78
7.4.2.11 P4 (Temperature protection of compressor discharge) diagnosis and solution.
Error Code
P4
Malfunction conditions
When the compressor discharge temperature(T5) is more
than 115
℃
for 10 seconds, the compressor will stop
and
restart till T5 is less than 90
℃
.
Potential causes
●
Refrigerant leakage
●
Wiring mistake
●
Faulty discharge temperature sensor
●
Faulty outdoor PCB
Trouble shooting:
Temperature protection of
compressor discharge
Check whether the
compressor discharge temp. is
more than 115°C ?
Check
whether
the
connection is right between
compressor discharge temp.
sensor and PCB according
to wiring diagrams?
Measure the resistance value
of compressor discharge
temp. sensor. If the value is
not normal
is normal refer to
the
Appendix
2?
No
Yes
Yes
No
Correct the wiring connection
Stop leaking and add refrigerant
Replace the compressor discharge temp. sensor
No
Yes
Replace high pressure valve assy
Yes
No
Replace outdoor main PCB
No
Check whether the
refrigerant is leak
Содержание YU2E18YJ6AMHO-Y
Страница 3: ...3 YU4E36YJ6AMHO Y WD30 metal plate 110 YU5E48YJ6AMHO Y WE30 metal plate 117...
Страница 23: ...23 6 Wiring Diagrams 6 1 Wiring diagram of 1 drive 2 outdoor YU2E18YJ6AMHO Y...
Страница 24: ...24 6 2 Wiring diagram of 1 drive 3 outdoor YU3E27YJ6AMHO Y...
Страница 25: ...25 6 3 Wiring diagram of 1 drive 4 outdoor YU4E36YJ6AMHO Y...
Страница 26: ...26 6 4 Wiring diagram of 1 drive 5 outdoor YU5E48YJ6AMHO Y...
Страница 37: ...37 Operating Standby Pic 2 IPM for 2 zone 3 zone...
Страница 38: ...38 PIC3 Main board LED when power on and unit standby Pic 2 IPM for5 zone Power Standby Operating...
Страница 44: ...44...
Страница 45: ...45 7 4 1 7 Over voltage or under voltage protection diagnosis and solution...
Страница 48: ...48 7 4 1 11 High temperature protection of IPM board diagnosis and solution...
Страница 51: ...51...
Страница 53: ...53 Operating Standby Pic 2 IPM board for 2 zone 3 zone...
Страница 54: ...54 PIC3 Main board LED when power on and unit standby Pic 2 IPM for5 zone Power Standby Operating...
Страница 55: ...55 PIC 4 Check point button press 1 time for check how many indoor units are connected...
Страница 60: ...60 IPM board for 2 zone 3 zone...
Страница 62: ...62 IPM board for 4 zone...
Страница 65: ...65 Two ports of the inductance Inductance...
Страница 68: ...68 Vs Vcc Vsp FG...
Страница 70: ...70...
Страница 71: ...71...
Страница 73: ...73...
Страница 74: ...74...
Страница 76: ...76...
Страница 77: ...77...
Страница 90: ...90 6 EXV check Disconnect the connectors...
Страница 91: ...91 Resistance to EXV coil Color of lead wire Normal Value Red Blue About 50 Red Yellow Brown Orange Brown White...
Страница 92: ...92 Red Blue Red Yellow...
Страница 93: ...93 Brown Orange...
Страница 94: ...94 Brown White...
Страница 104: ...104 Screws of right rear panel Screws of terminal board...