APPENDIX 2 - FACTORY RUN TEST PROCEDURE

Each unit undergoes a final QA check before the unit 

is shipped from the factory. This final check includes 

a complete operational test that verifies the operation 

of all of the systems and installed options on the unit. 

This Run Test is built into and performed by the unit 

controller (IPU). This mode can also be used in the 

field to verify operation at start-up.
The unit will arrive in the field with all the ordered 

options already configured. As part of start-up you 

may need to change set points and turn features ON or 

OFF based on the desires of the customer. Once con-

figured, the FACTORY RUN TEST mode can be used 

to verify operation. The controller will begin with the 

first applicable test in the order indicated in the table 

below. The controller will prompt you with a question 

“Initiate Test”. Indicate Yes by pressing the accept key 

(check key) or move to a different test on the list by 

pressing the up or down arrow keys. Pressing the can-

cel key will leave the RUN TEST mode.
For each test, the controller will indicate the test name 

and the state of the test. For the state of the test, the 

following information will be displayed:

•  NO TEST – This message indicates that the test 

shown has never been performed.

•  UNDERWAY – This message indicates the test 

shown has started.

•  PASS – This message indicates the test shown 

was completed successfully. When started in the 

field all the items should show PASS.

•  FAIL – this message indicates the test shown has 

ended and was not successful.

APPENDIX 2 - FACTORY RUN TEST PROCEDURE

To start the test, turn the UNIT rocker switch to the 

OFF position. Press the SERVICE key and enter pass-

word 9725. 

See Section 6 of the IOM for information 

on how to enter the PASSWORD.

Use the down arrow key 

to scroll down to FACTO-

RY RUN TEST. Press the check key (√ ) and use the 

right arrow key 

to change from USER DISABLED 

to USER ENABLED. Press the check key (√ ). The 

following test sequences will appear:

HIGH POST TEST

The first test that appears is HIGH POST TEST. Use 

the down arrow key to go to the next test.

SUPPLY FAN TEST

During this test sequence, the supply fan 

blower will operate at 42 hertz. Make sure 

this speed will not result in a static pres-

sure which could damage the building 

supply duct system.

To initiate the test press the check key (√ ). The control 

will ask you ARE YOU SURE? Press the check key 

(√ ) again. Once underway, the controller will perform 

the following sequence:

1.  Start the Supply Fan and set the Supply Fan VFD 

output to 50%.

2.  Wait 30 Seconds.
3.  Stop the Supply Fan.

Prompt Message #1

SPEED CORRECT? When the supply fan is running 

the supply fan VFD should indicate approximately 42 

Hertz. Press the check key if the speed is correct.

TABLE 1 - 

FACTORY RUN TEST PROCEDURE

RUN TEST 

ORDER

TEST DESCRIPTION

CRITERIA NECESSARY FOR TEST TO BE RUN

1

High Potential Test

All Units (FACTORY ONLY)

2

Supply Fan Test

All Units

3

Compressor System A

All Units

4

Compressor System B

All Units

5

Compressor System C

Unit Size => 39 Ton

6

Compressor System D

Unit Size => 39 Ton

7

Compressor System E

Unit Size => 100 Ton

8

Compressor System F

Unit Size => 100Ton

9

Analog Output Operation Test

All Units

10

Stage Electric Heat Test

Units with HEAT TYPE set to ELECTRIC

Содержание YSWU 10

Страница 1: ...R COOLED SELF CONTAINED YSWU 10 105 TON INDOOR DOWNFLOW WATER COOLED SELF CONTAINED YSWD 10 105 TON WITH IPU2 CONTROL Issue Date June 01 2011 INDOOR PACKAGED AIR CONDITIONING UNITS QUICK START UP GUIDE NEW RELEASE Form 145 05 SU3 611 ...

Страница 2: ...is individual will also be familiar with and com ply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in this document to alert the reader to areas of potential hazard CAUTION identifies a hazard which could lead to damage to the machine damage to other equipment and or envi ronmental pollution Usually an in...

