YO Refrigerant Monitor
User guide
v1.2
page 27/29
Payload description
If you want to connect to your own server, it is necessary to decode the specific payload for each
device. To accomplish this, a payload decoder is required, which can be downloaded using the
following link:
. Extended documentation of the protocol can be found in the
on our website. An example payload produced by YO Refrigerant is presented below with
divisions for each measurement and marked with decoded values, whose interpretation is described
in the
Example of YO Refrigerant Monitor payload with description:
02:00:00:00:08:00:01:11:a6:0d:00:01:01:07:10:00:00:33:16:00:11:6d:00:13:0d:00:11:6d:01:10
Payload header
First measurement (battery voltage)
0x02
0x00
0x00
0x00
0x08
0x00
0x01
0x11
0xA6
ver = 2
cnt = 0
pct [s] = 0
type = 2
prec = 0
md [s] = 0
addr_len = 0
meas_len = 2
val = 4518
(4518[mV])
Second measurement (temperature)
0x0D
0x00
0x01
0x01
0x07
type = 3
prec = 1
md [s] = 0
addr_len = 0
meas_len = 2
val = 263
(26,3 [°C])
Third measurement (relative humidity)
0x10
0x00
0x00
0x33
type = 4
prec = 0
md [s] = 0
addr_len = 0
meas_len = 1
val = 51
(51[%])
Fourth measurement (pressure)
0x16
0x00
0x11
0x6D
0x00
0x13
type = 5
prec = 2
md [s] = 0
addr_len =1,
meas_len = 2
addr=109
val=19
(0,19 [bar])
Fifth measurement (temperature)
0x0D
0x00
0x11
0x6D
0x01
0x10
type = 3
prec = 1
md [s] = 0
addr_len = 1
meas_len = 2
addr=109
val = 272
(27,2[°C])