York ZKT06 Скачать руководство пользователя страница 39

5121835-TIM-J-1118

Johnson Controls Ducted Systems

39

Phasing

ZK units are properly phased at the factory. Check for proper 
compressor rotation. If the blower or compressors rotate in the 
wrong direction at start-up, the electrical connection to the unit 
is misphased. Change the phasing of the field line connection at 
the factory or field supplied disconnect to obtain proper rotation. 
Scroll compressors operate in only one direction. The scroll is 
misphased if it is drawing low amperage, has similar suction 
and discharge pressures, or it produces a high noise level.

Blower rotation

Check for proper supply air blower rotation. If the blower is 
rotating backwards, the line voltage at the unit point of power 
connection is misphased. See 

Phasing on page 45

.

Adjusting the belt tension

To adjust the belt tension complete the following steps.

1.

Loosen the six belts nuts at the top and bottom. See Figure 
28

Note: 

Never loosen the static nut at the top of the adjustment 
bolt.

2.

Turn the adjustment bolt.

3.

Use a belt tension checker to apply a perpendicular force 
to one belt at the midpoint of the span shown in Figure 28. 
A deflection distance of 4 mm (5/32 in.) is obtained.

4.

To determine the deflection distance from normal position, 
use a straight edge from sheave to sheave as a reference 
line. 

The recommended deflection force is as follows:

Tension new belts at the max. deflection force 
recommended for the belt section. 

5.

Re-tighten the belt nuts.

Figure 28: Belt adjustment

CFM static pressure and power-altitude and temperature 
corrections

Use the information below to assist in the application of the 
product at altitudes at or exceeding 1000 feet above sea level.

The air flow rates listed in the standard blower performance 
tables are based on standard air at sea level. As the altitude or 
temperature increases, the density of air decreases. In order to 
use the indoor blower tables for high altitude applications, 
certain corrections are necessary.

A centrifugal fan is a constant volume device. This means that, 
if the RPM remains constant, the CFM delivered is the same 
regardless of the density of the air. However, since the air at 
high altitude is less dense, less static pressure is generated and 
less power is required than a similar application at sea level. Air 
density correction factors are shown in Table 17 and Figure 29.

Scroll compressors require proper rotation to operate 
correctly. Units are properly phased at the factory. Do 
not change the internal wiring to make the blower 
condenser fans, or compressor rotate correctly.

Table 16: Supply air limitations

Unit size (ton)

Minimum

Maximum

T06 (6.5)

1950

3250

T07 (7.5)

2250

3750

T08 (8.5)

2550

4250

T10 (10)

3000

5000

T12 (12.5)

3750

6250

Item

Component

A

Belt nuts

B

Adjustment bolt

C

Static nut

Check the belt tension at least two times during the first 
24 hours of operation. Any retensioning must fall 
between the min. and max. deflection force values.

A

A

A

B

SPAN LENGTH

DEFL. FORCE

C*

* NEVER LOOSEN

Table 17: Altitude/temperature correction factors

Air temp.

Altitude (Ft.)

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

Содержание ZKT06

Страница 1: ...ide duct application 42 20 Airflow performance bottom duct application 44 21 RPM selection 45 22 Indoor blower specifications 46 23 Power exhaust specifications 46 24 Motor sheave datum diameters 48 2...

Страница 2: ...precautions and codes including ANSI Z223 1 or CSA B149 1 latest edition Wear safety glasses and work gloves Use quenching cloth and have a fire extinguisher available during brazing operations Impro...

Страница 3: ...nd may be installed directly on combustible flooring or in the U S on wood flooring or Class A Class B or Class C roof covering materials For use with natural gas The unit can be converted to LP with...

Страница 4: ...hrowaway Filters 2 2 Pleated Filters Merv 8 3 2 Cleanable Filters 4 4 Pleated Filters Merv 13 A None C BACnet MSTP Modbus N2 COM Card F Fault Detection and Diagnostics FDD E Verasys Single Zone G Vera...

Страница 5: ...ure 1 Unit shipping bracket 2 Turn each bracket toward the ground The protective plywood covering drops to the ground 3 Remove the condenser coil protective covering 4 Remove the toolless doorknobs an...

