55
440 01 2020 01
THIS DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
Circulation Air Blower Data - *9MPV
Heating, Cooling & Continuous Airflow Settings
Continuous Blower (CFM) @ 0.10
²²²²
Static
Switch Settings
Furnace Model
#1
#2
50K
75K
100K
125K
0*
0*
540
540
700
703
0
1
660
660
860
821
1
0
780
780
1020
1000
1
1
900
900
1180
1160
*Factory Setting
Hi Heat Air Temperature Adjustment (
°°°°
F)**
Switch Settings
Furnace Model
#3
#4
#5
50K
75K
100K
125K
0**
0**
0**
0
0
0
0
0
0
1
3
2
3
2
0
1
0
6
4
5
6
0
1
1
14
6
9
11
1
0
0
17
11
13
13
1
0
1
--8
--4
--4
--5
1
1
0
--13
--4
--7
--5
1
1
1
--17
--4
--9
--5
*Factory setting
**Approximate air temperature change from factory setting @ 0.20
²
static on high heat ).
Lo Heat Air Temperature Adjustment (
°°°°
F)**
Switch Settings
Furnace Model
#3
#4
#5
50K
75K
100K
125K
0**
0**
0**
0
0
0
0
0
0
1
1
1
1
6
0
1
0
4
2
2
8
0
1
1
7
3
5
12
1
0
0
11
6
8
16
1
0
1
--7
--4
--5
--1
1
1
0
--11
--6
--9
--4
1
1
1
--15
--9
--11
--7
*Factory setting
**Approximate air temperature change from factory setting @ 0.20
²
static on high heat ).
Cooling (CFM) @ 0.50
²²²²
Static
Switch Settings
Furnace Model
#6
#7
#8
50K
75K
100K
125K
0*
0*
0*
1170
1395
2095
2059
0
0
1
1098
1197
1875
1859
0
1
0
991
1096
1642
1700
0
1
1
894
1000
1489
1621
1
0
0
807
907
1255
1410
1
0
1
697
799
1013
1191
1
1
0
621
650
830
986
1
1
1
556
543
750
800
*Factory setting
*EXAMPLE
Cooling Airflows Switches
6, 7 & 8:
000 3.5 Ton
001 3.0 Ton
010 2.5 Ton
011 2.0 Ton
*See “Technical Support
Manual” for correct airflow
rates.
0 1 0
Blower Motor Settings
INPUT
SIGNAL OR
THERMOSTAT
CONNECTIONS