SMART POSITIONER
TMP-3000
PRODUCT MANUAL
Ver. 1.03
31
6.8.7
Custom End Setting Mode (CST ENd)
CST ENd is the value of analog input signal corresponding to the end point of Set Value
for Split Range Control and is the percentage value of analog input signal (4 ~ 20mA, 0
~ 20mA, 0 ~ 5V, 0 ~ 10V) which can be set by the user. For example, if the analog input
signal is selected (4 to 20mA) and CST ZERO is set to 0% and CST END is set to 50%, the
valve opening will be 0 to 100% when the input signal is in the 4 to 12mA range.
The deviation of the current between the zero point and the end point should be at
least 25%.
6.8.8
Single and Double Acting Adjustment (SINGLE / dOUBLE)
You can change the single and double acting settings of the actuator.
<ENTER>
<DOWN>
5 times
<ENTER>
<UP>/<DOWN>
<ENTER>
<ESC>
3 times
<ENTER>
<DOWN>
6 times
<ENTER>
<UP>/<DOWN>
<ENTER>
<ESC>
3 times