Installation
Installation safety information
Read the following instructions before you install this appliance.
This is an outdoor combination heating and cooling unit. The
installer must assure that these instructions are made available
to the consumer. The installer must instruct the consumer to
retain the instructions for future reference.
• Refer to the unit rating plate for the approved type of gas
for this product.
• Install this unit only in a location and position as specified
on Page 9 of these instructions.
• Never test for gas leaks with an open flame. Use
commercially available soap solution made specifically for
the detection of leaks when you check all connections.
See Pages 5, 37, 37 and 67 of these instructions.
• Always install the furnace to operate within the furnace's
intended temperature-rise range with the duct system and
within the allowable external static pressure range. This
information is specified on the unit name/rating plate and
specified on Page 68 of these instructions.
• This equipment is not to be used for the temporary
heating of buildings or structures under construction.
It is permitted to use the unit for heating and cooling of buildings
or structures under construction where the application and use
must comply with all manufacturer's installation instructions
including the following:
• Proper installation of vent outlet air and combustion air
intake hoods.
• The unit must be operated under thermostatic control.
• Return and supply air ducts must be sealed to the unit.
• Air filters in place;
• The unit furnace input rate and temperature rise must be
set according to the rating plate marking.
• The return air temperature must be maintained between
55ºF (13ºC) and 80ºF (27ºC).
• When the construction phase is completed and before
formal start up and commissioning, the unit, duct work
and components must be thoroughly cleaned and
inspected. This is to ensure that the operation of the unit
during construction did not contaminate the unit.
Note:
If the unit is used during the construction phase, the
standard limited warranty provisions go into effect when
the unit is placed into operation.
Preceding installation
1.
Remove the two screws that hold the brackets in the front,
rear, and compressor side fork-lift slots. See Figure 1
t
Figure 1: Unit shipping bracket
2.
Turn each bracket toward the ground. The protective
plywood covering drops to the ground.
3.
Remove the toolless doorknobs and instruction packet, see
Figure 3.
Figure 2: Barometric relief hood - shipping location
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could result
in serious injury, death, or property damage.
Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections. A fire
or explosion may result causing property damage,
personal injury, or loss of life.
Item
Description
A
Bracket screws
B
Bracket
A
B
Barometric relief hood in
shipping location (if included)