Страница 6: ...ate If components are added to a unit to meet local codes they are installed at the dealer s and or customer s expense The size of the unit for the proposed installation must be based on a heat loss h...

Страница 7: ...Filter access 2 in or 4 in filter options O Compressor 1 access high efficiency compressor E Filter drier solid core P Side entry power and control knockouts F Micro channel aluminum tube aluminum fin...

Страница 8: ...nd proper unit operation Rigging and handling Exercise care when you move the unit Do not remove any packaging until the unit is near the place of installation To rig the unit attach chain or cable sl...

Страница 9: ...g cables so that it lifts evenly All panels must be secured in place when the unit is lifted The condenser coils must be protected from rigging cable damage with plywood or other suitable material D A...

Страница 10: ...t2 110 110 1 Weight given is for the maximum heater size available 54KW 2 Weight given is for the maximum number of tube heat exchangers available 8 tube LEFT A 59 00 C D E F 4 19 27 31 89 00 21 19 11...

Страница 11: ...3 16 5 1 4 Base Pan 17 13 16 View of Wall Across from Coil Gas Pipe Inlet 5 3 8 Table 6 ZKT06 through T12 unit clearances Direction Distance in Direction Distance in Top1 1 Units must be installed out...

Страница 12: ...Figure 12 ZKT06 through T10 unit side duct openings Item Description A Disconnect switch cover B Power entry 2 1 2 C Control entry 7 8 D Power entry 2 1 2 E Convenience outlet cover F Convenience out...

Страница 13: ...Unit model number Dimension in A B C D ZKT06 27 3 4 12 1 16 27 1 2 16 ZKT07 27 3 4 12 1 16 27 1 2 16 ZKT08 28 1 4 18 1 16 28 1 4 18 1 4 ZKT10 28 1 4 18 1 16 28 1 4 18 1 4 ZKT12 28 1 4 18 1 16 28 1 4 1...

Страница 14: ...of curb 8 or 14 50 1 2 30 20 20 80 5 8 6 A B E G D F C Roof curb components Item Description A Return air B Supply air C Right side of the unit D Front side of the unit E 2 typ F Insulated deck under...

Страница 15: ...he following steps 1 Remove the side duct covers 2 Orient the supply panel with the painted surface up 3 Slide the supply panel between the heat exchanger and the unit bottom The painted surface must...

Страница 16: ...ere POE polyolester compressor lubricants are known to cause long term damage to some synthetic roofing materials Procedures that risk oil leakage include but are not limited to the following Compress...

Страница 17: ...of a disconnect on the unit Confirm compliance with local code before you install a disconnect on the unit Electrical line must be sized properly to carry the load Note Use copper conductors only Each...

Страница 18: ...g unit with or without electric heat Figure 23 Typical field wiring disconnect cooling unit with gas heat THREE PHASE POWER SUPPLY FACTORY OR FIELD SUPPLIED DISCONNECT GROUND LUG TERMINAL BLOCK TB1 L1...

Страница 19: ...ostat to indicate the Occupied on X is an input to the thermostat to display Error Status condi ons 3 W2 Y1 G OCC Y2 X R SD 24 C W1 24V COM OUT Return or Space Humidity Sensor 0 10VDC TB4 3 823 R RAH...

Страница 20: ...50 E09 6 8 1 18 9 38 9 44 4 50 50 E18 13 5 2 37 5 53 3 60 2 60 70 E24 18 0 2 50 0 69 0 75 8 70 80 E36 25 5 2 70 8 95 0 101 9 100 110 230 13 1 83 1 20 5 2 1 5 2 5 5 0 0 None 38 9 44 4 50 50 E09 9 0 1...

Страница 21: ...90 90 E24 18 0 2 50 0 74 5 81 3 90 90 E36 25 5 2 70 8 100 5 107 4 110 110 E54 40 6 2 112 7 152 9 159 7 175 175 230 22 4 149 0 35 0 2 1 9 6 5 5 0 0 None 68 4 73 9 90 90 E18 18 0 2 43 3 68 4 73 9 90 90...

Страница 22: ...18 9 43 3 48 8 50 60 E18 13 5 2 37 5 58 8 65 7 60 70 E24 18 0 2 50 0 74 5 81 3 80 90 E36 25 5 2 70 8 100 5 107 4 110 110 230 13 1 83 1 20 5 2 1 9 6 5 5 0 0 None 43 3 48 8 50 60 E09 9 0 1 21 7 43 3 48...

Страница 23: ...0 100 E24 18 0 2 50 0 80 0 86 8 90 100 E36 25 5 2 70 8 106 0 112 9 110 125 E54 40 6 2 112 7 158 4 165 2 175 175 230 22 4 149 0 35 0 2 1 14 0 5 5 0 0 None 72 8 78 3 90 100 E18 18 0 2 43 3 72 8 78 5 90...

Страница 24: ...9 48 9 54 4 60 60 E18 13 5 2 37 5 65 8 72 7 70 80 E24 18 0 2 50 0 81 5 88 3 90 90 E36 25 5 2 70 8 107 5 114 4 110 125 230 13 1 83 1 20 5 2 1 5 2 5 5 10 0 None 48 9 54 4 60 60 E09 9 0 1 21 7 48 9 54 4...

Страница 25: ...9 100 100 E24 18 0 2 50 0 87 0 93 8 100 100 E36 25 5 2 70 8 113 0 119 9 125 125 E54 40 6 2 112 7 165 4 172 2 175 175 230 22 4 149 0 35 0 2 1 9 6 5 5 10 0 None 78 4 83 9 100 100 E18 18 0 2 43 3 78 6 85...

Страница 26: ...8 9 53 3 58 8 60 70 E18 13 5 2 37 5 71 3 78 2 80 80 E24 18 0 2 50 0 87 0 93 8 90 100 E36 25 5 2 70 8 113 0 119 9 125 125 230 13 1 83 1 20 5 2 1 9 6 5 5 10 0 None 53 3 58 8 60 70 E09 9 0 1 21 7 53 3 58...

Страница 27: ...100 110 E24 18 0 2 50 0 92 5 99 3 100 110 E36 25 5 2 70 8 118 5 125 4 125 150 E54 40 6 2 112 7 170 9 177 7 175 200 230 22 4 149 0 35 0 2 1 14 0 5 5 10 0 None 82 8 88 3 100 110 E18 18 0 2 43 3 84 1 91...

Страница 28: ...44 192 AFUE Steady state efficiency 80 80 80 80 80 80 80 80 80 80 No burners 4 6 4 6 4 6 6 8 6 8 No stages 24 24 24 24 24 24 24 24 24 24 Temperature rise range F 20 50 35 65 15 45 30 60 10 40 25 55 20...

Страница 29: ...er sheave AK74 AK64 AK74 AK61 AK89 AK74 AK84 AK74 AK74 BK77 Belt A49 A49 A49 A49 A56 A54 A56 A54 A54 BX55 Motor HP each 1 1 2 2 1 1 2 3 2 3 2 3 3 5 RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 172...

Страница 30: ...uperseded by local codes or gas utility requirements See Table 14 Gas pipe sizing capacity of pipe on page 31 The heating value of the gas may vary by locality You must check the value with the local...

Страница 31: ...d scale Hammer on the outside of the pipe and blow out loose particles Before initial start up make sure that all gas lines external to the unit are purged of air The gas supply must be a separate lin...

Страница 32: ...compartment with the heating elements extending into the supply air chamber All electric heaters are fused and intended for use with single point power supply Motorized outdoor damper The motorized ou...

Страница 33: ...nts should be set to the same value Free cooling Four types of free cooling options are available dry bulb changeover single enthalpy dual enthalpy changeover and Auto Dry bulb changeover For dry bulb...

Страница 34: ...f cooling If the economizer output goes to minimum position and the SAT is less than Economizer setpoint 1 F the control starts a 12 minute timer to de energize a compressor output If at any time the...

Страница 35: ...cts through circuit trace to 24V IN pin HOT C COM Mixed air temperature sensor input from 10K 77 F Type III negative temperature coefficient thermistor The MAT parameter reports input status F C 3 65...

Страница 36: ...tation sensor MOA Range parameter sets the cubic feet per minute liters per second measured by the air monitoring station sensor when it outputs 10 VDC Fr Air parameter reports input status 0 50000CFM...

