1. Introduction

This is a single phase meter with communication RS485 and RF. Protocol for RS485 is DTL645.
Meter with inside relay support for connect and disconnect functions.

2. Features and Technical Parameters

2.1 Features

●LCD display show voltage, current, power, and kWh.

●Measuring total energy consumption, support both active and reactive energy measurement.

●Meter with inside relay 80A which support on and off function through communication program

●Meter support both RF and RS485 communication, protocol for RS485 is DTL645, protocol for

RF is self defined.

RS485 communication:

baud rate 9600 (fixed), eight data bits, even parity check, one stop bit

RF communication:

baud rate 9600 (fixed), eight data bits, without parity check, one stop bit

●RF only used for communication with IHD (in home display)

●address for in home display and meter should corresponding and same

●It can received meter returned data when press ”SEND” on IHD

IHD will ask meter every 1 minute for get data in case of with power supply

2.2 Technical Parameters

Voltage:

230V

Current:

10(80) A

Impulse constant:

1600imp/kWh

Display:

LCD 6+2

Operating temperature

-20—45

Storage temperature

-25—70

relative humidity

≤75%

Frequency

50Hz

Accuracy class

1.0 s

Starting current

0.4%Ib(1.0s)

Power consumption

Voltage circuit Un

<2W / <10VA @ Un

Current circuit In

<2.5 VA @ (Ib)

Содержание D119014

Страница 1: ......

Страница 2: ...ned RS485 communication baud rate 9600 fixed eight data bits even parity check one stop bit RF communication baud rate 9600 fixed eight data bits without parity check one stop bit RF only used for com...

Страница 3: ...2 3 Description A relay status B Impulse indication C Turn Page Button Material Case ABS PC Hook ABS material A B C...

Страница 4: ...e LCD screen LCD display for present total kWh press button can be used to turn to different pages totally 4 pages Page 1 active power 000000 00 kWh page 2 voltage 000 0 V page 3 current 00 00 A page...

Страница 5: ...4 6 Meter Dimensions Height 100mm Width 76mm Depth 65mm Weight 0 3174kg Net 7 Software Connect the meter correctly with power according to connection diagram includes RS485 wire then power on...

Страница 6: ...5 7 1 RS485 communication 7 1 1 Open the software see following interface 7 1 2 Choose the serial port baud rate and open the serial port see following interface...

Страница 7: ...ss Factory Default 000000000000 and choose the object which need to be operated then click send data as following 7 1 4 When use broadcast address operate meter needs press button on the meter 7 1 5 T...

Страница 8: ...d by yourself fixed them in the location which are waiting for installation Push down the clip under the bottom of the meter for a gear see fig 1 Fig 1 Put the meter into the Din rail as per Fig 2 the...

Страница 9: ...8 Fig 4 is after installation Fig 4 Making the connection according to the wiring diagram see Fig 5 Fig 5...

Страница 10: ...9 After connection use lead sealing to seal terminal cover see Fig 6 Fig 6...

Страница 11: ...3 10 80 55 75 55 7 1 76 16 105 80 100 75 7 2 12 25 140 105 130 100 7 2 50 35 170 140 160 125 19 1 83 50 225 170 205 150 19 2 14 75 280 225 255 185 19 2 50 95 340 280 320 240 Note BX BLX copper aluminu...

Страница 12: ...d personnel Installation and operation of this equipment described in this manual may only be performed by qualified personal Only people that are authorized to install connect and use this equipment...

Страница 13: ...If in doubt don t use the equipment and contact technical staff Mounting of electric appliances must be carried out only by skilled electricians It is imperative to observe the generally applicable sa...

Отзывы: