5742637-YIM-D-0620
24
Johnson Controls Ducted Systems
060
(5.0)
208-1-60
4
24.4 144.2
38
4.4
6.7
10
NONE
-
-
-
51.6
70
E05
4
1
19.2
51.6
70
E07
5.6
1
26.9
54.5
70
E10
8
1
38.5
69
70
E15
11.9
2
57.2
92.4
100
E20
15.9
2
76.4
116.4
125
E30
22.2
2
106.7
154.3
175
230-1-60
4
24.4 144.2
38
4.4
6.7
10
NONE
-
-
-
51.6
70
E05
5.3
1
22.1
51.6
70
E07
7.5
1
31.2
59.9
70
E10
10.6
1
44.2
76.1
80
E15
15.9
2
66.2
103.7
110
E20
21.2
2
88.3
131.3
150
E30
29.6
2
123.3
175
200
208-3-60
16
110
24.9
4.4
4.3
10
NONE
-
-
-
38.7
50
E05
4
1
11.1
38.7
50
E07
5.6
1
15.5
38.7
50
E10
8
1
22.2
45.6
50
E15
11.9
2
33
59.2
60
E20
15.9
2
44.1
73
80
E30
22.2
2
61.6
94.9
100
230-3-60
16
110
24.9
4.4
4.3
10
NONE
-
-
-
38.7
50
E05
5.3
1
12.7
38.7
50
E07
7.5
1
18
40.4
50
E10
10.6
1
25.5
49.7
50
E15
15.9
2
38.2
65.7
70
E20
21.2
2
51
81.6
90
E30
29.6
2
71.2
106.9
110
460-3-60
7.8
52
12.1
4.4
2.1
5
NONE
-
-
-
19
25
E07
6.8
1
8.2
19.1
25
E10
10.1
1
12.1
24.1
25
E15
13.6
2
16.4
29.3
30
E20
19.5
2
23.5
38.2
40
E30
28.8
2
34.6
52.2
60
575-3-60
5.7
38.9
8.9
4.4
1.9
4
NONE
-
-
-
14.8
15
E10
10.6
1
10.2
20.1
25
E15
15.9
2
15.3
26.5
30
E20
21.2
2
20.4
32.9
35
E30
30.4
2
29.3
43.9
45
072
(6)
208-3-60
19.6
136
27
4.4
4.3
20
None
-
-
-
43.2
60
E05
4
1
11.1
43.2
60
E07
5.6
1
15.5
43.2
60
E10
8
1
22.2
45.6
60
E15
11.9
1
33
59.1
60
E20
15.9
2
44.1
73
80
E30
22.2
2
61.6
94.9
100
230-3-60
19.6
136
27
4.4
4.3
20
None
-
-
-
43.2
60
E05
5.3
1
12.7
43.2
60
E07
7.5
1
18
43.2
60
E10
10.6
1
25.5
49.8
60
E15
15.9
1
38.2
65.6
70
E20
21.2
2
51
81.6
90
E30
29.6
2
71.2
106.9
110
460-3-60
9.4
66.1
13
2.4
2.1
20
None
-
-
-
21.3
30
E07
6.8
1
8.2
21.3
30
E10
10.1
1
12.1
24
30
E15
13.6
1
16.4
29.4
30
E20
19.5
2
23.5
38.3
40
E30
28.8
2
34.6
52.1
60
575-3-60
7.1
55.3
10
4.4
1.9
20
None
-
-
-
16.6
20
E10
10.6
1
10.2
20.1
25
E15
15.9
1
15.3
26.5
30
E20
21.2
2
20.4
32.9
35
E30
30.4
2
29.3
44
45
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Electrical data for single phase gas heating units with belt drive is at the end of the electrical data section.
ZE036-072 - With Powered Convenience Outlet (Belt Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Accessory
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages Amps