3. Operation Modes and Functions
3.1 Manual Operation
3.1.1 The manual operation mode is controlled through “manual” pad in the wind in-take grid, including such two
modes as manual action and manual cooling. Push the manual pad for each switchover, the order for which
is shown below:
3.1.2 Manual Cooling
3.1.2.1 Under this mode, no remote control signal will be received.
3.1.2.2 The compressor is started up unconditionally and the rotating speed of indoor and outdoor fans is set to be
in high and forced cooling operation.
3.1.2.3 Under this mode, the buzzer will buzz twice with each lasting 0.5 second at 0.5 interval. During the first
30 minutes of unconditional forced cooling operation, the operation indicator will blink at 0.5Hz. In the
process of switchover to manual action mode, the buzzer buzzes for 0.5 second and the indicator is
illuminated.
3.1.2.4 Under this mode, the corresponding protections are in effective (3- minute delayed start-up, over current,
outdoor protection and evaporator low temperature protection.). Corresponding protection will act once any
protection is in active.
Push “manual” pad once to end this mode and enter the remote control pending status. The buzzer will buzz
for 1 second and the indicator turn off.
3.1.3 Manual Action
3.1.3.1 Under this mode, the remote signal will be received and corresponding actions will be taken accordingly
upon the receipt of the remote signal.
3.1.3.2 On entering this mode, the buzzer will buzz for 0.5 second and the indicator on.
3.1.3.3 The system will operate under the auto mode whose temperature is set to be 24°C and at the same time,
the wind grille will swing automatically.
3.1.3.4 Under this mode, corresponding protections are in effective.
3.1.3.5 Push “ manual” pad to end this mode and switch over to manual cooling mode.
REMOTE CONTROL
MANUAL ACTION
MANUAL COOLING
Содержание YKHC 18
Страница 1: ...Cassette YKHC 18 to 48 SERVICE MANUAL YKHC 18 YKHC 24 YKHC 30 YKHC 36 YKHC 48 SM YKHC 18 48GB 03 07...
Страница 24: ...22 Part8 Wiring diagram 1 YKHC 12 18 Indoor unit Outdoor unit...
Страница 25: ...23 2 YKHC 24 Indoor unit Outdoor unit XT1 XT2 RT3 XS1 XP1 KM1 CAP1 FAN COMP CAP2 XT3 VALVE...
Страница 35: ...33 4 Relocate the air in grid in the procedure of reversed order install the air in grid...
Страница 40: ...38...
Страница 45: ...43 Part12 Exploded view Indoor unit 1 YKHC 12 18...
Страница 53: ...www johnsoncontrols com SM YKHC 18 48GB 03 07...