Страница 37: ...o the 4 stage board and or fault detection diagnostics board 1 When wiring the unit and other devices using the SA Bus and FC Bus see Table 32 Smart Equipment economizer board analog outputs Location...

Страница 38: ...economizer actuator Connects through circuit trace to 24V IN pin COM EX FAN 24 VAC hot output to energize power exhaust fan contactor coil VFD enable relay coil ExFan parameter reports output status O...

Страница 39: ...elt nuts Figure 28 Belt adjustment CFM static pressure and power altitude and temperature corrections Use the information below to assist in the application of the product at altitudes at or exceeding...

Страница 40: ...is assumed The 1 5 in static pressure given is at an elevation of 5 000 ft The first step is to convert this static pressure to equivalent sea level conditions Sea level static pressure 1 5 832 1 80...

Страница 41: ...95 BHP exceeds the maximum continuous BHP rating of the 1 5 HP motor The 2 HP motor is required 6 1268 RPM is within the range of the 2 HP drives 7 Using the 2 HP motor and drive 5 turns open will ach...

Страница 42: ...94 1 43 1147 1 56 1201 1 67 1254 1 78 1309 1 90 1366 2 02 2600 902 0 97 962 1 16 1020 1 33 1076 1 47 1130 1 61 1183 1 73 1237 1 85 1291 1 96 1346 2 07 1402 2 19 2800 941 1 16 1002 1 35 1059 1 52 1115...

Страница 43: ...1 1 Blower performance includes gas heat exchangers and 2 in filters See the static resistance table for additional applications 2 See the RPM selection table to determine the required motor sheave se...

Страница 44: ...1347 1 84 1424 1 98 1503 2 14 1586 2 31 2600 957 1 10 1030 1 30 1102 1 47 1174 1 62 1246 1 76 1320 1 89 1394 2 03 1471 2 17 1551 2 33 1634 2 51 2800 1009 1 32 1082 1 51 1154 1 69 1225 1 84 1298 1 98...

Страница 45: ...HP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP and field supplied drive Standard 3 HP and drive High static 5 HP and drive 3200 837 1 44 889 1 57 940 1 69 989 1 81 1036 1 93 1...

Страница 46: ...r 10 12 hours run time Method two 1 Drill two 5 16 inch holes one in the return air duct as close to the inlet of the unit as possible and another in the supply air duct as close to the outlet of the...

Страница 47: ...are presented for side and bottom duct configuration 6 Determine the unit measured CFM from the blower performance table external static pressure and the number of turns the variable motor sheave is o...

Страница 48: ...review the installation for any installation errors leaks or undesirable systems effects that can result in loss of airflow Even small changes in blower speed can result in substantial changes in stat...

Страница 49: ...0 17 0 18 0 21 0 22 0 26 3900 0 09 0 29 0 23 0 19 0 20 0 23 0 24 0 28 4100 0 09 0 31 0 24 0 21 0 22 0 25 0 26 0 31 4300 0 10 0 30 0 25 0 23 0 24 0 28 0 29 0 34 4500 0 11 0 35 0 26 0 25 0 26 0 30 0 31...

Страница 50: ...ressor 1 is energized If compressor 1 is active for first stage cooling or the first compressor is locked out compressor 2 is energized In free cooling mode if the call for the second stage of cooling...

Страница 51: ...ressure switch opens for greater than 5 seconds the UCB de energizes the associated compressor initiates the ASCD and if the other compressor is idle stops the condenser fans If the call for cooling i...

Страница 52: ...n within the Smart Equipment Controller menu Those modes consist of a Normal Alternate and Aux each mode is described below Normal cooling mode When there is a call for first stage cooling with or wit...

Страница 53: ...is a call for cooling and the economizer is operating as first stage of cooling All safety devices function as previously described Optional Aux mode The Aux mode available with hot gas reheat units i...

Страница 54: ...ce Reducing the value below the correct setpoint gives shorter ON cycles and may result in the lowering of the temperature within the conditioned space See Table 28 for the required electric heat anti...

Страница 55: ...Flame sense Flame sensing occurs at all times If W1 is not present and a flame is sensed for 2 seconds the draft motor is energized and the GV is kept off The ICB halts any operation until a flame is...

Страница 56: ...e thermostat setting lower than the conditioned space temperature This resets any flash codes Gas heat anticipator setpoints The anticipator setpoint must be correct Too high of a setting results in l...

Страница 57: ...is unit has two stages of gas heat The first stage is 60 of the full fire input and is considered the minimum input for the furnace The intended input for each furnace is shown in Table 32 The table a...

Страница 58: ...just the second stage 100 input pressure first then adjust first stage 60 input pressure 1 Turn off electrical power to the unit 2 Using the outlet pressure port on the gas valve connect a manometer t...

Страница 59: ...e Figure 33 Typical flame Figure 34 Typical gas valve Charging the unit All ZK units use thermal expansion devices Charge the unit to nameplate charge Navigation components for the Smart Equipment con...

Страница 60: ...e also effective for economizer free cooling supply air temperature reset when the ClgStgs parameter is set for 1 or more G Continuous indoor blower request 24 VAC input switched from R OCC Occupancy...

Страница 61: ...erminate temporary occupancy COM Common for ST and SSO inputs Negative of VDC circuit for ST and SSO inputs SSO Space Sensor Offset input from 0 to 20K potentiometer Positive of VDC circuit 3 625 VDC...

Страница 62: ...hot return from Air Proving Switch When this optional input is enabled the air proving switch must close within 30 seconds of initiation of indoor blower operation and not open for greater than 10 se...

Страница 63: ...ntilation cooling reheat or heat pump heating demands C2 24 VAC hot output for compressor 2 Not effective for one stage compressor UCBs If demand is present and permissions allow compressor 2 operatio...

Страница 64: ...f the 15 VDC reading to C circuit for powering an optional netstat and or Multi Touch gateway C Common for SA BUS power and communication circuits Also incorporated in the J8 6 pin phone jack connecto...

Страница 65: ...than FC bus BACnet MSTP communication circuit FC FC Field Connected BUS BACnet MSTP communication Positive of the VDC typically a fluctuating 1 5 to 3 5 volts reading to COM at least 0 25 volts lower...

Страница 66: ...air Cable2 2 We recommend 26 AWG solid 6 wire 3 twisted pairs cable as the best fit for fabricating modular cables with the modular jack housing assembly Be sure the cable you use fits the modular jac...

Страница 67: ...WLDO VWDUW XS 7KLV FRQILGHQFH LV VXSSRUWHG E WKH GD GHDOHU SURWHFWLRQ FRYHUDJH SRUWLRQ RI RXU VWDQGDUG ZDUUDQW SROLF ZKLFK VWDWHV WKDW RKQVRQ RQWUROV XFWHG 6 VWHPV ZLOO FRYHU SDUWV DQG ODERU RQ QHZ HT...

Страница 68: ...LQ WKH IXOO RSHQ SRVLWLRQ DQG WKH IUHTXHQF GULYH LV RSHUDWLQJ DW R QRW SURFHHG ZLWK WKH HTXLSPHQW VWDUW XS ZLWKRXW WKH GHVLJQ 0 LQIRUPDWLRQ HVLJQ 6XSSO LU 0 BBBBBBBBBBBBBBBBBBBBBBBBBB HVLJQ 5HWXUQ LU...

Страница 69: ...RPSOHWH LU 0RYLQJ QVSHFWLRQ RPSOHWHG 6HH 1RWHV OLJQPHQW RI GULYH FRPSRQHQWV HOW WHQVLRQ DGMXVWHG SURSHUO ORZHU SXOOH V WLJKW RQ VKDIW EHDULQJ VHW VFUHZV WLJKW ZKHHO WLJKW WR VKDIW 3UHVVXUH VZLWFK RU W...

Страница 70: ...JH UHTXLUHG WR REWDLQ WKH FRUUHFW DLUIORZ DV LW QHFHVVDU WR LQFUHDVH RI GHFUHDVH WKH DLUIORZ WR PHHW WKH GHVLJQ FRQGLWLRQV I WKH PRWRU SXOOH VL H ZDV FKDQJHG PHDVXUH WKH RXWVLGH GLDPHWHUV RI WKH PRWRU...

Страница 71: ...BB 5 5HWXUQ LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 0L HG LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 6XSSO LU 7HPSHUDWXUH BBBBBBBBBBBBB...

Страница 72: ...BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB...

Отзывы: