6

 

B=1; Change all of the low alarm to be low deviation alarm; when deviation 

value (PV – SV) < L.ALx, it will trigger the alarm. When (PV – SV) > L.ALx – 

HYSx,  alarm  off,  set  the  L.ALx  value  to  minimum  will  disable  the  alarm 

function. 

nonc   

NO/NC 

selection 

Single  channel  relay  module  provides  both  normal  open  and  normal  close 

output, while dual relay output module L5 only provides normal open output. 

However, by parameter “nonc”, the NO output can be changed to NC output. 

nonc = 0, AL1, AL2 (L5 is installed in ALM socket) are normal open output. 

nonc = 127, AL1 and AL2 are normal close output

0, 127 

Loc   

Parameter lock 

Loc=0, Allow to display and modify parameter “Loc” and the field parameters 

which is defined in EP1~EP12 . 

Loc=1,  Allow  to  display  and  modify  parameter  “Loc”,  and  only  display  field 

parameters, can’t modify them. 

Loc=808, allow to display and set all parameters. 

Note:  This  setting  just  effect  on  external  display.  Modify  parameter  by 

communication was always allowed. 

0 ~9999 

EP1-12   

Field 

parameter 

When configuration of the instrument is completed, most parameters will not 

need  to  be  set  by  field  operators.  Furthermore,  field  operators  may  not 

understand many parameters, and may probably set parameters incorrectly 

by mistake and make the instrument unable to work.   

EP1~EP12  define  0~12  field  parameters  for  operators’  use  in  parameter 

table. Their parameter values are parameters except parameter EP itself, for 

example, H.AL1, L.AL1, .etc,   

Parameters from EP1 to EP12 can define 12 field parameters at most, if the 

number  of  field  parameters  is  less  than  12(sometimes  even  none),  it  is 

necessary  to  define  field  parameters  from  EP1  to  EP12  in  order,  the  first 

unused EP should be set to none.   

For  example,  four  parameters  of  SP1  to  SP4  (all  channels’  setpoints)  are 

need to be modified by field operators, the parameter EP can be set as : 

EP1=SP1, EP2=SP2, EP3=SP3, EP4=SP4, EP5=none, Loc=0   

Then  only  parameter  SP1~4  can  be  displayed  and  modified,  but  via 

communication, on the host computer, all parameters can be displayed and 

modified. 

NonE~bAud 

Содержание AI-7048

Страница 1: ...AI 7048 ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER Operation Instruction Ver 7 5 Dimension D5...

Страница 2: ...other AI series instruments One AI 7048 communicates with the host computer the same as four independent controllers Universal power supply of 100 240VAC or 24VDC New generation D5 E5 rail mounted di...

Страница 3: ...dry contact alarm output Terminal 1 and 2 Power supply of 100 240VAC 50Hz or 24VAC DC Terminal 9 12 The positive poles of thermocouple inputs of channel 1 4 Terminal 15 and 16 The common Negative pole...

Страница 4: ...ify a parameter Setpoints SV can be set by pressing or Press key to decrease the value Press key to increase the value Press key to move to the digit expected to modify Keep pressing or the speed of d...

Страница 5: ...strument in the same communication line should be assigned to different communication address The communication applies AIBUS protocol Every input channel takes one address For example if channel numb...

Страница 6: ...eleases when PVx H ALx HYSx 999 3200 L ALx Alarm low limit x channel low alarm is triggered when PVx L ALx alarm releases when PVx L ALx HYSx HYSx Hysteresis HYS is set to avoid high frequent alarm on...

Страница 7: ...rameter by communication was always allowed 0 9999 EP1 12 Field parameter When configuration of the instrument is completed most parameters will not need to be set by field operators Furthermore field...

Отзывы: