518676-BIM-C-0610
38
Johnson Controls Unitary Products
Figure 28: Honeywell Economizer Control W7212
Phasing
ZS units are properly phased at the factory. Check for proper
compressor rotation. If the blower or compressors rotate in the
wrong direction at start-up, the electrical connection to the unit
is misphased. Change the phasing of the
Field Line
Connection at the factory or field supplied disconnect
to
obtain proper rotation. (Scroll compressors operate in only one
direction. If the scroll is drawing low amperage, has similar
suction and discharge pressures, or producing a high noise
level, the scroll is misphased.)
Blower Rotation
Check for proper supply air blower rotation. If the blower is
rotating backwards, the line voltage at the unit point of power
connection is misphased (See ‘PHASING’).
Belt Tension
The tension on the belt should be adjusted as shown in Figure 29.
Figure 29: Belt Adjustment
N1
N
P1
P
EXH
Set
EXH
Min
Pos
IAQ
Max
IAQ
IAQ
Min
Free
Cool
T
T1
AQ1
AQ
SO+
SO
SR+
SR
A
B
C
D
TR
TR1
24
Vac
HOT
24
Vac
COM
EF
EF1
2
3
4
5
1
+
Exhaust Air
Adjustment
Screw
Exhaust Air LED
Damper Min.
Position
Screw
Indoor Air Quality
Max. Adjustment
Screw
Indoor Air Quality
LED
Indoor Air Quality
Min. Adjustment
Screw
Free Cooling LED
Economizer Enthalpy
Set Point Adjustment
Screw
Scroll compressors require proper rotation to operate
correctly. Units are properly phased at the factory. Do
not change the internal wiring to make the blower
condenser fans, or compressor rotate correctly.
Table 13: Supply Air Limitations
Unit Size (Ton)
Minimum
Maximum
-06 (6.5)
1950
3250
-07 (7.5)
2250
3750
-08 (8.5)
2550
4250
-10 (10)
3000
5000
-12 (12.5)
3750
6250
A
A
A
B
SPAN LENGTH
DEFL. FORCE
C*
* NEVER LOOSEN