Страница 3: ...ED SUPPLY AIR TEMPERATURE RESET COOLING 11 OUTDOOR AIR TEMPERATURE RESET COOLING 12 RETURN AIR TEMPERATURE RESET COOLING 13 SUPPLY FAN SPEED TEMPERATURE RESET COOLING 14 VAV HEATING 15 SECTION 5 FLEXSYS UNITS 17 FLEXSYS COOLING 17 FLEXSYS HEATING 18 CONDENSER WATER CONTROL 18 SECTON 6 OPTIONS 19 ECONOMIZER 19 VENTILATION 19 SUPPLY AIR TEMPERING 19 MORNING WARM UP 19 ADAPTIVE MORNING WARM UP 20 EME...

Страница 4: ...d by contacting the nearest Johnson Con trols Service office NOMENCLATURE BASE MODEL NUMBER 1 2 3 4 U Upflow W Water Cooled S Self Contained Y YORK D Downflow for FlexSys 5 0 6 3 7 9 Base Product Type Nominal Tonnage It is the responsibility of operating service personnel to verify the applicability of these documents to the equipment in question If there is any question in the mind of operating s...

Страница 5: ...re return air temperature or supply fan speed or FlexSys SECTION 1 INTRODUCTION Refer to applicable section for required field wiring miscellaneous connections and programming References to Programming indicates the setpoints that should be programmed verified under the respec tive key on the User Interface keypad SETPOINT PROGRAM OPTIONS DATE TIME and SCHED ULE keys Unit options should be program...

Страница 6: ...JOHNSON CONTROLS 6 FORM 145 05 RP3 611 ISSUE DATE 6 01 2011 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 7: ...osition The unit will then be switched to ON based on the OCCUPIED schedule programmed in the User Interface Field Wiring None required Programming PROGRAM KEY Unit Data Subsection CLOCK SCHEDULE USER ENABLED ON OFF COMMUNICATED To turn the unit ON turn the ON AUTO OFF toggle switch located below the User Interface from the OFF to AUTO position The unit will then be switched to ON based on a commu...

Страница 8: ...JOHNSON CONTROLS 8 FORM 145 05 RP3 611 ISSUE DATE 6 01 2011 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 9: ...NT 60 0 950 F Program Key Unit Data Subsection CONTROL METHOD WIRED ZONE TEMP Date Time Key Enter Correct Date and Time SECTION 3 CONSTANT VOLUME UNITS ZONE SENSOR CONTROL HEATING Field Wiring Connect zone sensor wiring to terminals 13 and 14 of terminal block CTB1 located inside the control panel see Appendix 1 CTB1 for zone sensor connections Miscellaneous Connections No additional connections r...

Страница 10: ... Program key Unit Data Subsection CONTROL METHOD COMM ZONE TEMP Date Time Key Enter Correct Date and Time COMMUNICATED ZONE TEMP HEATING Field Wiring Hardwire BAS system to Primary Unit Controller Miscellaneous Connections No additional connections required Programming Options Key Heating Subsection HEATING SYS TYPE NONE ELECTRIC HOT WATER STEAM ELEC HEAT CAPACITY 41 KW 17 KW 34 KW 68 KW Setpoints...

Страница 11: ...in tons from the listed choices REFRIGERANT TYPE Select R22 407C or R410A COMP STAGING SEQ For units with four stages of cooling select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED...

Страница 12: ...ng select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED if the optional SF VFD Bypass is installed DUCT PRESS SENSOR 2 Should be set to IN STALLED if an optional 2nd duct static tra...

Страница 13: ...ing select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED if the optional SF VFD Bypass is installed DUCT PRESS SENSOR 2 Should be set to IN STALLED if an optional 2nd duct static tr...

Страница 14: ... of cooling select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED if the optional SF VFD Bypass is installed DUCT PRESS SENSOR 2 Should be set to IN STALLED if an optional 2nd duct s...

Страница 15: ...ensor tubing to the selected duct location A field supplied static pressure probe and tubing must be installed in the field prior to unit start up Refer to the unit IOM Form 145 05 NOM3 for details on how to install the static pressure probe and tubing Programming Options Key Heating Subsection HEATING SYS TYPE NONE ELECTRIC HOT WATER STEAM ELEC HEAT CAPACITY 11 KW 17 KW 34 KW 68 KW Setpoints Key ...

Страница 16: ...JOHNSON CONTROLS 16 FORM 145 05 RP3 611 ISSUE DATE 6 01 2011 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 17: ... of cooling select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED if the optional SF VFD Bypass is installed DUCT PRESS SENSOR 2 Should be set to IN STALLED if an optional 2nd duct s...

Страница 18: ...robe and tubing Programming Options Key Heating Subsection HEATING SYS TYPE NONE ELECTRIC HOT WATER STEAM ELEC HEAT CAPACITY 11 KW 17 KW 34 KW 68 KW Setpoints Key Heating Subsection HEATING SAT 80 0 115 00 F UNOCC ZONE HEATING SETPOINT 45 0 99 00 F HEAT LIMITTEMPERATURE 100 0 150 00 F RAT HEATING SETPOINT 550 F RAT COOLING SETPOINT 2 00 F Program Key Heating Subsection HEATING SYSTEM USER ENABLED ...

Страница 19: ...STANDARD Setpoints Key Ventilation Subsection OA Damper Minimum Position 0 100 OA Damper Maximum Position OA Damper Minimum Position 100 Program Key Ventilation Subsection VENTILATION SYSTEM USER ENABLED Only used on Constant Volume Units COMFORT VENTILATION USER EN ABLED USER DISABLED Only used on Constant Volume Units SUPPLY AIR TEMPERING Field Wiring No additional connections required Miscellan...

Страница 20: ...r to identify when an alarm is present connect the external device to terminals 15 and 16 of the TB1 terminal block Miscellaneous Connections No additional connections required Programming No programming is required PUMP OUTPUT Field Wiring The Primary Unit Controller has the ability to close three sets of dry contacts which can be used to ener gize the condenser water control pump To use this fea...

Страница 21: ...TPOINTS PROGRAM or OPTIONS key will take the user to the Login Prompt When the user is first presented with the Login Prompt the pass word field will be blank If the user wishes to change Level 1 or Level 2 parameters the user must know the appropriate password At that point only the parame ters changeable under the specific password level will be displayed For example if the user presses the OP T...

Страница 22: ...n at the digit to be changed After the desired numeric value has been entered press the key to save the new value and exit the edit mode Press ing the key will fill in the default value Edits will only be accepted when followed by pressing the key Pressing the key while in the edit mode will cancel the edit mode and leave the value unchanged If an out of range value is entered the Default High and...

Страница 23: ...er the COMPRESSOR SYSTEMS key pressing the key will scroll sideways to the Sys 2 Pressures display and pressing the key will scroll sideways to the Sys Pressures display for the last system on the unit When programming numeric or non numeric values the key and the key are used to scroll forward down and backward up through the items to be pro grammed or set FORM 145 05 SU3 611 ISSUE DATE 6 01 2011...

Страница 24: ...own Closed Run Closed Occupied Open Unoccupied Contacts Close When VAV Boxes Should Open 17 18 XX 13 14 15 16 9 10 LD13325A Wiring Notes 1 Wiring shown indicates typical wiring Refer to the IOM for more detailed wiring methods and options 2 All wiring is Class 2 low voltage 3 Maximum power available from the 24VAC terminal is 40 VA 4 Use shielded wire where shown 5 Relay contacts suitable for pilo...

Страница 25: ...test shown has ended and was not successful APPENDIX 2 FACTORY RUN TEST PROCEDURE To start the test turn the UNIT rocker switch to the OFF position Press the SERVICE key and enter pass word 9725 See Section 6 of the IOM for information on how to enter the PASSWORD Use the down arrow key to scroll down to FACTO RY RUN TEST Press the check key and use the right arrow key to change from USER DISABLED...

Страница 26: ...erform the following 1 Set the SUPPLY FAN to ON 2 Set SUPPLY FAN VFD AO to 60 3 Wait 30 Seconds 4 Set COMPRESSOR A to ON 5 Wait 180 seconds 6 Set COMPRESSOR A to OFF 7 Wait 10 seconds 8 PASS will be indicated for this test and all outputs will be turned OFF If at any time during this test the Com pressor System 1 status is not OKAY all outputs will be immediately turned OFF and FAIL will be indica...

Страница 27: ...esent at the HEAT STAGE 1 heater ele ment If operating properly press the check key to accept If contactor and or heater element did not come on determine why and correct the problem If an accept is not received in 60 seconds the screen will indicate FAIL and all outputs will be homed Once accepted perform the following 1 Se t HEAT STAGE 1 output to OFF 2 Set HEAT STAGE 2 output to ON Prompt Messa...