYSTEM COMPONENTS FROM DIFFERENT SOURCES OR 
MODIFYING THE DIMENSIONAL SPECIFICATION OF COMPONENTS MAY RESULT IN HAZARDOUS 
CONDITIONS. WHERE SUCH ACTION IS CONSIDERED, THE MANUFACTURER SHOULD BE 
CONSULTED IN THE FIRST INSTANCE. 

 
E. 

CRACKED AND BROKEN COMPONENTS E.G. GLASS PANELS OR FIRE BRICKS, MAY RENDER THE 
INSTALLATION UNSAFE. 

 
IF A WATERBOOSTER IS FITTED: 

NOTE: A WATER BOOSTER CANNOT BE FITTED TO THE FITZROY (SUB 1.0) CLEAN AIR MODEL 

 

A. DO NOT CONNECT TO AN UNVENTED HOT WATER SYSTEM  
B. INSTALL IN ACCORDANCE WITH AS 3500.4.1 OR NZS 4603 AND THE APPROPRIATE 

REQUIREMENTS OF THE RELEVANT BUILDING CODES. 

 

SEISMIC RESTRAINT

   

Secure the heater base to the hearth or sub-framing with dynabolts or similar through the holes provided. 
Follow 

local Council’s Specifications.

 

Содержание fitzroy

Страница 1: ...walls Tested to AS NZS 2918 2001 by APPLIED RESEARCH SERVICES Clearance Rear Clearance from rear of top lip with YUNCA flue mounted shield fitted N B clearance from rear panel is 120mm 100 mm Side Clearance with YUNCA flue mounted shield fitted 300 mm Corner Clearance with YUNCA flue mounted shield fitted 130 mm F YUNCA Flue Kit Tested to AS NZS 2918 2001 Appendix F Fig A B E 1 4 2m x 150mm stainl...

Страница 2: ... FLUES Refer Fig E 1 The FLUE shall extend to Not less than 600mm above the highest point on the roof if within 3 0m of that point or Not less than 1000mm above the intersection point with the roof and not lower than any point of the roof within 3 0m In any case the length of the flue shall not be less than 4 6m from the ash floor protector In some situations the Local Council may vary the above r...

Страница 3: ...FLUE MOUNTED SHIELD FITTED Measurements in millimetres A B E F G H 100 300 130 320 620 501 FIG D MINIMUM FLOOR PROTECTION MEASUREMENTS WITH YUNCA FLUE MOUNTED SHIELD FITTED Measurements in millimetres C D J K L M N O P 300 100 840 880 1274 1150 560 640 580 Above Non combustible wall clearances Brick lining from floor to within 25mm of ceiling Leave air vents at the bottom to allow airflow in the c...

Страница 4: ...THE MARKING TESTED TO AS NZS 4013 C ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN WRITING BY THE TESTING AUTHORITY IS CONSIDERED TO BE IN BREACH OF THE APPROVAL GRANTED FOR COMPLIANCE WITH AS NZS 4013 D MIXING OF APPLIANCE OR FLUE SYSTEM COMPONENTS FROM DIFFERENT SOURCES OR MODIFYING THE DIMENSIONAL SPECIFICATION OF COMPONENTS MAY RESULT IN HAZARDOUS CONDITIONS WHERE SUCH ACTION ...

Отзывы: