www.yoshitake.jp
13
-7
13
T
emperatur
e Regulator
Temperature Regulator
Step
2
Nominal Size Selection for Temperature Regulator
Calculation formula for Cv value
(1) For
steam
When
P
2
> P
1
2 Cv =
Wk
138 ΔP(P
1
+ P
2
)
When
P
2
P
1
2 Cv =
Wk
120P
1
(2) For
liquid
Cv = 0.365V
G
ΔP
W : Max. flow rate of steam [kg/h]
P
1
: Inlet pressure [MPa ∙ A]
P
2
: Outlet pressure [MPa ∙ A]
ΔP : P
1
- P
2
[MPa]
k : 1 + 0.0013 x {superheated steam temperature [˚C]
– saturated steam temperature [˚C]}
G : Specific gravity (against water in the case of fluid)
V : Max. flow rate of fluid [m
3
/h]
Cv : Cv value of each nominal size
Cv value table
Nominal size
Model
15A
20A
25A
32A
40A
50A
65A
80A
100A
125A
150A
OB-30, 31
0.8
1
1.2
−
−
−
−
−
−
−
−
OB-2000
5.0
7.2
10.9
14.3
18.8
32
54
70
108
−
−
OB-1, 1G
2
2
4
7
10
−
−
−
−
−
−
OB-2, 2G
2
2
4
7
10
14
21
27
42
72
94
OB-3, 3G
2
2
4
7
10
−
−
−
−
−
−
OB-4, 4G
2
2
4
7
10
14
21
27
42
72
94
OB-5
1
1
2
−
−
−
−
−
−
−
−
OB-6
1
1
2
−
−
−
−
−
−
−
−
Point to remember when selecting the size
∙ If system has small capacity and seat leakage become a problem, select single valve type such as OB-30 Series, OB-5 or OB-6.
∙ Differential pressure between inlet and outlet of temperature regulator should be 0.05 MPa in principle. It is recommended that inlet
pressure be 0.2-0.3 MPa to obtain the best performance of the temperature regulator and its longer product life.